Building Inspection, Diagnosis & Repair Info

Dropping Water Pressure FAQs

Questions & answers on the causes of water pressure dropping off after the water pump has stopped.

Water pressure may fall a few psi and stop or it may continue falling. Why?

This article series describes how to diagnose slow water pressure loss and erratic well pump behavior. We give a step by step diagnostic procedure for falling water pressure trouble.

InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers, products, or services discussed at this website.

- Daniel Friedman, Publisher/Editor/Author - See WHO ARE WE?





ADVERTISEMENT





Q&A on pressure loss after the pump turns off

Causes of bad water pressureThese questions about diagnosing the cause of a slow fall-off in building water pressure when no water is being run (we think) were posted originally in the article above: WATER PRESSURE FALLS SLOWLY, ERRATIC PUMP - you will want to look through the causes and cures listed there.

Also see our index to all water pressure problem diagnosis and repair Q&A at WATER PRESSURE LOSS DIAGNOSIS FAQs

Article Index

...

Every time our water pump reaches cut off pressure the water pressure drops about 5psi, then stays there: Why?

The water pressure drops 5 psi every time it stops either at 50 or 60. If I set to 30/50, it stops at 50, then comes down to 45..at 40/60, it stops at 60, but comes down to 55... every time.

At first I thought there was a leak somewhere, but then I noticed the pressure will not keep going down.. I've left it for over 2 hrs and it will not continue to drop once it drops the 5 psi. So maybe there is no leak.

I have replaced the pressure switch and the gauge a couple of times with new ones and different models. Same thing.

This have driven me crazy for a very long time and I can't figure it out. On 2017-04-28 by Mac

by (mod)

How much does pressure fall? Could there be a toilet tank filling? Could there be a debris clogged, slow-to-respond pressure gauge?

by Chun

Mac, same exact thing is happening to me, it drops about 5psi then it stays there every time it reaches cut off, let me know if you have figured it out On 2017-07-08

Explanation by (mod) re: common reason for small pressure drop after the pump stops running

Chun and Mac:

I've seen this pressure drop at the end of a pump-on cycle and have corresponded with quite a few readers about it. Possible explanations for a fixed pressure drop at the end of a pump cycle are at WATER PRESSURE FALLS BRIEFLY THEN STOPS

I've seen this pressure drop at the end of a pump-on cycle too. When pressure remains steady afterwards we know it's not an actual water leak. Or we think so.

I've always figured it was an artifact of the particular pump, piping arrangement, controls - and not something that I think needs fixing. It's probably nothing to do with the switch - more likely the tank and piping and an air cushion somewhere.

But there is another possibility: a very small pinhole leak in the flexible rubber bladder in the pressure tank may open enough to pass a few psi worth of water at your cutoff pressure - say 50 psi - then as pressure drops even a little - to say 45 psi - the hole closes enough that any remaining leakage is so slow that you don't notice it.

You'll eventually find this problem - if it is what's happening in your case - when over time the water pressure tank becomes waterlogged even though with an internal bladder that should not occur. It will show up as

- pump cycles on and off increasingly frequently even though the water usage rate remains unchanged (in a test case)
- the water pressure tank becomes heavier when tested "empty" - with pump off and all pressure drained from the system via nearby taps the pressure tank has more weight than when new

A less-likely possible explanation is that pressure during pumping is, after the pump stops, converted to an expansion of plastic parts or a tank bladder component that absorbs a bit more of the system pressure.

Also see BOYLE's LAW where we explain P1V1 = P2V2 at constant temperature

...

Water Pressure Keeps Falling Slowly After Pump Stops

We have a drilled Well 16yrs old. Previous owner said 400+ ft. I had a short cycle issue that was resolved by re-pressurizing the tank. Pump now works 40-60 as expected and tank is holding the expected air pressure.

I then noticed a slow leak of water pressure while I was correcting the short cycle.

Symptom: Gauge at well shows about 62 when pump stops.

Then settles down to 59. I assume that much play in gauge is OK given it is a $6 part.

Water pressure then slowly drops at a slightly variable rate over hours. 15 lbs-9 hrs, 5 lbs-6 hrs, 7 lbs-6.5 hrs, etc.

I can turn off the flow to the house at the well and the well and tank holds water pressure constant at 59 lbs for 6 hours.

That leaves me to believe that the drilled well itself (foot valve, piping, etc..) is OK. I don't see any signs of leakage in my home (no visible water, no toilet leak,etc..), but to make sure, I turn off the water as it enters the house and have similar drop rates in pressure as listed above.

That leaves me to believe I have a slow leak in the yard line between the well and the home. Does that sound right? Of course there is no visible evidence of a leak, and that line crosses the sewage, power, phone/internet and propane gas line before it enters the home as the builder was apparently not a good planner.

Question: My tank at the well is supposed to produce a 5 gal draw down at 40/60. So, if I let the well pump 60lbs then open the faucet at the well and let it run in a bucket until the pump kicks back on, I should expect to fill up a 5 gal bucket? So I did that after 6 hours and had about 2 gals in the bucket.

So, I'm leaking 3 gals in 6 hours correct? I don't know much about this, but I assume if the water pressure drops that the water had to go somewhere even I can't find the leak. I don't understand how air could leak into the system, but I've had several people and couple of articles on this site indicate that air might be leaking into the system. Any comments or suggestions? (Nov 14, 2014) Tim2014

Reply: look for a slow leak or water usage in the building such as a running toilet

Tim

A slow leak of water out of the piping anywhere between well bottom and building water equipment including leaks or water running in the house can leak both water out and in some circumstances air in to the system.

Usually we look first for a bad foot valve or check valve. But if you shut of water going into the house and pressure in the rest of the water system holds steady, that tells me that the leak is in the house, not in the well piping nor foot valve.

So you should look first for a slow-running toilet. That can be tricky to spot as if the toilet flush valve leak is small, you may not notice it by simply taking a quick look in the toilet bowl or tank.

See our detailed diagnostic procedure at TOILET RUNS CONTINUOUSLY 

More clues and sources of hard-to-find water line leaks or check valve leaks are at WATER PUMP INTERMITTENT CYCLING

 

Water pump shuts off, then pressure drops, 20 minutes later pump comes on

I have a double line jet pump system. The cut in is 30 and off is 50 on pressure switch.

The problem is as soon it shuts off, the pressure drops, takes about 20 minutes then cycles again.

We installed a check flow valve at the pump, thinking water was flowing back down to well. That didn't solve it. What could be the problem? (Mar 28, 2013) janet

Reply:

Janet,

It should be pretty easy to determine if the leak is in the building, at the pump and water tank, or in the well piping. If you shut off all water entering the building and pressure drops, the problem is not a leak in the building.

If your check valve is absolutely perfect, or if you use a temporary shutoff valve between the pressure tank and pump and the well itself, and pressure drops, there is a leak on the pump and tank side of that valve.

See more causes and solutions of this problem at WATER PUMP INTERMITTENT CYCLING

 

...

Continue reading at WATER PRESSURE FALLS SLOWLY, ERRATIC PUMP - topic home, or select a topic from the closely-related articles below, or see the complete ARTICLE INDEX.

Or see these

Recommended Articles

Suggested citation for this web page

WATER PRESSURE FALLS SLOWLY FAQs at InspectApedia.com - online encyclopedia of building & environmental inspection, testing, diagnosis, repair, & problem prevention advice.

Or see this

INDEX to RELATED ARTICLES: ARTICLE INDEX to WATER SUPPLY, PUMPS TANKS WELLS

Or use the SEARCH BOX found below to Ask a Question or Search InspectApedia

Ask a Question or Search InspectApedia

Share this article:

Search the InspectApedia website

Need to make a private comment? Email editor@inspectApedia.com. We welcome email with your website content critique, corrections, suggestions or questions. Email is monitored daily but our workload may prevent an immediate reply. For immediate results, we hope you'll first try asking your question using the search box just above.

Citations & References

In addition to any citations in the article above, a full list is available on request.



ADVERTISEMENT