Building Inspection, Diagnosis & Repair Info

Guardrail collapse led to injury (C) Daniel Friedman Guardrail & Handrail Strength Requirements & Testing

Guard rail & handrail strength requirements & strength testing requirements specified in various building codes & standards. This article provides details about standards, requirements & testing procedures for handrailings & guardrailings in or on the exterior of buildings.

Our page top photo shows an odd guardrail along a tiny walking space - the DIY owner-installer never considered that someone (a house painter) might actually need the railing to be secure and functional. The result was a serious injury.

InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers, products, or services discussed at this website.

- Daniel Friedman, Publisher/Editor/Author - See WHO ARE WE?





ADVERTISEMENT





Guardrail, Stair Rail & Handrail Strength Requirements - the 200 pound load criterion & others

Deer Net deck rail (C) Daniel FriedmanDefinition of handrail & guardrail strength requirements along with appropriate building code citations. Types of guardrailings vs. strength requirements for cable, glass, plastic, wood & other guardrail types.

In their 2001 study of an unsafe wooden deck railing assembly, Barnett and Switalski point out that the first American safety standard to address railing design (except residential railings) was the American Standard Safety Code for Floor and Wall Openings, Railings and Toe Boards, ASA A12-1932. [45][46]

That study and other sources cite an array of standards that address some but most-likely not all of the considerations in building or testing a safe guardrail or deck rail system.

By 1967 in the U.S. there were national standards for railings and guardrails, and by 1973 ANSI standards were available.

The railing must be strong enough to resist horizontal loads from people leaning on it.

Article Contents

200 Pound Concentrated Load, 50 Pound PSF Load Guardrail Strength Requirements

The 2000 IRC (IRC Table R301.5) and other typical building codes requires that a guardrail or a handrail be able to resist a 200-pound concentrated load applied along the top in any direction, while some local codes still in effect specify a smaller load of 20 pounds per linear foot.

After an above-ground swimming pool was removed, the owners continued to use the deck in our photo (left). Deer netting was installed across the open edge of the deck - and it worked fine until someone fell thorough it. The torn remains of the deer netting can be seen on the left side of this photograph.

Continuing from from Best Practices Guide to Residential Construction (Steve Bliss, J Wiley & Sons) :

Under the IRC, the infill or balusters must resist a concentrated horizontal load of 50 pounds applied to a square foot area. The baluster requirement is easily met with standard fastening techniques, but meeting the IRC guardrail requirement is difficult without adding steel hardware. The majority of residential decks, which rely on notched posts lag-screwed into the band joist, do not meet the 200-pound requirement.

Watch out: at least some of the standards & procedures specified for testing handrailing & guardrailing or stair rail strength focus on static strength testing. Dynamic testing such as the forces exerted when a person is falling and grabs onto a railing may be important for further consideration.

An additional warning from ASTM explains how you can or cannot use the standards summaries listed here and in further detail at the ASTM website. Quoting:

This abstract is a brief summary of the referenced standard. It is informational only and not an official part of the standard; the full text of the standard itself must be referred to for its use and application. ASTM does not give any warranty express or implied or make any representation that the contents of this abstract are accurate, complete or up to date. [1]

Guardrailing strength specifications & testing procedures & standards

General references

Cable & Other Guardrailing Systems - OSHA

Reader Question: are cable railings permitted by OSHA?

(Aug 5, 2015) Fran said:
Can these cables be applied for OSHA guardrailing?

This question was posted originally

at CABLE RAILINGS & GUARDRAILS

Reply: OSHA requirements for fall protection for workers

There is not an explicit discussion of cable railings and guardrails in the OSHA language, as you'll see in the citation below. My OPINION is that because of the tension required to provide secure cable railings the time, cost and trouble of installing a cable system instead of a more rigid system may be inconvenient at some jobsites even if OSHA would approve the system.

Where workers on a construction site are exposed to vertical drops of 6 feet or more, OSHA requires that employers provide fall protection in one of three ways before work begins:

Many times the nature and location of the work will dictate the form that fall protection takes. If the employer chooses to use a guardrail system, he must comply with the following provisions:

Source:

Glass & Laminated Glass Railings, Guardrails: strength & testing codes & standards

Glass guardrailing & glass stair guard (C) Daniel Friedman

Our photograph above shows a glass panel guardrailing atop a balcony as well as a glass guard along the stairwell itself. I'm doubtful that the balcony glass guard meets the requirements of the IBC and note that there is no top railing along the glass guard enclosure.

There is a "handrailing" along the glass guard on the stairs themselves: I forgot to measure the handrailing height - it may be a bit high for some stair users.

Reader Question: are guardrailings required along the top of glass guardrails on balconies or decks?

I'm building a glass guardrailing around my deck overlooking a lake. Do I need a railing along the top of the glass or is the glass strong enough to meet code?

Reply:

Glass guard railing in New York City (C) Daniel Friedman

At left we illustrate a glass guardrailing as well as a glass stair rail (at right in the photo) installed in a shopping mall in New York City.

Note the position of the stair-user's right hand (red arrow- click to enlarge any image) suggesting that while the railing along the top of the glass guards at both balcony and along the stair may serve to meet the code requirements below, the position of the rail along the top of the stair guard may be too high for comfortable use by people walking on the stairs. [For privacy we blurred the faces of the pedestrians in this photo - Ed.]

According to the ICC, a top rail, at a height of 42" above the walking surface is required along a glass guardrail will be required unless the glass panels themselves will meet the structural strength required by IBC 1607.7.

Considering the safety factor cited from the IBC for the top rail it is unlikely that glass panels will meet that requirement. (Wagner Companies ret. 2015).

The top rail should continue to meet the guardrailing load requirements even should a glass panel itself fail, fall, or break. Note that you may be required to use laminated, tempered or safety glass for glass guards in your area. Check with your local building official by providing the plan and design specifications for your glass guardrailing system as obtained from your professional engineer or architect.

Note that the above is only discussing the top rail along a glass guardrail or stair guard. In addition to a top rail, along a stair guard or ramp that is enclosed by glass "guards", a handrailing will be required at a height between 34" and 38".

In-Situ Testing of Guardrails & Handrails

Metal Railings, Guardrails, Handrails testing standards

Guardrail collapse led to injury (C) Daniel Friedman

Plastic Railings, Guardrails, Handrails testing standards

Wood-Plastic Composite Railings, Guardrails, Handrails testing standards

Wood Railings, Guardrails, Handrails, testing & strength standards

Railing & Handrail Strength & Failure Studies

...




ADVERTISEMENT





Reader Comments, Questions & Answers About The Article Above

Below you will find questions and answers previously posted on this page at its page bottom reader comment box.

Reader Q&A - also see RECOMMENDED ARTICLES & FAQs

On 2022-05-27 by Anonymous: regulations for balcony guardrailings considering dynamic loading force?

Do you have any specific regulation for building balcony handrail on dynamic loading force?

Because, dynamic loading force is normally bigger than statistic load as you well know,

Best regards,

- Anonymous by private email

On 2022-05-27 by InspectApedia-911 (mod)

@Anonymous

Thank you for the interesting question about the dynamic loading force on guardrails or handrails.

You'll see that the force requirements are expressed rather simply - at least in North America. For example while a force in pounds is specified, there's no consideration given to speed. I think that's because of an assumption of the most-common situations in which a person falls against a handrail or guardrail (or grasps the rail in an effort to arrest a fall) and the acceleration associated with that fall.

That is to say the acceleration and distance of movement between the person and the guard or handrail is rather small.

So in designing handrails and guardrails for human activity, it's the static load that gets primary consideration.

Let me know what you think.

Note: my comments above pertain to pedestrian or human interaction with handrails and guardrails.

A very different view is taken with respect to guard rails along roadways or highways where the combination of mass and speed of vehicles is very significant.

Research on the Role of Dynamic Force on Guardrail & Handrail Strength Requirements & Testing

  • Escamilla, Alfonso Cobo, María de las Nieves González García, and Nuria Llauradó Pérez. STATIC LOAD BEHAVIOR AND ENERGY ABSORPTION OF SAFETY GUARDRAILS FOR CONSTRUCTION WORKSs [PDF] Revista de la Construcción. Journal of Construction 15, no. 2 (2016): 46-54.
    Abstract

    One of the requirements which must be met by the temporary edge protection systems (TEPS) is to stop a worker who walks, stumbles, falls and knocks against the system. The effect of the worker’s crash with the protection system is a dynamic type stress applied as an impact.

    The capacity of the system to withstand the impact depends on its ductility and its ability to absorb energy. The area enclosed by the load-displacement graph of a TEPS when the load is statically applied is an indicator of its ductility and its ability to absorb energy.

    In Europe, the EN 13374 standard specifies the requirements to be fulfilled by the TEPS. For systems placed in floor slabs with a slope smaller than 10° (class A systems), the standard indicates that the testing should be performed using static loads.

    In this work, TEPS manufactured from steel, wood, injected plastic, and composites have been tested with the static loads test system specified in the EN 13374 standard for assessing class A systems.


    Subsequently, the areas enclosed in the load-displacement diagram have been tested and have been compared with the estimated values of impact energy.
    Keywords: safety guardrails, energy absorption, static load, accident, construction.


    This paper can be hard to retrieve so we include a copy here
  • Racic, Vitomir, Aleksandar Pavic, and J. M. W. Brownjohn. "Experimental identification and analytical modelling of human walking forces: Literature review." Journal of Sound and Vibration 326, no. 1-2 (2009): 1-49.
  • Maksud-Ul-Alam, Mohammad, and A. F. M. S. Amin. "Pedestrian induced vibrations in footbridges: Reappraisal of code provisions." In IABSE-JSCE Joint Conference on Advances in Bridge Engineering-II. 2010.
  • Pinto, Armando, and Luis Reis. "Barrier for buildings: analysis of mechanical resistance requirements." Procedia Structural Integrity 1 (2016): 281-288.
    Abstract

    Barriers (guardrails and balustrades) prevents people from falling, for example, from balcony, open windows and stairs. Barriers also retain, stop or guide person in buildings.


    To increase the transparency of these components, traditional materials such as bricks, wood and metal are being replaced by glass or an organic material, which has mechanical behavior different from traditional materials.

    Regulation usually specify some action to take into account in the design of barriers, but do not define the required resistance. There are no international standards (ISO or EN) to assess the fitness for use of barriers, only national standards, with different testing loading conditions and mechanical resistance requirements.


    In this paper is presented a comparison of requirements and experimental testing conditions specified in standards from Portugal, Spain, France, UK, USA and Brazil.

    The goal of this research is to find some equivalence between standards, regarding the mechanical resistance behavior of different materials (brittle/ductile materials) and set a worst case scenario as the basis for the guardrails mechanical resistance profile.

    Some relations between the service limits state (plasticity) of metal guardrails and maximum deflection are proposed.
  • Reid, John D., Jason A. Hascall, Dean L. Sicking, and Ronald K. Faller. "Inertial effects during impact testing." Transportation research record 2120, no. 1 (2009): 39-46.
    Abstract:

    Shortcomings were identified in historic dynamic guardrail post testing methods that could overestimate the strength of guardrail posts by a factor of two. This inaccuracy resulted from the influence of inertia that was not previously accounted for during dynamic component testing.

    The effects of inertia were verified and quantified with several analysis methods including nonlinear finite element analysis, which was used to develop a computer simulation of the dynamic tests. Several alternative testing procedures that could significantly reduce the effects of inertia were identified and investigated.

    One of these testing alternatives–-use of a crushable impact head–-was shown with computer simulation to reduce the effects of inertia and maintain the benefits of strain rate effects.

    The use of such an impact head is recommended for all future dynamic post strength testing. The results of the study imply that changes should be made not only in the standard design procedures used for guardrail and other vehicular barriers, which are clearly influenced by inertial effects, but in all designs that are based on dynamic strength testing.

    Dynamic testing is very common in the field of transportation engineering and care should be taken to ensure that inertial effects are considered when performing such tests.
  • Wu, Weijia, and Robert Thomson. "A study of the interaction between a guardrail post and soil during quasi-static and dynamic loading." International Journal of Impact Engineering 34, no. 5 (2007): 883-898.

On 2022-05-27 by Anonymous

Anonymous - posted by moderator from private email

Thank you for your quick reply .
I’ll appreciated your concern.
My further comment is as follows .
Plese read and evaluate my understanding on dynamic force corrosion against hand rail.
Regards - Anonymous, in Japan

Comment:

Normally , if we confide to something with some speed “V”, it should be considered to count dynamic moving energy .

And then, dynamic moving energy is estimated as MV2

Therefore, total among of force will be reach to several times of static force.

When person’s weight is 50 kg weight , the person rushed to handrail, the received hand rail load force will be 50kg x 20 times or over =1000kg…..1 ton….. this means extremely bigger force will be given by dynamic corrosion .

In short, dynamic load force will be very bigger than statistic force.

On 2022-05-27 by InspectApedia-911 (mod) - role of velocity or momentum on handrail & guardrail strength requirements, failures, falls

@Anonymous in Japan

You raise and argue for a very interesting point, makes sense to me, and is not addressed in model building codes.
Indeed some of the most horrible accidents I've investigated have involved handrail and guardrail failures (or the absence of them entirely).

I'm not sure, however that we have an accurate idea of the speed with which someone rushes to an handrail, nor that their entire bodyweight is applied when the grasp it at that moment.

Where most or all body weight is applied to the rail is when someone is trying to arrest a fall that has started.

Aside: General comment on falls & force: (I'm not a physicist)

Just two weeks ago, I fell myself, walking on a flat EPDM (*Rubber) roof. My subjective time sense was less than a second. I was walking and then in "zero" time, wham! I was on my back on the roof. The roof surface had a coating of algae and was wet. The static coefficient friction of wet algae is one of the lowest substances known. Had this been a stair I'd not have even had time to grasp the handrail.

Had I fallen against a guardrail it'd have been 175 lbs static force + the momentum that might be achieved across the space between myself or a hand or torso, and the railing.

On stairwells people are no more than stairwell width from the handrail.

On a large balcony or deck that distance could be much greater, but I think that it would be rare for someone to be running towards the guardrail and then crash smack into it.

It will be instructive to look at actual research data on the contribution of momentum to loads on both handrails and guardrails.

Aside: another handrail failure I witnessed last year was a complete loss of connection of the handrailing to the wall in a private home when a heavy-set occupant, sitting on the lower step, pulled on the handrail simply to help raise himself to a standing position. It appears to me that at least in the U.S. handrail brackets widely sold in building supply stores may be seriously deficient in strength.

The stair user broke the handrail bracket nearest his hand and the railing then came off of the wall. I'm led from that field observation to focus more immediate attention on hand and guardrail connections.

Shopping at a Home Depot store a few months ago in preparing to add a hand railing along a stairway, I looked at two grades of handrail bracket available - I bought the stronger of the two but note that the stronger units were hard to find and much more costly.

No normal carpenter or railing installer would give a thought to the possibility that the mounting system was as weak and dangerous as I found it to be.

  • Kinoshita, Satomi. "Handrail position and shape that best facilitate sit-to-stand movement." Journal of back and musculoskeletal rehabilitation 25, no. 1 (2012): 33-45.

There has been some research on the contribution of momentum in stair-falls (and perhaps in guardrail failures) - perhaps you have more expertise on this and can cite additional sources.

Below I cite a few findings from searching for "role of momentum in guardrail strength requirements" - though most discussions appear not to focus exactly on your argument.

In particular see the Komisar PDF copy that I attach, and the momentum data on p. 11

  • Debelle, Héloïse, Carla Harkness-Armstrong, Kathryn Hadwin, Constantinos N. Maganaris, and Thomas D. O'Brien. "Recovery from a forward falling slip: measurement of dynamic stability and strength requirements using a split-belt instrumented treadmill." Frontiers in sports and active living 2 (2020): 82.
  • Komisar, Vicki, Konika Nirmalanathan, and Alison C. Novak. "Influence of handrail height and fall direction on center of mass control and the physical demands of reach-to-grasp balance recovery reactions." Gait & Posture 60 (2018): 209-216.
  • Komisar, Vicki, Konika Nirmalanathan, and Alison C. Novak. INFLUENCE OF HANDRAIL HEIGHT AND FALLING DIRECTION ON CENTER-OF-MASS CONTROL AND THE PHYSICAL DEMANDS OF REACH-TO-GRASP BALANCE RECOVERY REACTIONS [PDF] -

    Abstract:
    The ability to maintain and recover center of mass (COM) and trunk control after a destabilization is critical for avoiding falls and fall-related injuries. Handrails can significantly enhance a person’s ability to recover from large destabilizations, by enabling the person to grasp and apply high forces to the rail to stabilize their COM.

    However, the influence of handrail height and falling direction on COM control and the demands of grasping are unknown. We investigated the effect of handrail height (34, 38, 42 inches) and fall direction (forward, backward) on COM and trunk control, and the corresponding physical demands of reach-to-grasp balance reactions.

    Thirteen young adults were destabilized with platform perturbations, and reached to grasp a nearby handrail to recover balance without stepping. COM kinematics and applied handrail forces were collected. COM control was evaluated in terms of: (1) COM range and peak displacement, velocity and momentum in all Cartesian axes; and (2) trunk angular displacement, velocity and momentum in the roll and pitch axes.

    The physical demands of grasping were estimated via resultant handrail impulse. Compared to forward-directed falling, backward-directed falling was generally associated with greater peak COM and trunk angular displacement, velocity and momentum, along with greater handrail impulse. Higher handrails generally resulted in reduced peak COM and trunk angular displacement, velocity and momentum, as well as reduced handrail impulse.

    These results suggest that higher handrails(within the range of heights tested) may provide a stability advantage within the range of handrail heights tested, with better COM control achieved with lower physical demands of grasping.
  • Park, Sungwoo, and James M. Finley. "Manual stabilization reveals a transient role for balance control during locomotor adaptation." bioRxiv (2019): 647453.

On 2019-09-17 by Taylor - maximum distance newel posts should be when on a ramp?

Re-Posted by (mod)

Taylor said:

What is the maximum distance newel posts should be when on a ramp?
Is there a certain type of screw/bolt that needs to be used to anchor the newel posts to concrete when mounting them outside?
What is the best way to mount the handrail to the newel post since the metal on the handrailing is so thin?

On 2017-01-23 by Damon Bourque - At what angle is the applied load required to be pulled at when applying the 800 lb.

At what angle is the applied load required to be pulled at when applying the 800 lb. (200 x factor of 4) to the top rail of a glass rail system

Moderator reply:

Taylor

I am not aware of a specific newel post separation distance on ramps; in my OPINON that distance will vary substantially depending on the guardrailing construction materials, newel post materials, ramp materials, and fasteners used.

The guardrailing's supporting posts must be sufficient to secure the guardrail against wobbling or worse, detachment, or breakage, or failure in response to side-loading forces .

Similarly, the proper attachments between balusters and guardrail top and bottom and attachments for handrailing depend on the materials involved. There is no single "fastener" that is proper for all possible materials. For example wood and steel handrailing connectors may be quite different.

This Q&A were posted originally at RAMP RAILING CODES https://inspectapedia.com/Stairs/Access_Ramp_Railing_Codes.php

...

Continue reading at GUARDRAIL POST CODES & SPECS or select a topic from the closely-related articles below, or see the complete ARTICLE INDEX.

Or see these

Recommended Articles

Suggested citation for this web page

GUARDRAIL & HANDRAIL STRENGTH at InspectApedia.com - online encyclopedia of building & environmental inspection, testing, diagnosis, repair, & problem prevention advice.

Or see this

INDEX to RELATED ARTICLES: ARTICLE INDEX to STAIRS RAILINGS LANDINGS RAMPS

Or use the SEARCH BOX found below to Ask a Question or Search InspectApedia

Ask a Question or Search InspectApedia

Share this article:

Ask a Question or Search the InspectApedia website using the box just below.

Need to make a private comment? Email editor@inspectApedia.com. We welcome email with your website content critique, corrections, suggestions or questions. Email is monitored daily but our workload may prevent an immediate reply. For immediate results, we hope you'll first try asking your question using the search box just above.

Citations & Reviewers

In addition to any citations in the article above, a full list is available on request.

  • [1] ASTM web search 02/04/2013, original source: http://www.astm.org/
  • [2] §3209. Standard Guardrails, California Building Code, provides description of how guard rails should be constructed. Web search 09/02/2011,original source: www.dir.ca.gov/title8/3209.html
  • [3] Stephenson, Elliott O., THE ELIMINATION OF UNSAFE GUARDRAILS, A PROGRESS REPORT [PDF] Building Standards, March-April 1993
  • [9] Falls and Related Injuries: Slips, Trips, Missteps, and Their Consequences, Lawyers & Judges Publishing, (June 2002), ISBN-10: 0913875430 ISBN-13: 978-0913875438
  • [12] Slips, Trips, Missteps and Their Consequences, Second Edition, Gary M. Bakken, H. Harvey Cohen,A. S. Hyde, Jon R. Abele, ISBN-13: 978-1-933264-01-1 or ISBN 10: 1-933264-01-2, available from the publisher, Lawyers ^ Judges Publishing Company,Inc., www.lawyersandjudges.com sales@lawyersandjudges.com
  • [13] Slips, Trips, Missteps and Their Consequences, Gary M. Bakken, H. Harvey Cohen, Jon R. Abele, Alvin S. Hyde, Cindy A. LaRue, Lawyers and Judges Publishing; ISBN-10: 1933264012 ISBN-13: 978-1933264011
  • [14] The Stairway Manufacturers' Association, (877) 500-5759, provides a pictorial guide to the stair and railing portion of the International Residential Code. http://www.stairways.or
  • [43] International Building Code, Stairway Provisions, Section 1009: Stairways and Handrails, retrieved 8/29/12, original source: http://www.amezz.com/ibc-stairs-code.htm [copy on file as IBC Stairs Code.pdf]
  • [44] Model Building Code, Chapter 10, Means of Egress, retrieved 8/29/12, original source: http://www2.iccsafe.org/states/newjersey/NJ_Building/PDFs/NJ_Bldg_Chapter10.pdf, [copy on file as NJ_Bldg_Chapter10.pdf] adopted, for example by New Jersey. International Code Council, 500 New Jersey Avenue, NW, 6th Floor, Washington, DC 20001, Tel: 800-786-4452
  • [45] Ralph L. Barnett* and William G. Switalski, "Case Study and a Senior Mechanical Engineer, Triodyne Inc., Niles, IL (respectively. Contact information: Triodyne Inc. Consulting Engineers & Scientists – Safety Philosophy & Technology 5950 West Touhy Avenue Niles, IL 60714-4610 (847) 677-4730 FAX: (847) 647-2047 e-mail: infoserv@triodyne.com www.triodyne.com, web search 02/04/2013, original source: http://www.triodyne.com/SAFETY~1/Sb_v18n1.pdf, copy on file as BarnettSwitalski_Railing_Study.pdf.
  • [46] “American Standard Safety Code for Floor and Wall Openings, Railings, and Toe Boards,” AS A12 -1932. New York: American Standards Association, approved May 3, 1932.
  • [49] “Requirements for Fixed Industrial Stairs,” USAS A64.1-1968. New York: American National Standards Institute, approved February 16, 1968.
  • [50] “Fall Protection,” 29 CFR 1926.451(g)(4)(vii). Washington, D.C., Occupational Safety and Health Administration; Chapter XVII, 7/1/99 edition.
  • [51] “Special Loads,” Section 1615.0, The BOCA National Building Code/ 1993. Country Club Hills, IL: Building Officials & Code Administration International, Inc. 1993, pp. 185 – 186.
  • In addition to citations & references found in this article, see the research citations given at the end of the related articles found at our suggested

    CONTINUE READING or RECOMMENDED ARTICLES.


ADVERTISEMENT