Building Inspection, Diagnosis & Repair Info

Flare fittings on an LP gas line (C) Daniel Friedmanat InspectApedia.comHow to Install Copper Pipe Flare Fittings

This article series provides an updated version of Hubbard Cobb's Your Dream Home, illustrated by Sigman-Ward, first published by Wm. H. Wise & Co. New York, 1950.

Here we've added copper pipe flare fitting tools and methods current through 2024.

From site selection and obtaining financing through each step in construction of a single family home the simple procedures and drawings in this book are still useful for anyone building or repairing a home or other small structure.

 

InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers, products, or services discussed at this website.

- Daniel Friedman, Publisher/Editor/Author - See WHO ARE WE?





ADVERTISEMENT





How to Install Flared Copper Pipe Fittings

Photograph of a leaky brass flare fittingHere we discuss how to make copper pipe or copper tubing connections using flare fittings like the male flare connector end shown here.

Using a special flaring tool the soft copper tubing or piping is actually spread open or flared at its end in order to mate with the female end of the flare fitting connector shown in our photograph.

Watch out: defects in flare fittings used on flexible copper tubing can result in gas leaks out of gas piping, and in the case of oil piping such as for oil-fired heaters, flare fitting defects result in both oil leaks out of the system and air leaks into the system.

Our photo shows a line across the mating face of the male flare fitting - that caused a small gas leak that was hard to find.

This is a section of Chapter 13 of BUILD YOUR DREAM HOME at InspectApedia.com - online encyclopedia of building & environmental inspection, testing, diagnosis, repair, & problem prevention advice.

This article series provides an updated version of Hubbard Cobb's Your Dream Home, illustrated by Sigman-Ward, first published by Wm. H. Wise & Co. New York, 1950.

The link above provides versions of each chapter as a web page, as an ePub, and in the original form as a PDF file.

 

Figure 17: a completed copper flare fitting joint (C) (C) InspectApedia.com 2019.com 2019

Fig. 17. A completed flared fitting.

The other method of making up joints in copper tubing (besides soldering or crimping discussed

at COPPER PIPE INSTALLATION )

is to use the flared fitting. See Figs. 17 and 18.

Figure 18: interior view of a copper pipe flare joint (C) (C) InspectApedia.com 2019.com 2019

Fig. 18. The interior view of a flared fitting.

After cutting the tube, which is done in the same manner as for soldered fittings, the first step is to slip a sleeve nut on the section of tubing. See Fig. 19.

Figure 19: procedure for installing flare fittings on copper tubing or pipe (C) InspecctApedia.com 2019

Fig. 19. Slip the union nut over the pipe before you flare the pipe.

Figure 20: copper flaring tool or swaging tool (C) InspecctApedia.com 2019

Fig. 20. A flaring tool, shown above, is also referred to as a copper swaging tool. A similar tool can be used to swage or expand the end of copper pipe to make a slip joint connection that is soldered instead of using a flare fitting.

Note: while flaring tools like the one shown above are still used in some applications, below we show more-contemporary and much-easier-to-use copper tubing flaring tools.

Basic Steps in Making a Copper Tubing or Pipe Flare Joint Connection

With a bit of care it's easy to make flare joints, following the instructions that come with even an inexpensive flaring tool like the one I'll show below (less than $30. U.S.)

It's best to use a copper tubing cutter to make a clean cut of copper tubing or pipe.

First, here is a copper tubing cutter from Milwaukee.

Copper tubing cutter from Milwaukee - cited & discussed at InspectApedia.com

[Click to enlarge any image]

Below, using an image from Milwaukee Tools, we illustrate this tubing cutter in-use.

Copper tubing cutter from Milwaukee - cited & discussed at InspectApedia.com

After cutting the copper tubing, be sure to clean the edges of the tubing, both exterior and interior, before making the flare, otherwise your flare will be irregular and risks leaking - a dangerous mistake when installing gas piping.

Most tubing cutters include a retractable triangular blade used to trim out / off the burr left inside of the tubing - be SURE to do this before making the flare joint else your joint is likely to be un-even and leaky, risking an LPG explosion or fire.

Below is an example of another tubing cutter that shows the triangular blade you'll need to use to deburr or ream the interior of copper tubing after it has been cut.

Copper tubing cutter showing blade for reaming out the tubing lip formed by cutting - cited & discussed at Inspectapedia.com

A similar cutter used to de-burr both the copper pipe or tubing interior and exterior is shown below. This tool includes an outer reamer and an inner reamer. This example is made by Doact - properly-named a pipe hamfer tool or tubing burr removal tool or de-burring tool. Cost about $9.00 U.S.

Copper pipe or tubing deburring tool from Doact cited & discussed at InspectApedia.com used making flare or solder fittings.


I then use very fine sandpaper or steel wool to remove any oxide from the tubing exterior before making the flare. Or you can buy the special tool sold to clean off the end of copper tubing - one of those is shown below.

Below: tools used to clean the end of copper tubing, especially important before soldering. This copper tubing cleaner is made by Tofl tools.

tools used to clean the end of copper tubing before flaring, and especially before soldering. This copper tubing cleaner is made by Tofl tools - cited & discussed at InspectApedia.com

Then slide the flare fitting over the tubing,

Then make the flare using a copper tubing/pipe flaring tool like the one shown below.

Watch out: remember to slide the flare nut fitting over the tubing before you make the flare - else you won't be able to get the fitting on, you'll need to cut off the flared-end and start-over.

Copper flare tool for use with copper tubing or pipe. cited & discussed at InspectApedia.com

The tubing is pinched in the die and you screw down the flaring head to gradually flare out the tubing.

Inspect the result to be sure there are no nicks or cuts in the mating surface of the flare fittings.

The illustration below, showing the flare nut down on the tubing, the copper flare, and a male flare fitting in the top of the image is adapted from the Copper Development Association, Inc., cited below.

Flare joint being assembled, adapted from Cu Copper Development Association, Inc., cited & discussed at InspectApedia.com

Copper Flare Joint References

Below we continue with Dream Home's original text on making copper flare joints.

Tip: buy a hand-operated copper tubing flaring tool to make nicer flare joints and reserve the swaging or flaring tool shown here for making direct pipe to pipe soldered joints without flare fittings.

Figure 21: how to use a flaring or swaging tool to make the flare on a copper pipe.

Fig. 21. Make sure that the flaring tool is properly centered in the end of the pipe.

Next, the end of the tubing is burred and then flared out with a flaring tool.

See Fig. 20. This tool must correspond in size to the tube. Put a few drops of oil on the tool and then carefully center it over the end of the tube. Using a hammer, strike the flaring tool until the end of the tubing has been flared out to the outside diameter of the flaring tool. See Fig. 21.

Figure 22: comonent parts of a copper pipe flare fitting ready for assembling: shown is a coupling (C) InspectApedia.com 2019

Fig. 22. Component parts of a flared fitting for copper pipe.

Now the flared end of the tube is placed (See Fig. 22) over the fitting and the sleeve nut is run up and tightened with a wrench. See Fig. 23.

Figure 23: tightening up a flare joint (C) InspectApedia.com 2019

Fig. 23. Tightening up a flared joint with a monkey wrench or an adjustable wrench (such as a "crescent wrench").

Flared copper tubing and flare fittings are sometimes used on water supply but are most-widely used not on water supply systems but rather on lower-pressure piping systems for LP or natural gas piping and for heating oil piping systems.

See details about flared copper piping and flare fittings & flaring tools at FLARE FITTINGS

Flare fittings used on flexible copper piping and their leaks and defects are also discussed at GAS LEAK DETECTION, LP / NG and GAS PIPING CLEARANCES, CODES & DEFECTS.

Also see GAS PIPING, VALVES, CONTROLS - home

Avoid Galvanic Corrosion Leaks

The best practice is to use the same type of pipe throughout the fresh-water system. There is little to be gained by using half copper and brass and half galvanized steel.

In fact, connecting copper to steel will cause trouble - galvanic corrosion between dissimilar metals (copper and steel) will lead to leaks. Brass and copper, however, can be used together without harm.

See details at GALVANIC SCALE & METAL CORROSION

This entire chapter is also available as PLUMBING SYSTEM INSTALLATION [eBook], or as a PDF image at THE HOUSE PLUMBING SYSTEM [PDF] original page images.


...

Continue reading at at PIPE SIZE SELECTION - next section of this chapter, or go to book contents at BUILD YOUR DREAM HOME, or select a topic from the closely-related articles below, or see the complete ARTICLE INDEX.

Or see these sections of Chapter 13 - PLUMBING SYSTEM INSTALLATION

  1. PROPER PLUMBING WORK is IMPORTANT
  2. WATER SUPPLY SOURCES
  3. TYPES of PIPING MATERIALS
  4. COPPER PIPE INSTALLATION
  5. COPPER FLARE CONNECTIONS
  6. PIPE SIZE SELECTION
  7. CAST IRON PIPE INSTALLATION
  8. PLUMBING SYSTEM LAYOUT PLAN
  9. PLUMBING FIXTURE INSTALLATION BATH KITCHEN
  10. WATER HEATERS & TANKS
  11. PLUMBING SYSTEM PRESSURE TESTS
  12. SEPTIC TANK, DRAINFIELD INSTALLATION
  13. PLUMBING MATERIALS LIST for the basic house

Or see these

Recommended Articles

Suggested citation for this web page

COPPER FLARE CONNECTIONS at InspectApedia.com - online encyclopedia of building & environmental inspection, testing, diagnosis, repair, & problem prevention advice.

Or see this

INDEX to RELATED ARTICLES: ARTICLE INDEX to PLUMBING SYSTEMS

Or use the SEARCH BOX found below to Ask a Question or Search InspectApedia

Ask a Question or Search InspectApedia

Share this article:

Questions & answers or comments about how to identify the architectural style of buildings and building components

Search the InspectApedia website

Need to make a private comment? Email editor@inspectApedia.com. We welcome email with your website content critique, corrections, suggestions or questions. Email is monitored daily but our workload may prevent an immediate reply. For immediate results, we hope you'll first try asking your question using the search box just above.

Citations & References

In addition to any citations in the article above, a full list is available on request.



ADVERTISEMENT