Continuous HVAC Blower Fan Operation for Optimum Indoor Air QualityContinuous blower unit fan operation guide:
This article explains how and why to set your air conditioning or heating system blower fan to continuous operation in order to improve indoor air quality by increased and continuous indoor air filtration.
We also describe use of the manual FAN-ON switch present on some fan limit controls (or thermostats) and we discuss how to add an inexpensive manual FAN ON/OFF switch to an existing fan limit controller.
(Naturally if there is an IAQ problem source in the building it is essential to also find and correct that condition. This website answers almost any question you might ask about air filters for heating or air conditioning systems.
InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers, products, or services discussed at this website.
- Daniel Friedman, Publisher/Editor/Author - See WHO ARE WE?
For maximum indoor air qality (IAQ) improvement in buildings: for a new blower installation
we selected a fan unit which had both the capability of delivering adequate CFM of air flow and a blower fan motor duty cycle which
permits continuous operation if we wish to run the system that way.
[Click to enlarge any image]
...
Running the blower continuously at low speed resulted in continual air scrubbing in the building. When the heating or cooling needs of the building require, the fan shifts automatically to high speed. Here are the details:
There are reasons to leave the fan in the ON position on a heating or cooling system, but we do not recommend that you do this without first asking for advice from your heating and service technician.
If your air conditioner or heating system fan blower unit was designed to permit the fan to run all of the time that's great and you can consider the benefits of continuous fan operation we list just below.
But if your fan motor was not intended for continuous duty and you run the fan that way, you may find the motor fails prematurely.
A benefit of continuous fan operation is reduction of bioaerosol growth (mold etc.)
An additional benefit of continuous fan operation is reduction of bioaerosol growth (mold etc.)
During cool periods (like overnight), the AC is off and the coil and drain pan warm up. The longer the fan is off, the higher the relative humidity becomes in the air handler, limited only by how much water was in the drain pan.
If there is sufficient humidity, microbes can grow anywhere in the air handler there is even a spec of dust.
Running the fan continuously keeps relative humidity in the equipment to the same, presumably lower, level as found in the rest of the building.
This even helps compensate for a poor installation with an improperly leveled drain pan.
AC disinfectant tablets can also help.
Most people will never notice this problem, but mold sensitive people can start experiencing problems with brand new systems in the first month of operation. If you are using AC to help allergy problems, consider running the fan continuously. On 2011-09-07 by Gil Vice
...
...
Most heating or cooling systems have one or perhaps two methods for turning the blower fan to continuous "on": at the room wall themostat and (for heating systems) at the fan limit switch - a safety control found inside the heating appliance.
If your air handler unit provides both heating and cooling (that is not just air conditioning) then there will be a limit swtich installed inside the air handler blower compartment or burner compartment.
Look for the white push-pull switch such as the one shown in our photo at left. You will see this switch without having to remove the cover from the limit swith itself.
If your limit swith includes this fan switch, try
moving the fan switch from "Auto" to "Fan On". You should hear the blower fan turn on and continue running as long as the switch is in this position.
To find the manual furnace or air handler blower fan switch, see the articles, photos, and sketches in these articles
See the white knob at lower left in our fan limit switch photo just above?
That's the manual fan-on switch on a limit control. As we note, not all limit controls include this switch. The cover has been removed from the switch in this picture.
...
Our reader asked:
Thank you for your website, it has been very helpful as a new homeowner.
I have a Lennox G12Q3-120-1 furnace (ground floor) with only two wires (R, W) run to a Lennox mercury thermostat (second floor) for heat only.
I would like to add a manual fan control to use the furnace can to circulate air in the hot summer months.
It is not feasible for me to run a new wire to the thermostat so I was thinking of adding a switch at the furnace itself.
[Click to enlarge any image]
Looking online, I found that people jumped the R and G terminals with a switch; however, I discovered that my furnace does not have a terminal strip.
I have a fan control relay and an unused white wire on the 24v side of the relay, which I believe is the fan control wire and would normally be connected to the G terminal on a thermostat if so equipped.
Also, I believe my blower motor has been wired for single speed operation as the red and black leads from it have been connected together, and this is consistent with how the furnace functions.
To manually control the fan, is it possible for me to wire a switch between the blue 24v wire from the transformer to the white fan control wire on the relay?
Here are some photos of the furnace internals:
Please let me know if you need more information.
Thank you for your time and help! - Anonymous by private email 2020/03/22
An EXAMPLE wiring modification to add a manual FAN-ON switch using the Honeywell L4064 Fan Limit controller is shown above - the red wires.
Watch out: this modification is NOT approved nor recommended by the manufacturer (Honeywell) nor by your furnace manufacturer. If you are not trained in proper and safe electrical wiring and HVAC controls, making a mistake can cause equipment damage, a building fire, or electrical shock or injury or death.
IF a fan control wire is available at your thermostat you could have simply replaced your simple thermostat with a model that includes a manual FAN-ON switch.
Our illustration above is also discussed
at FAN ON AUTO MAN THERMOSTAT SWITCH
But you cannot do that as you don't have the necessary control wires..
Similarly, a separate or external switch jumping R and G terminals can, if the R and G wires are connected to the fan control board at the air handler, be used to switch the fan ON and OFF manually.
But that approach will not work either in your case because you report that you have only two wires right at your thermostat: probably R and W that simply turn the furnace ON or OFF in response to room temperature.
Take a look at our articles on the furnace / air handler fan limit control switch starting at FAN LIMIT SWITCH https://inspectapedia.com/heat/Fan_Limit_Switch_Guide.php
Then consider:
Some of those controls have a white pull-push switch that can turn the fan ON to run continuously.
That control is illustrated above and is also discussed in FAN RUNS ONLY ON FAN-ON / MAN
Find the manual and more wiring and installation instructions for your heater (if you don't already have it) at
LENNOX G12 / G12E SERIES FURNACE INSTALLATION MANUAL [PDF] using one of 3 types of fan limit controls: Camstat, Cemco, or Honeywell.
or at
LENNOX HVAC MANUALS & PARTS GUIDES Lennox Industries Air Conditioners, Furnaces, Heat Pumps , Manuals, Guides
At FAN LIMIT SWITCH INSTALLATION & WIRING MANUALS we describe how the control is wired and give links to installation manuals for all of the brands of fan limit controllers found on air handlers.
Finding yours will let you find the wires or connections that you might use to connect up an independent manual FAN-ON switch if your controller doesn't already offer that feature.
(Or you could replace the control with a similar model that already includes the FAN-ON manual switch.
...
...
Continue reading at BLOWER FAN OPERATION & TESTING or select a topic from the closely-related articles below, or see the complete ARTICLE INDEX.
Or see BLOWER FAN CONTINUOUS OPERATION FAQs - questions and answers posted originally on this page
Or see these
BLOWER FAN CONTINUOUS OPERATION at InspectApedia.com - online encyclopedia of building & environmental inspection, testing, diagnosis, repair, & problem prevention advice.
Or see this
Or use the SEARCH BOX found below to Ask a Question or Search InspectApedia
Search the InspectApedia website
Need to make a private comment? Email editor@inspectApedia.com. We welcome email with your website content critique, corrections, suggestions or questions. Email is monitored daily but our workload may prevent an immediate reply. For immediate results, we hope you'll first try asking your question using the search box just above.
In addition to any citations in the article above, a full list is available on request.