Building Inspection, Diagnosis & Repair Info

Frank Adam Electric Co. Panel, (C) John Weber Hartford HSB cited at InspectApedia.comFrank Adam Electrical Panel Hazards

  • POST a QUESTION or COMMENT about Frank Adam Electrical Panel Safety, buying, repairing, replacing Zinsco electrical panels & parts

Example photos of Frank Adam panels, a split bus panel design, and Frank Adam panel identification labels.

This Frank Adam electrical panel article gives the history of the Frank Adam electrical company and also discusses the electrical, fire, and shock hazards associated with Frank Adam electrical components, circuit breakers, electrical panels, including the incorporation of Frank Adam and Zinsco circuit breaker design and components.

Page top photo: an older Frank Adam electrical panel still in use in a U.S. home.

InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers, products, or services discussed at this website.

- Daniel Friedman, Publisher/Editor/Author - See WHO ARE WE?





ADVERTISEMENT





Frank Adam Electrical Panels & Advice for Homeowners and Home Buyers

Frank Adam split bus electrical panel (C) InspectApedia.com Lawrence Transue home inspectorFrank Adam electrical panels, shown here, do not offer the level of overcurrent and fire protection provided by most other electrical panels and circuit breakers.

Independent test results show that Frank Adam circuit breakers had a significantly higher failure rate than most other electrical panel brands.

Photo: a split-bus Frank Adam electrical panel, courtesy Larry Transue.

[Click to enlarge any image]

In addition to the circuit breaker failure rates in Frank Adams panels, at least some Frank Adam electrical panels are of the split bus design, as illustrated later in this article in a photo courtesy of ASHI inspector Larry Transue and other home inspectors (cited below).

A "split bus" electrical panel is one in which circuit breaker connections are configured so that a group of breakers in the upper panel include one or more that provides power to an electrical bus in the lower half of the electrical panel.

In other words, there may not be a single "main breaker" that will turn off all electrical power.

Using a different brand (Cutler Hammer), the safety concern with split bus panels is detailed

at SPLIT BUS ELECTRICAL PANEL HAZARDS

Watch out: OPINION: we do not recommend installing "replacement" Zinsco circuit breakers as there some indications that the performance and safety of those devices may be poor.

Frank Adam Electrical Panel & Breaker Failure Rate Test Results

Limited test results reported by Dr. Jess Aronstein indicate that the central Zinsco electrical panel and circuit breaker failure problem appears to be burn ups at the clip-to-bus connections such as shown in our photo of a burned Zinsco electrical panel bus and breaker.

Zinsco breaker burnup (C) J P Simmons & D J Friedman

A circuit breaker whose bus connection burns can lead to overheating damage to the circuit breaker itself, rendering it non-functional.

For a summary of Frank Adam, Zinsco and UBI-Zinsco-Replacement circuit breaker test results to date,

see ZINSCO CIRCUIT BREAKER TEST REPORT - separate article.

Also see ZINSCO FAILURE REPORTS where we indicate that nearly 32% of the Zinsco circuit breakers tested to date failed to trip as required by the UL testing standard.

A very small sample of UBI-brand replacement circuit breakers for Zinsco panels also failed to trip.

Photo at page top of a burned and failed Zinsco main circuit breaker, courtesy of J. P. Simmons - Mr. Electric. Simmons adds: "In this case the failure damaged the main wire to a mobile home also (you can see the melted wire to the left of the main).

This is a good example of why I do not like to see anyone remove these breakers. You can not tell how bad they are damaged by looking at them.

With the exception of the more seriously failing FPE Stab-Lok electrical panels, we have not received any significant number of field failure reports concerning other electrical panel brands that also use aluminum parts and that are or were priced in the same range as Zinsco.

This means homes with this equipment may be at greater risk of fire or other electrical hazard.

Frank Adam Electrical Panel Replacement Recommended?

Photo of a Zinsco type circuit breaker with arc burning (C) Daniel Friedman at InspectApedia.com

Where a Frank Adams electrical panel uses Zinsco-type circuit breakers (shown in the photo above) is in use, arcing, contact-point burn, and even circuit breaker case blow-out have been observed in the field.

We do not have statistically solid data that supports an unequivocal argument to replace Zinsco electrical panels.

OPINION: However, based on field reports to-date and preliminary tests, where these electrical panels are discovered in buildings a homeowner should consider replacing the panel to reduce fire and shock hazards and owners should be careful to avoid overloading their electrical circuits where this equipment is installed.

Building owners or electricians encountering problems with this equipment are asked to contact us to add that information to our electrical failure data base in an effort to develop accurate safety information which is then shared with appropriate federal and state agencies.

Thanks to Mr. James Simmons, a licensed electrician with extensive field experience and the contributor of most of the photos and case reports at this web page.

Our photo (above left) illustrates a burned-up electrical receptacle whose circuit was protected by a Zinsco-design circuit breaker that failed to trip and in fact had burned itself in the panel.

Frank Adam Electrical Panel History, Age, Dates & Patents for Zinsco Electrical Panels & GTE-Sylvania Zinsco Electrical Panels

Frank Adam Electric Co. Panel, (C) John Weber Hartford HSB cited at InspectApedia.com[Citations needed, use the page bottom CONTACT link if you can provide additional data - Ed.]

This article series discusses the electrical, fire, and shock hazards associated with Zinsco electrical components, circuit breakers, electrical panels, including certain Sylvania electrical panels and breakers which are in fact of the same product design and origin.

Zinsco-type QSF electrical panel circuit breakers may also appear in Frank Adam Electric Panelboards.

The following history giving key dates in the history of Frank Adam electrical panels is excerpted from a more-detailed history given

at ZINSCO SYLVANIA ELECTRICAL PANELS

That the presence of Frank Adams, the Frank Adam electric company, and its employees were a major factor in the development of electrical panels is evident in the list of patent disclosures and other documents we list just below, starting in 1891.

Frank Adams Fuse Panel circa 1929 (C) InspectApedia.com

The above photo is of a FA panel that was still in service when reader Steve bought an Architect designed, vintage 1929, house in Oakland CA in 2008. The first item to be up graded was the electric system including the box.

Specifics of the box are:

Underwriters  Lab Tag-
Panel board number 503849
Patent Applied for
150 Amps
Frank Adams Electric Tag-
Fuselok Switch
125/250             60amp

Frank Adams Electric
St Louis Mo

Frank Adam PULFUZSW electrical panel in Fort Wayne Indian, (C) InspectApedia.com Eugene Knuth

Photo above: A Frank Adam PULFUZSW electrical panel in a 1956 Indiana home, showing a fused main current overload protection dev ice above its two columns of circuit breakers.

Photo courtesy of Fort Wayne, Indiana home inspector Eugene Knuth @ EKnuth.homeinspections@gmail.com Tel: 260-385-2536

Frank Adams PULFUZSW for sale on eBay in January 2026; circuit breakers in panels for which this may be the main fuse continue to have safety concerns - cited & discussed at InspectApedia.com

Above and below: examples of main fuse pullouts in Frank Adams PULFUZSW and KLAMPSWFUZ electrical panels that we found for sale on eBay in January 2026.

Frank Adams PULFUZSW for sale on eBay in January 2026; circuit breakers in panels for which this may be the main fuse continue to have safety concerns - cited & discussed at InspectApedia.com

Watch out: while fuses won't have the same safety concerns as the circuit breakers in these Frank Adams electrical panels, the circuit breaker hazards are still present.

Frank Adams KLAMPSWFUZ for sale on eBay in January 2026; circuit breakers in panels for which this may be the main fuse continue to have safety concerns - cited & discussed at InspectApedia.com

Above: the identification label for a Frank Adams KLAMPSFUZ fuse panel - for sale at eBay in January 2026, and below, the internals of the fuse pullout.

Frank Adams KLAMPSWFUZ for sale on eBay in January 2026; circuit breakers in panels for which this may be the main fuse continue to have safety concerns - cited & discussed at InspectApedia.com

Frank Adams electrical panels in Satelitte Beach Florida Condominium constructed in 1964, (C) InspectApedia.com doublescope Inspections

Notice that there is no main circuit breaker in these electrical panels and that unless such a switch is quite close-by they violate the "rule of six".

Frank Adams electrical panels in Satelitte Beach Florida Condominium constructed in 1964, (C) InspectApedia.com doublescope Inspections

Given that the inspector found these Frank Adams panels we both suspected that most of the other condos in that building have the same unreliable electrical panel. 

Frank Adams electrical panels in Satelitte Beach Florida Condominium constructed in 1964, (C) InspectApedia.com doublescope Inspections

...




ADVERTISEMENT





Reader Comments, Questions & Answers About The Article Above

Below you will find questions and answers previously posted on this page at its page bottom reader comment box.

Reader Q&A - also see RECOMMENDED ARTICLES & FAQs

Photos of Frank Adam Split Bus Electrical Panel & ID Label

Special thankyou to professional home inspector Lawrence Transue for these photos of a Frank Adam Split Bus electrical panel and of the Frank Adam panel identification label.

Frank Adam split bus electrical panel (C) InspectApedia.com Lawrence Transue home inspector

This Frank Adam panel was found in a Stewartsville NJ home constructed around 1760, thus giving range to several generations of history of devices used in the home's electrical service.

Below: an identification label in this Frank Adam electrical panel, perhaps from the 1960s.

Frank Adam electrical panel identification label (C) InspectApedia.com Lawrence Transue cited

Mr. Transue is a technical content contributor to InspectApedia.com.

Evidence that this Frank Adam electrical panel does Not use Zinsco-Design Breakers:

Detail of Frank Adam copper bus not-Zinsco electrical panel (C) InspectApedia.com Transue

Watch out: see details of potential hazards of split bus electrical panels

at SPLIT BUS ELECTRICAL PANEL HAZARDS

See details about Frank Adam Electrical panels and their role in the Zinsco history beginning remarkably in 1891 and extending at least to 1965, found

at HISTORY of ZINSCO ELECTRICAL PANELS

The failure rate of Frank Adam circuit breakes is detailed

at CIRCUIT BREAKER RELIABILITY TESTS

Lawrence Transue is a Pennsylvania building scientist and consultant, a certified ASHI home inspector, a Licensed Pesticide Applicator, a BPI Building Analyst & Envelope Professional, with 18 Years of Home Inspection Experience. He can be reached by Telephone: 610.417.0763, by Email: lawrence@lawrencetransue.com as well as at his WEBSITE and at FACEBOOK

 

Identify this Electrical Panel: Frank Adam Electric Co. Brand

Can you identify the panel brand shown in the attachment? - JW by private email 2019/06/12

Frank Adam Electric Co. Panel, (C) John Weber Hartford HSB cited at InspectApedia.com

Moderator reply: Frank Adam panel, possibly using Zinsco breakers

I have not seen that emossed-front electrical panel, JW but I suspect it's a 1940's or 1950's era product.

Let's both research to see what we can find, perhaps trying a Google Image Match search. A logo or an internal label in the panel enclosure will be definitive.

I'll look further through my examples to see if I can spot anything similar.

Were you able to pull the panel cover to see if they were any labels inside? I also like the two broken toggle switches. Do we know anything about the age and location of the building where the panel is installed?

Watch out: those white colored toggle switches and long narrow breakers may be evidence that this Frank Adam panel uses Zinsco-design circuit breakers that are unsafe.

Ask your electrician to take a closer look at the circuit breakers in your panel and to compare them with this photo:

Characteristic deep notch in side of a Zinsco circuit breaker showing arc burns - this is an unsafe circuit breaker (C) Daniel Friedman at InspectApedia.com

See details at ZINSCO CIRCUIT BREAKER TEST REPORT

Reader Follow-up:

Found the answer to the panel inquiry if you are interested. See below:

Frank Adam Electric Co. Panel, (C) John Weber Hartford HSB cited at InspectApedia.com

Above: logo on a Frank Adam panelboard, Frank Adam Electric Co., St. Louis MO, USA

Watch out: intersting to readers who owned hazardous Zinsco electrical panels, we have this historical note from Wikipedia's Zinsco entry:

Frank Adam Electric, a manufacturer of electrical panels and circuit breakers, was founded in 1891 as part of the Blacker and Adam Watch Company in St. Louis, Missouri. ...

In 1943, Martin bought the company from his father and renamed it Zinsco Electric.

What is the life expectancy of a Frank Adams panel?

What is the life expectancy of a Frank Adams panel? On 2022-08-26 by kristeen lentvorski

by InspectApedia-911 (mod) - a Frank Adams panel is obsolete - past end of useful life

@kristeen lentvorski,

If you have a building with a Frank Adams electrical panel most inspectors would tell you it's long obsolete.

Details are at FRANK ADAM ELECTRICAL PANELS

Excerpting from that page you'll read:

Frank Adam electrical panels ... do not offer the level of overcurrent and fire protection provided by most other electrical panels and circuit breakers.

Independent test results show that Frank Adam circuit breakers had a significantly higher failure rate than most other electrical panel brands.

Question: Identify this Electrical Panel: Frank Adam Electric Co. Brand

Frank Adam Electric Co. Panel, (C) John Weber Hartford HSB cited at InspectApedia.com

Can you identify the panel brand shown in the attachment? - JW by private email 2019/06/12

Frank Adam Electric Co. Panel, (C) John Weber Hartford HSB cited at InspectApedia.com

Moderator reply:

Yes, that's a Frank Adams Electrical panel - obsolete.

See IDENTIFY FRANK ADAM ELECTRICAL PANELS

...

Continue reading  at GTE-SYLVANIA-ZINSCO FAILURE MECHANISM or select a topic from the closely-related articles below, or see the complete ARTICLE INDEX.

Or see these

Recommended Articles

Suggested citation for this web page

FRANK ADAM ELECTRICAL PANELS at InspectApedia.com - online encyclopedia of building & environmental inspection, testing, diagnosis, repair, & problem prevention advice.

Or see this

INDEX to RELATED ARTICLES: ARTICLE INDEX to ELECTRICAL INSPECTION & TESTING

Or use the SEARCH BOX found below to Ask a Question or Search InspectApedia

Ask a Question or Search InspectApedia

Share this article:

Search the InspectApedia website

Need to make a private comment? Email editor@inspectApedia.com. We welcome email with your website content critique, corrections, suggestions or questions. Email is monitored daily but our workload may prevent an immediate reply. For immediate results, we hope you'll first try asking your question using the search box just above.

Citations & Reviewers

In addition to any citations in the article above, a full list is available on request.

  • [1] Personal communication, J. Aronstein to D. Friedman, 3/6/2006.Dr. Jess Aronstein, protune@aol.com is a research consultant and an electrical engineer in Schenectady, NY. Dr. Aronstein provides forensic engineering services and independent laboratory testing for various agencies. Dr. Aronstein has published widely on and has designed and conducted tests on aluminum wiring failures, Federal Pacific Stab-Lok electrical equipment, and numerous electrical products and hazards. See Aluminum Wiring Bibliography and see FPE HAZARD ARTICLES, STUDIES for examples.
  • [2] James P. Simmons: Personal communication and photographs used in this article series, J. Simmons to Daniel Friedman, 3/4/2006, 2/19/2008. Photographs contributed to this website by Jim P. Simmons, Mr. Electric, Licensed Master Electrician, 1320 Dayton Street SE, Olympia, WA 98501, 360-705-4225, Fax 360-705-0130 or by email to mrelectricoly@msn.com
  • [6] Thanks to Texas electrician Jeff Weissman for contribution of photographs of burned Zinsco circuit breakers. 03/06/2007. Mr Weissman can be reached at jeffweissman@gmail.com or by telephone at 713-666-6605
  • intenance Enewsletter @ AFullHouseInspection.com -->
  • In addition to citations & references found in this article, see the research citations given at the end of the related articles found at our suggested

    CONTINUE READING or RECOMMENDED ARTICLES.


ADVERTISEMENT