Building Inspection, Diagnosis & Repair Info

White Rodgers Type 1311 heating zone control valve wiring diagram and principles of operation cited & discussed at InspectApedia.comWhite Rodgers HVAC & Control Manuals

This page provides company contact information and free PDF downloads of manuals for many White Rodgers HVAC system controls and components used in heating, air conditioning, and other applications.

Page top: wiring details for White Rodgers aquastat No. 1131. [Click to enlarge any image]

InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers, products, or services discussed at this website.

- Daniel Friedman, Publisher/Editor/Author - See WHO ARE WE?





ADVERTISEMENT





White Rodgers Controls - Emerson White Rodgers

White Rodgers aquastat No. 1131 at InspectApedia.com

Illustration: White Rodgers Aquastat No. 1131-102.

[Click to enlarge any image]

...

White Rodgers Manuals by Product Group / Type

White Rodgers Cad Cell Relay Instructions

White Rodgers Fan Limit Control Manuals

White Rodgers 5D Fan Limit control at InspectApedia.com

Below: White Rodgers Manual Reset Snap Disc Limit Control L200 3L02-200

- opens at 200 degF / 93 degC. Similar controls are the WR 3L02-190, WR 3L02-180 and WR 3L02-170

White Rogers  Manual Reset Snap Disc Limit Control L200 3L02-200 from mccombsupply dot com - cited & discussed at InspectApedia.com

White Rodgers Manual Freeze Protection Control

White Rodgers freeze protection control for cooling equpment - cited & discussed at InspectApedia.com

Above: White Roders Manual Freeze Protection Control, can be set to -20 degF up to + 50 degF, used to shut down cooling systems and equipment to protect against too-low temperatures. Flexible tubing connects remote temperature sensor probe.

White Rodgers Gas Valves & Flame Sensor Instructions

White Rodgers 36-C gas valve cited & discussed at Inspectapedia.com

White Rodgers gas pilot igniter system replacent parts, wiring at InspectApedia.com

Above: White Rodgers gas pilot ignition system replacement parts.

 

White Rodgers Ignition Control Modules & Isolation Relays

White Rodgers isolation relay at InspectApedia.com

 

White Rodgers Thermostat Manuals

White Rodgers 1F90 room thermostat cited & discussed (C) InspectApedia.com

White Rodgers  1F90-97 thermostat wiring detail cited & discussed at InspectApedia.com

Above: an example White Rodgers 1F90 thermostat wiring detail excerpted from the guide above.

White Rodgers Zone Valve Installation, Wiring, & Operating Manuals

...




ADVERTISEMENT





Reader Comments, Questions & Answers About The Article Above

Below you will find questions and answers previously posted on this page at its page bottom reader comment box.

Reader Q&A - also see RECOMMENDED ARTICLES & FAQs

What's a replacement for an old White Rogers Fan Relay Control Type 5A75-46, Style V2PIYZ ?

Have an old furnace that works fine. I'm concerned that the fan relay in the White Rogers control (Type 5A75-46, Style V2PIYZ) might fail. Does anyone know of a replacement? On 2019-05-17 by John H

by (mod) - replacement for limit control White Rogers control (Type 5A75-46, Style V2PIYZ)

John a search of InspectApedia using the search box just above to look for FAN LIMIT SWITCH UNIVERSAL REPLACEMENT

finds FAN LIMIT SWITCH INSTALLATION & WIRING at https://inspectapedia.com/heat/Fan_Limit_Switch_Installation_Wiring.php

where you will find HONEYWELL L4064B, L4064R UNIVERSAL COMBINATION FAN & LIMIT CONTROLLER INSTALLATION MANUAL [PDF] (2017) [*** A LIVE LINK to this PDF is on the page I cited above ***]

Honeywell 1985 Douglas Drive North Golden Valley, MN 55422-3992 customer.honeywell.com

This L4064B, L4064R limit controller is a universal replacement for older furnace fan limit controllers. Here is the difference between the L4064B and L4064R, excerpting from the document above:

These combination warm air fan and limit controllers are suitable for various types of forced air heating systems. The controllers have 2 switches; one which opens the limit circuit if the plenum temperature exceeds the preset safety limit; it resets automatically. The other switch turns the fan on and off.

The fan is turned on and off according to plenum temperature.

The L4064R has a special high temperature range suitable for gravity heating systems.

All models may be used as limit controllers by wiring only the limit side. Limit contacts are suitable for both line voltage and low voltage. For low voltage applications, the brass jumper must be removed.
...
Follow furnace or burner manufacturer’s instructions, if available.

Maximum element temperature is:

L4064B—350 ºF (177 ºC).

L4064R—250 ºF (121 ºC) above limit setting.

Maximum switch temperature is: L4064B,R—190 ºF (88 ºC).

 

Where to find specs for oil burner setup for a White Rodgers NuWay Oil Burner?

Am i the only one on this planet with a Miller gun White Rodgers Nu Way oil burner?

Can't find specks any place trying to find specs for electrodes and replacements giving up

This Q&A were posted originally

at OIL BURNER ELECTRODES On 2019-10-17 by Chip

by (mod) - find specs & manuals for White Rodgers NuWay Oil Burner

OIL BURNER MANUALS under "N" you'll find two NuWay oil burner manuals

and also see

MANUALS & PARTS GUIDES - HVAC

 

White Rodgers 1F80-261 settings for summer weather

I have a programmable thermostat, White Rodgers 1F80-261. Researching what temperature to set the thermostat in summer, it has recommended the following:

"Normal cooling settings are 75 degrees - 80 degrees. Normal heating settings are 68 - 72 degrees.

You should always set your thermostat to the highest possible setting that is comfortable for you in the summer, and the lowest setting in the winter".

Could you explain the rationale for setting the thermostat to the highest possible setting when the room temperature is already hot in summer? Wouldn't this make the room increasingly hot?

Currently, I have a gas furnace but no air-conditioning for the house.

This Question was posted at FAN ON AUTO MAN Thermostat Switch On 2018-07-18 by Sam -

by (mod)

Good question, Sam

What the instruction writers intended to say was that you can minimize your cooling cost by not setting the indoor temperature to a lower number than that at which you'll be comfortable.

 

White Rodgers 1F80-0471 thermostat repair

I had to change the batteries of my White Rodgers 1F80-0471 thermostat. I pulled the unit off the wall, changed the batteries and put the unit back on the wall. Didn't realize the battery door is on top and didn't need to pull the whole unit off.

Now, my fan won't stop running. I shut off the A/C switch in the breaker box, also shut off the furnace switch. Still running. I went into my utility room and had to switch the main furnace switch off to get the fan to stop

How can I fix this? - On 2017-06-02 by Deanna

Reply by (mod) - Check that the White Rodgers thermostat batteries are good and facing the right way

Deanna you want to check that the batteries are good and that you placed the + and - marked-terminals of the batteries facing the right way, matching the +/- terminals in the thermostat

 

Replaced a White-Rodgers hot water relay with a Honeywell 8124 - no power at C1 C2 (circulator circuit)

Replaced a White-Rodgers hot water relay with a Honeywell 8124 because I had no power across C1 and C2 and suspected the relay was bad. I still have no power across C1 and C2. I have four H/W radiation zones, one circulator pump for the entire house. Can you advise? - (Jan 6, 2016) Wayne

Reply:

Wow that's too bad. You replaced the entire control, so the problem is likely to be outside the control, in the power circuit to the control, to the circulator, or at the thermostat.

Try eliminating the thermostat from the equation by removing its wires and jumping the two TT connections right at the control. That should turn on the circulator. If it does the problem is in the thermostat or its wires.

 

Do I need an external transformer to wire up White Rodgers zone valves?

I am trying to wire 2 white Rodgers zone valves ( 1361-104) that are currently not wired. The thermostat is wired directly to the boiler ( mini therm 2 jvt125n) not sure if I need an external transformer to power them. Any help will be highly appreciated - On 2015-12-18 by Howard

by (mod) -

The existing 24VAC transformer used by your boiler for the existing thermostat may be sufficient.

Also see the zone valve instructions for your WR 1361 zone valve listed as a PDF download

above on this page

 

Need replacement for White-Rodgers Type 5A75-5 Style V2QP1Y Fan and Limit controller.

I have an old warm air furnace that uses White-Rodgers Type 5A75-5 Style V2QP1Y Fan and Limit controller.

This model is discontinued and I cannot find them anywhere. Is there a direct replacement either from White-Rodgers are from any other major brand? On 2015-11-20 by Peter

by (mod)

Peter

You may be able to use a Honeywell fan limit switch "universal" model if it is of proper dimensions, particularly it has to fit in the location of the old one and its probe has to extend properly into the plenum;

See this HONEYWELL L4064B UNIVERSAL FAN & LIMIT CONTROLLER SUPER TRADELINE INSTALLATION INSTRUCTIONS [PDF] (2006)

 

 

White Rodgers M150 thermostat heat cycling on and off when it should not

I just got a new white Rodgers m150 thermostat and the furnace states a .75 anticipator heat setting so we set it at that and it comes on and off 3 times more now with this thermostat
so we set it to the high setting that it has of 1.2 and it still cycles way more than the old one ? (Dec 6, 2014) dave

Reply:

Dave let's see if we can figure out why the thermostat is cycling heat more often: here are some things to check

- possible cold draft - e.g. through the wall

- loose wire or connection in the tt circuit is shorting

- colder weather conditions

- a service issue with the furnace

- a defective thermostat

- something else we've not considered

If you have the old TT and can reinstall it, if that behaves the same way as the new one (frequent cycling) then the issue is not in the thermostat itself

...

Continue reading at THERMOSTAT WIRING WHITE RODGERS, or select a topic from the closely-related articles below, or see the complete ARTICLE INDEX.

Or see these

Recommended Articles

Suggested citation for this web page

WHITE RODGERS CONTROLS & MANUALS at InspectApedia.com - online encyclopedia of building & environmental inspection, testing, diagnosis, repair, & problem prevention advice.

Or see this

INDEX to RELATED ARTICLES: ARTICLE INDEX to AIR CONDITIONING & HEAT PUMPS

Or use the SEARCH BOX found below to Ask a Question or Search InspectApedia

Or see

INDEX to RELATED ARTICLES: ARTICLE INDEX to HEATING SYSTEMS

Or use the SEARCH BOX found below to Ask a Question or Search InspectApedia

Ask a Question or Search InspectApedia

Share this article:

Search the InspectApedia website



Comments & Questions are Welcome Here

If you posted comments here and no longer see what you wrote, please check for your comment in the Reader Q&A found above on this page.

Citations & References

In addition to any citations in the article above, a full list is available on request.



ADVERTISEMENT