Building Inspection, Diagnosis & Repair Info

Drain back valve removed from well piping tee (C) Daniel FriedmanDrain Back Valves & Snifter Valves

  • POST a QUESTION or COMMENT about sifter valves, Dill valves, and how the snifter valve works together with US Gauge & Similar Type 310WJ, Type 300SL, or Type 6 Rectangular Air Volume Controls

Drain Back Valves, Bleed-Back Systems & Snifter Valves for Well or Lake Pipe Freeze Protection & Air Volume Control:

This article series describes snifter valves and drain-back valve , what they are, how they regulate air in a well water system, how they work with an air volume control,& how these components protect well piping against freezing. We describe how & where the snifter valve, drainback valve and air volume control are installed & what they look like.

InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers, products, or services discussed at this website.

- Daniel Friedman, Publisher/Editor/Author - See WHO ARE WE?





ADVERTISEMENT





Snifter Valves, Drain-back Valves, & Air Inflators Offer Protection From Well Pipe Freezing & Air Volume Control

Snifter valve on submersible pump system can protect against well pipe freezing (C) Daniel Friedman

Snifter valves & drain-back valves along with AVCs are a three-part air volume control system designed to allow water to drain out of well piping and back into the well while also maintaining water pressure in the building and the air charge in a well water pressure tank.

These devices are used on some submersible pump systems or lake water supply systems where a bladderless water tank is installed and where well piping is exposed to freezing.

This article discusses how snifter or bleed-back valves are maintained, replaced, or in some cases how and when they can or should be eliminated.

Article Series Contents

[Click to enlarge any image]

Why are Drain Back Valves & Snifter Valve Air Type Volume Control Systems Used?

There are three reasons why a snifter valve & drain-back valve may be used along with a submersible well pump, bladderless-type water tank, and check valve.

  1. Water line freeze protection:

    the main one is to allow water to drain out of well piping and back into the well to prevent freezing of well piping that is not buried below the frost line.

    Drain back valve systems may be used to freeze-protect water supply piping from drilled wells (well bores) or from other water sources such as freshwater lakes in freezing climates.
  2. Air supply to the pressure tank:

    a second feature of drain-back / snifter valve systems is the injection of air into the water pressure tank, a process that involves further air management by an air volume control valve that will vent excess air from the tank.
  3. Water odor & taste improvements:

    A third feature claimed by some installers is a reduction in both iron and smelly sulphur odors, though the level of this benefit is questionable.

Snifter Valves, Air Inflator Stems, & Drain-Back Vents Inject Air Into the Well or Lake Water Piping System

Synonyms for this well pipe freeze protection system include: snifter valve system, drain-back valve system, bleed-back system, well pipe freeze protection system, bladderless water tank air injection system as well as Brady valves or Dill valves.

Air inlet and air purge snifter valve photos © D Friedman at InspectApedia.com

In our well pipe freeze protection system photo (above left) the green arrow points to the air release valve opening on the water tank's air volume control (AVC) and the red arrow points to the snifter valve air inlet fitting mounted on a check valve. Below: my finger points to the snifter valve at its mount on the check valve.

Snifter valve on a submersible pump well system © D Friedman at InspectApedia.com

We give a closer look at these components shortly.

Snifter valves (photo above right, shown mounted on the 1/8" tapping on a check valve) provide an air inlet, typically located on a check valve on the water line near the bladderless water pressure tank. The air inlet snifter valve works in concert with a water drain-back valve (a bleeder orifice) that you cannot see - located on well piping inside the well where a submersible pump is used.

At the end of a well pump on-cycle (when the well pump stops) this snifter air valve mounted on a check valve on the well line ahead of water pressure tank opens to allow air into the well piping.

This incoming air allows water to drain out of the well piping at the drain-back valve: a bleeder fitting mounted on a tee on the well piping, inside the well.

A photo of the drain back bleeder mounting tee on the well piping is shown at below left. We've pulled the piping out of the well for this photo. A close up of the drain back bleeder valve itself is shown at below right.

Air inlet valve tee on well piping (C) D Friedman Rasmussen Well Drilling

A check valve located near the bottom of the water tank on the incoming well piping (on which the snifter valve is mounted in our photo) keeps water in the pressure tank from draining back down into the well when the well pump has stopped.

Air volume control air inlet valve for well piping © D Friedman at InspectApedia.com

Because the snifter valve system will usually push more air into the water tank than is needed, an air release valve mounted on the water pressure tank is also installed to purge excess air from the water tank as necessary. So if you hear air hissing from the air purge valve, that's normal.

Watch out: The snifter valve stem looks like any other air inlet valve but it uses a weak internal spring to allow the valve to open on its own, admitting air into the piping. DO NOT tighten the valve stem cap found on the snifter valve and don't replace a vented valve stem cap with a solid plastic one - if you do so your well pipes may freeze to death.

That's because if no air can enter the snifter valve, no air can enter the well piping and the well pipe freeze protection system won't work. If you find water leaking out of the snifter valve it needs repair or replacement.

Air introduced by a snifter valve / bleed-back system may reduce unwanted tastes, iron or odors of sulphur in the water supply

Rasmussen points out that in Northern Minnesota and on water systems in other very cold climates, the system's ability to drain water back into the well, leaving just air in the higher sections of well piping can help protect a well system from freezing.

According to our well driller friends, on water systems whose well provides water high in smelly hydrogen sulfide (that rotten egg smell) or perhaps high in iron, the high absorption of air into the well water provided by this design might help oxidize and thus reduce those contaminants in the water supply.

By contrast, a bladder type water pressure tank keeps the water supply physically separate from the pressure tank's air charge - air is never absorbed into the building water supply and other treatment methods would be needed to remove sulphur, hydrogen sulfide, or high iron levels.

Really? We have read this claim in several articles about drain-back or bleed-back systems but have not [yet] found research supporting the claim that added air induction into the well water system was alone able to remove significant levels of iron (FE) nor hydrogen sulfide (H2S). Contact us if you've found such data.

We are not confident that air injection ALONE will cure a serious sulphur odor in the water supply.

More likely we'll need to install a treatment system such as a potassium permanganate "green sand as the plumbers call it" system or a chlorine injection system, combined with filtration, or some equivalent.

Drain-Back Systems Work with Submersible Pump Systems

But the use of a drain-back system to prevent well piping systems is long established as a method that works on well water supply systems that use a submersible pump and a bladderless type water pressure tank.

Why only with submersible well pumps? If we drain the water out of well piping in a jet pump system the pump is going to lose prime and may be unable to re-prime itself, thus losing water supply and risking pump burn-up.

Why with bladderless type water pressure tanks: those tanks can be fitted with an AVC or air volume control that will release the excess air allowed into the system by the drain-back valve and snifter valve.

Drain Back Valve, Dill Valve, & Snifter Valve Components, Definitions & Functions

This discussion has moved to a separate article

at DRAIN BACK & SNIFTER VALVE SYSTEM COMPONENTS

How the Drain Back System Actually Works on Well or Lake Water Piping to Protect from Freezing & to the Keep Air Charge in the Pressure Tank

Steel bladderless water pressure tank using a drain-back valve and snifter valve (C) Daniel Friedman

The bleed-back or drain-back system on a water piping system works automatically to drain water out of piping between the water pressure tank or check valve and the bleed back or drain back valve opening found on the well or lake water piping in the well casing or at a level below the frost line. By allowing air to enter the piping system it is protected from freezing.

Details are at DRAIN BACK & SNIFTER VALVE OPERATION

Troubleshooting Frozen Well Pipes on Drain-Back Valve, Dill Valve, & Snifter Valve Systems

Now found at DRAIN BACK / SNIFTER VALVE TROUBLESHOOTING

Drain Back Valve & Snifter Valve Installation, Repair or Replacement

Moved to DRAIN BACK & SNIFTER VALVE INSTALLATION / REPLACEMENT

Converting a Bladderless Water Tank to a Tank with an Internal Bladder? Remove all the Snifter Valve Components!

Snifter valve on a submersible pump well system © D Friedman at InspectApedia.com

[Click to enlarge any image]

In our snifter valve photo (above Rasmussen Well Drilling, Inc., Two Harbors MN & DJ Friedman) ) my finger points to the stem of the snifter valve: an air inlet valve mounted on a bronze check valve.

Stains on the floor show that there has been leakage at this particular valve.

In that photo we have a clue that the snifter valve had not worked for years and was also leaky. You can see the copper stains on the floor below the valve (my finger points to the snifter valve stem). How did the owners get away with this? Their well piping was buried at more that eight feet below ground: below the frost line in their areas of Northern Minnesota.

So the owners didn't have a problem with freezing well piping. But they did report a long-standing problem with a water-logged water pressure tank whose well pump short-cycling shenanigans had been dealt-with by manually adding air to the pressure tank at frequent intervals.

See WATER PUMP SHORT CYCLING.

Because the well piping between the well bore and the building was buried sufficiently to eschew the worry about freezing well lines, the owners decided to tackle the recurrent short-cycling problem of their well pump not by replacing the snifter valve (which was the real culprit) but by replacing the steel bladderless water pressure tank with a new internal bladder water pressure tank.

To complete that installation the well-plumber would keep a check valve at the pressure tank outlet but remove the snifter valve and he'd also have to remove the drain-back or bleed-back valve located in the well piping.

Watch out: if on a submersible well pump system that uses a snifter valve for air volume control you later convert a bladderless water pressure tank to a tank using an internal bladder, you should remember to remove both the snifter valve located on the check valve near the water pressure tank and the bleeder orifice or drain-back valve located on the well piping.

If you fail to remove these components you will suffer from constant air discharge at the building faucets and other plumbing fixtures as the air injected into the piping system will be pushed into the water-containing bladder in the new pressure tank: a location from which there is no escape as there is no air volume control and no mechanism to remove this air on an internal-bladder pressure tank set-up.

See AIR DISCHARGE at FAUCETS, FIXTURES

Drain Back Valve & Snifter Valve Suppliers

...




ADVERTISEMENT





Reader Comments, Questions & Answers About The Article Above

Below you will find questions and answers previously posted on this page at its page bottom reader comment box.

Reader Q&A - also see RECOMMENDED ARTICLES & FAQs

Is my Pump and Well Snifter / Drainback Valve Working?

Drainback system snifter valve (C) InspectApedia.com Frank

Hello, I have a drain back system at my cottage. One day I noticed I wasn’t getting water coming in at a normal rate to fill my tank. I could hear the well’s submerged pump running tho. I looked in the well and saw a hole in the fitting on top of the pump.

This is where water was spraying out of and therefore the pump couldn’t successfully fill my tank, see image.

I plugged the hole with JB weld and it’s holding ok for now. While I was in the well I didn’t see any drain back valve on the piping. My snifter valve seems to be working since I hear a hiss when pump stops. Could the water in my system just drain back from the pump’s intake and if so is that acceptable? Thanks, Frank.

Drainback system snifter valve (C) InspectApedia.com Frank

On 2022-07-12 by Frank

by InspectApedia-911 (mod) - drainback system components

@Frank,

Thanks for the helpful question and photo.

A drain-back system has two components:

1. a low-spring-pressure schrader valve above-ground, usually close to the water pressure tank, often on well piping hear the tank (photos above on this page), to allow air to enter the system at the end of a pump-on cycle.

2. a drain-back valve, a one-way ball type check valve (usually) in the well, on piping, above the high water level in the well, to allow water in the well pipe above that point to drain slowly back into the well at the end of a pump-on cycle. This drain-back is what draws air in at the Schrader valve.

Notice that this valve will not normally be close to the submersible pump, it'll be quite a few feet above that point, since the pump will be under-water in the well while the drain-back valve will be above the high-water line in the well.

So I'm unclear what was the purpose of the hole you found on fittings just above the pump. Was it an obvious, deliberate opening, or due to corrosion?

When I click to enlarge your photo and zoom-in, that hole sure looks like a corroded opening, not a deliberate one.

Was the hole smooth-sided or threaded?

And higher on the well piping did you find the drain-back valve itself, out of the water, and similar in appearance to the valve shown at the top of this page?

I don't expect water to drain back through a pump's intake opening; usually the pump will contain one or more check valves. But then none of us knows it all.

Followup 13 by Frank

@InspectApedia-911, Hello, Thanks so much for your reply. The fitting on top of the pump looks like the fitting in the house where the snifter valve is screwed into. Maybe the same fitting was used for both but the one on the pump was plugged with a screw plug instead of having a snifter valve. See photo.

Drainback system snifter valve (C) InspectApedia.com Frank

Then possibly it corroded and left the hole and then the pump wasn’t able to successfully fill the tank because of spray out from that hole. I plugged the hole and the system seems to be working fine now. When the pump cuts out I hear a hiss from the snifter valve inside so water is draining back down to the well and air is filling in the pipe. I also know the pipe is filling with air when water is draining back because the next time the pump comes on air is pushed into the system to pressurize the system again.

Drainback system snifter valve (C) InspectApedia.com Frank

As far as the ball type drain back vale there definitely isn’t one on my black plastic piping. The piping is about 10-12 feet from the ground to the bottom of the well where the submerged pump is. See photo. If I blow on to of the pump fitting air does go out of the pump. Maybe a ball type valve wasn’t needed for my system? Maybe there isn’t any check valve at the pump and water can just drain back from the pump intake?”

Anyway, I’m thinking of replacing my system with a bladder type system and 40 feet of heat line. What is your thoughts/opinion about that? I just got a quote here in Ontario Canada to do that for $2,500 including tank, heat line, and all fittings and labour. Does that sound reasonable? Thanks again, Frank.

by InspectApedia-911 (mod) - drain back system with an internal bladder tank in northern Minnesota

@Frank,

Thank you for the additional photos and discussion.

When we replace a drain back system with an internal bladder tank at a building in northern Minnesota, an area also subject to very cold freezing conditions, the line between well and building was buried below the frost line so we weren't worried about Frozen well pipe. We made the change in part because we needed a new pressure tank anyway.

In the case that you describe, while the conventional bladder type water tank and elimination of drain back valves and sniffer valves seems to simplify the system, you could face a risk that in a time of power outage your well line could freeze and take considerable time possibly having to wait until spring, to thaw.

So your discussion is a reminder of the value of a drain back system in very cold climate as a method to avoid frozen water supply piping between well and building. It's a nice solution that, as it doesn't require a heat tape and electrical source for the heat tape, doesn't require that electrical power stay on past the time that the pump last ran.

 

How do I know what size sniffer valve I need

How do I know what size sniffer valve I need to replace the one I have? Also, will a regular valve stem from a car tire work to replace the one that's gone bad in mine. Just the stem, not the whole valve. On 2021-04-01 by Gene Heard -

by (mod) - where & how to buy replacement snifter valve or well drain-back valve parts

Well snifter valve at Inspectapedia.com@Gene Heard,

Thanks, that's a helpful question about replacement snifter valve "size".

Size of the air inlet snifter valve at the pressure tank

At or near the water pressure tank, the air inlet or snifter valve outlet is a standard size, either a 1/4" MNPT or 1/8" MNPT depending on the size of the tapped or threaded fitting into which the snifter mounts on your well pump system - and sold by your well or plumbing supplier.

Watch out
: At the water pressure tank, the air inlet snifter valve fitting looks like a standard Schrader valve or tire valve, and its size and threads are identical, and so it also looks exactly like the air pressure adjustment valve found on many water pressure tanks. But it is NOT. The difference is in the spring used on the actual valve core.

Because the air inlet needs to open at a lower pressure range than a tire valve, the spring is a "weaker" one and is special to and sold with that device, also purchased from your well or plumbing supplier.

Examples of the air inlet snifter valve with a "light spring" are the

Campbell Snifter Air Valve with Light Spring - sold in both 1/8" MNPT and 1/4" MNPT sizes and shown below.

Another brand is made by A.Y. McDonald - the company's Pump Snifter Valve also sold in two models:
A.Y. McDonald 6512-372, Model 7891, Snifter Valve, 1/8 Inch
or
A.Y. McDonald 6512-373, Model 7892, Snifter Valve, 1/4 Inch

Size of the Bleeder Valve or Drain-Back Valve in the Well

Rubber bleeder for drain back valve on well snifter system - at Inspectapedia.com

An example of the in-well snifter valve component - the water outlet or "bleeder valve" or drainback valve, also referred to as a "Bleeder Orifice" is this rubber version sold by plumbingsupply.com

Usually sold as a 3/4" MNPT sized device this is installed in the submersible pump drop pipe, approximately 10 to 12 feet below the well head.

The manufacturer notes that this bleeder:

Provides fast water bleed capacity through its large orifice opening when pump shuts off

Orifice completely closes when the pump is running and prevents loss of pumping volume

Molded virgin rubber construction

And shown below, these brass well bleeder valves, like the rubber bleeder valve shown above, and also sold as 3/4" MNPT threaded devices are also used as the traditional and most-common drain-back valve in the well.

These are an exact replacement for the 30 year old brass drain-back valve shown in the article above on this page.

These brass bleeder valves are available from your local well or plumbing supplier as well as from online plumbing suppliers such as the Denver WinPump Company at denverwinpumpsales.com

Drainback valve bleeder fitting for well and air tank air control - at Inspectapedia.com

 

Can a snifter valve let in too much air ?

Can a snifter valve let in too much air and cause air at faucets in my deep well system? On 2020-11-15 by Tom Purnell

Reply by (mod) -

Yes, Tom

The snifter valve works in concert with a vent or AVC on the pressure tank designed to let out the excess air; so if that AVC is not working you may end up with excess air in the system that is discharged at a nearby faucet

 

Loud Burps from Air in Snifter Valve Fed Water Tank

Morrison well system (C) InspectApedia.com JamesI have a Deep well 500 feet and a Drain Back setup , but the amount of AIR interring my 82 gallon galvanizes tank is over 3 gallons by volume, the well is 130 feet down hill from my basement . I get a very loud Burp when the air his the bottom of the tank.

I need a way an Automatic Air Vent to let off this large volume before it enters the tank. I have not found one in hrs of internet searching and letters written to suppliers and Manufacturers. Can you help?

I put in a larger Vacuum breaker to help the water drain back to . the Snifter Valve was too small and the water risked freezing in the pipe as its only possible to cover the pipe 18" over some of the Granite on it way back to the Well On 2020-10-18 by James

Solution by (mod) -

James

Thanks, that's an interesting well problem to figure-out.

Usually an air-release valve on the AVC on the pressure tank is there specifically to release the excessive air that may be sent back to the pressure tank from the snifter valve system at each pump-on cycle.

If that valve is present and working on your AVC then there ought not be a problem of too much air in the tank.

So what's left is the annoying noise of air entering the tank bottom?

Have I misunderstood something?

by James

And the Sulfur and taste has gone away in my water. That could be that I use more water now and the well does not sit unused for weeks and months at at a time

yes the noise is the biggest problem , If I am not going to have too much air in the tank. It seams like over 130 feet of 1" pex holds too much air volume for the small AVC on the tank to handle.

The larger vacuum breaker was my well guys suggestion so that in very cold days the water drains back faster.

I was over thinking it and in the warmer months . just shut off the Vacuum breaker . snifter valve and keep the pipe Full.

by (mod)

Interesting;

I just spent the day learning about another way that all this air can be vented back to the well in a drain-back system; you might want to take a look at

MORRISON WELL SYSTEM FUNCTION & REPAIR

 

Weep holes in well piping prevent conversion from bladderless to a bladder type water pressure tank?

My well guy told me that there are "weep holes" in the well pipe that is deep in the ground. It's expensive to pull a well pump and seal those weep holes so I really have to stay with a bladderless system.

The home improvement places do not carry bladderless tanks anymore but they are still available. - Anonymous

Reply: Your well guy may have been referring to a snifter valve that needs removal if changing to an internal bladder water tank

Anonymous: frankly I'm unclear why the system you describe would make one iota of difference between choosing a bladder-type or bladderless water pressure tank.

In either case the tanks have the same working effect on the plumbing system.

Leaky well piping should be replaced

If your well piping is leaking and you are losing tank pressure back into the well after the pump shuts off, the proper repair is to replace the leaky well line (saving burn out of the pump), though you could try installing a check valve above ground on the line that returns to the well. Review this with an experienced plumber so you get it right.

Snifter valves for air volume control need to be discontinued if changing to an internal bladder water pressure tank

However, it is certianly true that on some submersible pump installations that used a bladderless water pressure tank, a snifter valve system was used to maintain the air volume in the water pressure tank.

The snifter valve system can include an air inlet valve above ground near the water pressure tank and an air inlet and water drain outlet port that is installed on a special fitting on the water riser pipe inside the well. Where a snifter valve system is installed it needs to be removed when changing to an internal bladder water pressure tank.

We discuss snifter valves on wells and water pressure tanks in detail at SNIFTER & DRAIN BACK VALVES

 

What's the purpose of this air valve on our well casing?

I have pump short cyclying - pressure guage moves between 35 - 60 in 5 seconds. The pressure tank is buried outside the house. House was built in 1971.

How do tell what type of valve it is? See attached impage

How to drain water out of a buried tank? Or add air to it ?

Here’s the image of the valve.

Thanks! On 2020-06-06 by Jean

by (mod) - air valve located at the well casing: what for?

Jean:

If the rusty pipe we see in the center of your photo, to which the black-capped schrader valve is attached, is connected to a buried water pressure tank it may have been for restoring the air charge to a bladderless water pressure tank buried near your well

- an unusual and in my opinion poor installation as it makes servicing the tank or replacing it expensive and it may reduce the tank life (by burying it).

If this is the case you'd simply use a canister of air or even a simple bicycle pump to add air to your pressure tank by connecting the pump or tank to the Schrader valve shown in your photo (yellow arrow added by us).

If the air valve is connected simply to a pipe teed off of the well piping between the well casing (at left in your photo?) and the house, it could be an air inlet valve like the snifter valves discussed on this page. .

Can you confirm that your water tank is really buried near the well?

For diagnosing a pump that turns on and off too rapidly see the advice

at WATER PUMP SHORT CYCLING

Adding that from your earlier comment I infer that your water pressure tank is waterlogged or has lost its air charge.

 

Do I have to use a bladderless water tsank if I have a drain back setup on my well piing?

Drainback well system parts as illustraged by Dean Bennett Supply in Denver CO cited & discussed at InspectApedia.comIs a bladderless pressure tank (instead of bladder tank) required for using with a "drain-back" set up for water piped from a well I have an existing tank that is failing. It is in a cold climate. It is set up as a "drain back" system, so it has a Schrader valve.

When the tank reaches its max psi, the pump shuts off, and the Schrader valve allows the water to drain back from the tank and back down into the well.

The pressure tank in a shed 20' from the well head. The 20' of horizontal underground pipe to the well head is NOT below frost line (too much underground rock). That's why there is the drain-back apparatus. The tank is old and corroding; needs to be replaced.

QUESTION: I think, for a "drain-back" set up, you HAVE to use a bladderless tank. Is this correct? Any recommendations for a brand/model? Thank you for any info you can provide. On 2019-11-27 by archbald

Answer by (mod) - what type of water tank works with a drain-back freeze-proofing system?

Arch.

This illustration of the key parts of a snifter-valve and drain-back system is adapted from Dean Bennett Supply in Denver, Colorado - retrieved 2019/11/26 original source: www.deanbennettsupply.com/drain-back-pressure-tank-systems.html

Of course you should be able to find all of these parts at your local well and plumbing supplier as well.

www.deanbennettsupply.com/drain-back-pressure-tank-systems.html

Case 1: need a drainback system to avoid freezing water pipes:

Yes, Arch, with a drain-back well pump and tank system, the drain-back components (air control at the tank, snifter valve, drainback valve in the well) work together with a bladderless pressure tank.

The components for a drain-back well pump system include:

(1) a well pump pressure control switch and

(2) brass nipple to mount the switch on well piping, at the pressure tank, or on the check valve (4)

(3) the snifter or air inlet valve, a schrader type valve or air valve that permits air to enter the well piping at the end of a pump-on cycle; this valve also often mounts on the tank or right on the check valve (4)

(4) a check valve that prevents water in the pressure tank (and house piping) from all draining back into the well

(8) a drain-back tee that is installed on well piping in the well, above the high water line

(8) a drain-back valve that allows water to drain out of the tee and into the well at the end of a pump-on cycle.

(not shown) a bladderless (no internal bladder) water pressure tank

I would stay with a bladderless pressure tank; otherwise you may find (using an internal-bladder type tank) air discharge at the fixtures every time your system cycles on and off.

Also see this older and less-common drain back system:

MORRISON WELL SYSTEM FUNCTION & REPAIR

Case 2: don't need drainback: (on an well system whose water pipes are all below the frost line)

On an older well that used a drainback system we demonstrated that one can use a pressure tank that uses an internal-bladder;

However when converting that older set-up that previously used a bladderless water pressure tank we had to remove the drain-back valve that's found in the well on the well piping riser.

Above is a photo of the key parts of a snifter-valve and drain-back system, sold by Dean Bennett Supply in Denver, Colorado (but of course you should be able to find all of these parts at your local well and plumbing supplier)

See more details at

DRAIN BACK & SNIFTER VALVE OPERATION

 

Can I install a drainback and snifter valve on a bladder type water tank?

Can you install a drain back valve and sniffer valve with a bladder tank? On 2018-11-22 by gary osterman

Solution by (mod) - it's possible: here's what will happen

Gary,

The purpose of a snifter valve is to keep the air charge in a water pressure tank for pressure tanks that do not use an internal bladder.

Therefore you would not normally use a snifter valve on a bladder type tank water system.

However if you need to install a drain back system in order to prevent frozen water pipes to a well it may be possible to install both the drain back valve in the well and the snifter valve on well piping inside the building near the water pressure tank.

What will happen is excess air will be sent by that system into the water portion of the bladder tank. That are in turn will eventually emerge at faucets and fixtures when you run the water.

So it's a rather hybrid system. I think that would work but if I were going to install that I would discuss the plan with the tank manufacturer because they may have a suggestion about venting some of that excess are ahead of the fixtures.

 

Is it true that snifter valve air volume control systems can remove iron and sulphur from water?

Hello I am writing about the snifter valve. If you read your article on why are snifter valve air volume control systems used one it states that the high absorption of air into the system helps oxidize and thus reduce hydrogen sulfide or perhaps iron.

But in your last email to me you said it would not. So you have me confused. Thanks for your reply. JOE (Jan 22, 2014) joe

Reply: no

Thanks so much Joe, I will review these articles and fix that inconsistency.

Honestly, I am sure that I added the statement to which you refer while I was reviewing research about snifter valves, but in replying to your email I simply forgot about it.

You were right, I was mistaken. However we need some clarification:

A snifter valve is only used on deep wells that are operated by a submersible pump AND that feed water into an older-style bladderless expansion tank. The snifter valve, installed in the well piping lets air into the system at each pump on cycle.

A companion vent valve installed above ground, close to the pressure tank, or in some cases ON the pressure tank, vents excess air out of the tank to keep the tank's air charge at the proper level.

A water supply system that uses a "captive air" type water pressure tank that incorporates an internal bladder does not need this automatic injection of make-up air, so will not have a snifter valve.

In fact when a plumber converts a water supply system from bladderless-tank to internal-bladder tank, s/he needs to also pull the well piping and remove the old snifter valve if one was installed. That is what was going on in my photo series about snifter valves.

So if your water system uses a bladder type tank you wouldn't have a snifter valve installed.

Finally, and here is where we need to do more research, despite the claims of the snifter valve camp, I am doubtful that air injection ALONE will cure a serious sulphur odor in the water supply. More likely we'll need to install a treatment system such as a potassium permanganate "green sand as the plumbers call it" system or a chlorine injection system, combined with filtration, or some equivalent.

Do keep me posted, and thank you VERY much for helping me out with clarity and pointing out an inconsistency on this topic.

 

To drain the water line I should open the cap on the snifter valve?

I recently had a new well installed, drilled w/ a submergible pump. a internal bladder tank was installed .

I was concerned about the water in the tank and water line freezing in the winter , so a sniffer valve was installed on the the check valve.

I was told when shutting the system down for the winter, to open and drain the water tank, and to open the green valve cap on the sniffer/check valve to introduce sir to the system , that would allow the water in the line to drain back into the well.

Will this advise work? is their any problem with the sniffer valve installed with an internal bladder water tank? thank You (Oct 13, 2014) Ray

Reply:

Yes there's a possibility that the advice you were given will work, Ray. But just removing a valve cap won't do it. That cap is supposed to be loose and able to admit air at all times.

You shouldn't have to open the snifter valve (found on a check valve usually mounted at the bottom of the water pressure tank) as it should open to admit air on its own - at the end of a pump-on cycle.

If your snifter valve is not working it probably needs a replacement. If you're replacing just the valve stem core don't buy one at your auto parts store - those schrader valves and valve cores operate at different (higher) pressure ranges and are not designed for this application.


...

Continue reading at DRAIN BACK & SNIFTER VALVE SYSTEM COMPONENTS or select a topic from the closely-related articles below, or see the complete ARTICLE INDEX.

Or see these

Recommended Articles

Suggested citation for this web page

SNIFTER & DRAIN BACK VALVES at InspectApedia.com - online encyclopedia of building & environmental inspection, testing, diagnosis, repair, & problem prevention advice.

Or see this

INDEX to RELATED ARTICLES: ARTICLE INDEX to WATER SUPPLY, PUMPS TANKS WELLS & SPRINGS

Or use the SEARCH BOX found below to Ask a Question or Search InspectApedia

Ask a Question or Search InspectApedia

Share this article:

Search the InspectApedia website

Need to make a private comment? Email editor@inspectApedia.com. We welcome email with your website content critique, corrections, suggestions or questions. Email is monitored daily but our workload may prevent an immediate reply. For immediate results, we hope you'll first try asking your question using the search box just above.

Citations & References

In addition to any citations in the article above, a full list is available on request.



ADVERTISEMENT