Stair, Landing, Railing Code FAQs #3
Stair, railing, guardrail, handrail, landing & platform building code & specification FAQs set 3:
More Q&A on stair and railing code & design specifications & relations to model building codes.
Our page to
This article series lists all major building code specifications for stairs, railings, landings, and guardrails - information useful for constructing or inspecting indoor or outdoor stairs, railings, landings, & treads, and for evaluating stairways and railings for safety and proper construction.
We compare stair and railing code requirements for various model, national, state and local building codes and we include explicit text & specifications from those building codes. Page top sketch of stair dimensions courtesy of Carson Dunlop Associates, a Toronto home inspection, education & report writing tool company [ carsondunlop.com ].
InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers, products, or services discussed at this website.
- Daniel Friedman, Publisher/Editor/Author - See WHO ARE WE?
Set #3 of frequently-asked questions and answers about stair & railing codes & build specifications. These questions and replies were posted originally
at STAIR CODES & STANDARDS the home page for this topic.
[Click to enlarge any image]
We have a back door onto a slab 4" patio. The door's threshold is ~20" above above grade. The slab is continous up to the house. Building a concrete stairway/flight to code will require 2 treads, to reach the threshhold.
Is the final rise from the top tread to the treshhold considered a riser, even though the stairway/flight has no such riser?
To make the question more understandable, you build a stairway/flight and then position it against the house. If the elevation from the top tread to the threshhold considered a riser?
Also, is a footing required, even though the stairway/flight is on a 4" concrete slab? - dansbysa
Dansbysa
As I read it, every vertical rise between stair treads is a "riser" - that is, every time a user has to lift a foot to the next level up, that's a riser. So what you call the "top tread" we call the next to last tread or step in that there is one more rise to climb to reach the finish floor height.
The requirement for a footing below stair stringers might be excused by your local code official if s/he accepts the stair bottom platform or 4" thick slab as adequate support against settlement of the stairway in the future.
(Oct 26, 2012) george pearson
I have a set of stairs that go down to basement and is open on both sides of stairway do I need 2 hand rails or will one be sufficient for code
George: the answer depends on your local building codes and the width of your stairway. For example on a 36" wide stair you may be permitted to install handraillings (you'll also need stair guard railings or balusters) along the open side of the stair.
(Nov 29, 2012) pat
i have a cape with no beams to second story stairway conections please help me to fix cause keep breaking banister conection to wall in stairway
Pat: the best solution is to move the bannister or handrailing support to a place on the wall where its screws can connect directly into a wall stud. Usually just connecting to drywall or plaster is a weak and unsafe connection.
If you needed to install a banister-to-wall connection where there was no nearby wood or other framing to which it could connect you'd need to either open the wall and insert a horizontal structural member between the nearest studs and located to accept the banister support, or you'd need to install wall anchors of a size and spacing that is rated to withstand the loads involved. The second choice sounds rather unlikely to me.
(Dec 11, 2012) Ed Sim
I have a sloped property and on the front I would like to put steps in the middle instead of climbing up the slope of the ground. if I have 4 steps to make it easier to walk up the slope must I have a railing even though you could step sideways and be on the ground level What is the height from the step to the ground if I build the steps on the top of the ground level that does not require a railing?
Ed, most localities specify the requirement for handrails and guardrails based in part on the total height involved (typically 3 feet), some use the number of steps (typically 3 or more) but as there are falling hazards even at a single step I recommend installing railings and guardrails.
(Mar 12, 2013) Jeremy
Is there a code for the studs (2x14) under the tread? On a 36" tread should there be a middle support in addition to the ones on the ends?
If your stair stringers are deep notched and not secured along at least one side by a wall you should consider additional support.
(Mar 19, 2013) mike
Is there a requirement in OSHA that states how long you can go between supports for a temporary staircase? Rialing supports that is.
Mike I don't see an explicit answer to your question, most likely because the answer would depend on the components used for the supporting structure or supporting the railing and the strength and stiffness of the railing and guardrail itself. Because of the very wide range of possible situations codes for this problem usually say that the handrail or guardrail has to meet certain strength loads instead of specifying how it should be built.
(Mar 9, 2014) Mike C
Could outdoor deck bench seating along edge of deck pass code instead of placing railing on outer edge?
Some inspectors pass that design provided the bench seating includes a continuous back of adequate height.
(Mar 17, 2014) Anonymous
What is code for railing size in public buildings in wisconsin
Anon, assuming you're asking about handrailing cross section and dimensions, in the article above (or by searching InspectApedia) you'll want to read Details about safe graspable and unsafe non-graspable handrailings found
at GRASPABILITY of HANDRAILINGS
Using Kenosha WI code as a model, for 1 and 2 family dwellings, handrailings can be 2" diameter round or 2 7/8" rectangular maximum, and 2x4s etc are not allowed as handrails.
(Mar 19, 2014) Does an outside stairway qualify as a main stairway for egress?
I am putiing a spiral stairway in my home and removing the existing straight stairway with landing. The second floor is completely surrounded by a continuous balcony.
I will be putting a straight stairway with a landing on the outside of the house similar to the type found in 2-story apartment complexes and motels. Do you think that would suffice to satisfy code requirements for egress?
Thank you,
Jared Gill
I think so (personal opinion) but really as local codes vary you want to ask your local building department about local requirements. For example, the stairway may need to be covered or protected from weather (ice and snow). And of course there are lighting, railing and related requirements.
(Apr 18, 2014) Rich O
My house in Westminster CO is just out of warranty and one of the staircase risers has started to visibly deflect (and squeak) when traversing the stairs. I've requested the builder take a look, in the meanwhile, is there a specific code I can refer to in order to ascertain if the stair was properly constructed? Thanks, Rich
So, used improper terminology below, believe I should have used "stringer" versus "riser", the entire 12' stringer (wood construction) is now deflecting as if a support has failed. Thanks again, Rich
Yes a riser is the vertical board enclosing the space between horizontal walking surfaces, i.e. treads.
The stringer is the support for the stairs.
If a stringer is deflecting, depending on the amount, it may be damaged or may have been inadequate to begin with.
For safety, investigate and determine what repair or additional support is needed.
Because stringer notch depth for designs that actually notch the 2x12 or 2x14 framing lumber typically used can vary depending on stair design, codes do not specify explicit lumber dimensions. Instead codes typically specify the strength required of the ending design. One may need to increase the number of stringers accordingly.
For example the IRC specifies that stairs shall be designed to withstand a live load of 40 pounds - as with a building floor.
Individual stair treads shall be designed for the uniformly distributed liveload or a 300–pound concentrated load acting over an area of 4 square inches, whichever produces the greater stresses.
Before an inspection has been performed we don't know if the deflection of the stair stringer to which you refer is due to damage (rot for example) or a design inadequacy. But the initial focus must be on the detection of and response to any *immediate safety hazard* such as conditions that could permit a stair collapse, fall, or injury.
Here is a model building code citation for stair stringer support requirements for residential stairs
using the 2003 IRC.
R301.5 Live Load.
Minimum required live load for Stairs 40 psf. c.
c. Individual stair treads shall be designed for the uniformly distributed live load or a 300-pound concentrated load acting over an area of 4 square inches, whichever produces the greater stresses.
301.1.1 Alternative provisions.
As an alternative to the requirements in Section R301.1 the following standards are permitted subject to the limitations of this code and the limitations therein. Where engineered design is used in conjunction with these standards the design shall comply with the International Building Code.
1. American Forest and Paper Association (AF&PA) Wood Frame Construction Manual (WFCM).
2. American Iron and Steel Institute (AISI), Standard for Cold-Formed Steel Framing—Prescriptive Method for One- and Two-family Dwellings (COFS/PM).
Rich: I wanted to add that one of the most thoughtful articles I've found on stair stringer design addresses the lack of specificity of stair stringer design in the model codes and provides some helpful engineering analysis and assumptions. See
Christopher R. Fournier, P.E., "Wood Framed Stair Stringer Design & Construction", Structure Magazine, March 2013, p. 45-46. Mr. Fournier is a structural engineer in North Conway NH. His article is available online, retrieved 4/19/14 original source: www.structuremag.org/Archives/2013-3/C-StrucDesign-Fournier-March13.pdf
See details at STAIR STRINGER DEFECTS
Anonymous
Hello,
My house burned down a few months ago and we are in the process of planning our rebuild (thank goodness for insurance). Our house was 102 years old, so one of the challenges in redesigning is accommodating code compliant stairs (we have some of the original 1912 blueprints and are trying to recreate as much as possible).
We thought we'd come up with a way to fit code compliant stairs in, but now our architect has expressed concern that our attic stair will not comply with code because, as drawn, it is accessed through the 2nd floor laundry room rather than a hall. But, I don't see anything in the code about this. The stair otherwise meets all requirements I can find (width, treads, risers, landings). Can anyone provide insight? Thanks very much.
Anon,
I need to better understand the question. If the concern is the pathway to access an attic stair, I have not found a restriction that says which room must provide that entry point. The ICC Model Code section 1022 describes Interior Exit Stairways & Ramps. 1022.3 Termination.
Interior exit stairways and ramps shall terminate at an exit discharge or a public way.
Exception: Interior exit stairways and ramps shall be permitted to terminate at an exit passageway complying with Section 1023, provided the exit passageway terminates at an exit discharge or a public way.
But an attic stair, presuming that it is not accessing an occupied living space, is more likely to be able to be treated as having more limited constraints such as those required for access to mechanicals or storage.
Please ask your architect to be more specific, giving us the code violation that he is citing and I'll be very glad to research the topic further.
Daniel
katie said:
Thank you so much for the quick and detailed response! The attic will be unfinished in the rebuild, but we have emphasized that we'd like to finish the attic in the future when funds allow and therefore requested a real stairway instead of a pull down and collar ties that will allow for minimum ceiling height requirements.
This must be why architect is concerned (but I will verify with him). Our laundry room is on 2nd floor off the main hall that leads to stairs to first floor.
Exit pathway or public way must mean that the laundry room cannot have a door that separates it from the hallway? In other words, perhaps if the laundry didn't have a door it would be considered an extension or branch of the main hall? Of course, a doorless laundry room would be problematic with my messy ways... :)
Katie, For an attic that's to be an occupied space, you're looking at sleeping areas on the third floor of a home - which may not be permitted in your jurisdiction unless there is a second fire exit stairway.
Also for an occupied space the laundry room becomes a passageway as well.
Don't take code citations literally without determining the class of occupancy of the building, as you'll see that different restrictions apply. I'm doubtful that a door will be an issue. Unobstructed passage width might be.
It would make sense to take the question to your building department.
katie said:
thanks again very much, i will take your advice and ask the building department ;)
5/22/2014 Ian McIlvaine said:
My father-in-law has tripped several times on his stairs and blamed the protruding nosing. He asked me why stairs have nosings and I had to confess that I didn't really know. I did some research on tripping and protruding nosings and found that the
Australian code does not allow open risers or protruding lips/nosings on stair treads precisely because they are a trip hazard for the disabled. It is interesting, then, that this article mentions that a stair MUST have a protruding nosing of min
3/4" to max. 1-1/2". Can anyone explain why this is so when such a lip can so easily catch a toe of someone climbing a stair?
Ian you raise an interesting and important question.
In part the differences in opinion on stair tread design, not just nosing but riser height, stem from differences in how different people climb and descend stairs.
I agree that not all model stair codes necessarily specify the use of a tread nose, and I've found and cited research arguing both sides of the issue.
Some have argued that as well as differences ascribed to age, physical size and strength, we even step differently ascending than descending stairs.
Keep in mind that for an elderly or disabled person, living in a home with no stairs at all and with careful attention to remove trip hazards such as thresholds, wires, loose rugs, are all important changes.
To have sufficient space to cite research and to continue this discussion I'm moving your question and my reply to
STAIR TREAD NOSE SPECIFICATIONS
Please take a look and comment or ask further as it suits.
(June 12, 2014) Kirby Gehman said:
Is there any word in the code about the current trend on sites like Pinterest that show stairs with drawers built into the riser to make use of space under the stairs for storage.
They strike me as incredibly dangerous if a drawer is left even a little bit open. Are there specifics you can point me to in the code about this?
Thanks,
Kirby
Kirby, there are building codes specifying the required clearance under stairways and in public area a requirement for sensible guards to protect people who are visually impaired (see the American ADA).
I have not found an explicit code addressing the presence of a drawer built into a stairway riser but I agree that even if a stair otherwise meets riser and tread dimension guidelines, bulit-in statir-storage designs can produce a very serious trip and fall hazard from
Use our email at the page bottom CONTACT link to send me photos of the stairs you describe and we will research the question further.
...
Continue reading at STAIR CODES & STANDARDS or select a topic from the closely-related articles below, or see the complete ARTICLE INDEX.
Or see CODES for STAIRS & RAILING, FAQs-4 - still more-recently posted questions and answers about stair, tread, and railing codes
Or see these
CODES for STAIRS & RAILING, FAQs-3 at InspectApedia.com - online encyclopedia of building & environmental inspection, testing, diagnosis, repair, & problem prevention advice.
Or see this
Or use the SEARCH BOX found below to Ask a Question or Search InspectApedia
Search the InspectApedia website
Need to make a private comment? Email editor@inspectApedia.com. We welcome email with your website content critique, corrections, suggestions or questions. Email is monitored daily but our workload may prevent an immediate reply. For immediate results, we hope you'll first try asking your question using the search box just above.
In addition to any citations in the article above, a full list is available on request.