Thermostat Wire Color Codes
This article describes several tricks of the trade used by professionals when installing room thermostats and wiring them up. It describes the standard wire color conventions for HVAC thermostats.
InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers, products, or services discussed at this website.
- Daniel Friedman, Publisher/Editor/Author - See WHO ARE WE?
ADVERTISEMENT
Thermostat Wiring Tips & Color Conventions for 24V Thermostats
Complete guide to thermostat wire color code convenions + 9 Wiring Tips for Room Thermostats: Helpful Pointers Regarding 24V Thermostat Wiring & Heat-Anticipators

For HVAC technicians and others who need to determine wire color code conventions & connections for both new and older heating and cooling equipment, heat pumps, split systems, etc., here we give themost-common conventions for identifying or connecting thermostat wires based on wire color and wiring terminal identification letter(s).

Watch out: The type of heating system installed determines what thermostat wires are necessary and how they must be connected. You will always want to follow the instructions from the manufacturer of your specific thermostat or heating or cooling equipment directly as often the wire color and connection points will vary from "standard" conventions.
Our complete thermostat wiring guide for various types of heating or cooling systems and thermostat brands and models is found
at THERMOSTAT WIRE CONNECTIONS.
Additional wiring details are
at THERMOSTAT WIRING DIAGRAMS if you prefer those.
Article Contents

Also see HVAC SYSTEM TYPES, and see for our complete guide to wiring different types of heating, cooling systems & various brands and types of room thermostats.
Basic Thermostat Terminal Wiring Color Codes
Basic Thermostat Wire Color Codes |
| Color |
Terminal |
Use |
Details |
| Green |
G |
Fan control |
Switches on AHU blower fan |
| Red |
R |
24VAC |
Power from the transformer |
| Black |
C |
24VAC |
may be other colors |
| Yellow |
Y |
Cooling |
A/C unit if present - to the compressor relay. |
| White |
W |
Heating |
Heater |
Notes to the table above
As shown these thermostat wire connections are for a heating only or heating and cooling system (not heat pumps) using a single 24VAC transformer for power.
- Y = A/C, may be routed from the thermostat to the air handler (blower unit for indoor air) and from there to the A./C compressor/condenser unit (outside)
Newer HVAC systems and thermostats may sport additonal terminals by convention used as follows:
- Rc = cooling - takes power to the cooling system; may be jumpered to R in single-transformer systems; Not jumpered if using a separate transformers for heating & cooling systems
- Rh = heating - takes power to the heating system; may be jumpered to R in single-transformer systems; Not jumpered if using a separate transformers for heating & cooling systems
- G = fan, possibly switched by the thermostat's FAN ON control if present
- C = common, brings 24VAC power to the thermostat to power various features
Contempory Thermostat WIring Color Codes - heat pumps
Traditional Thermostat Wire Color Codes |
| Color |
Terminal |
Use |
Details |
Black - or -
Blue |
C |
Common 24VAC |
"Neutral" side of transformer or L2 |
| Blue |
B |
Switched to Reversing Valve |
Heat pump reversing valve energized to Heating Mode
when TT switched from cooling to heating |
| Red |
R or V |
Switched 24VAC |
"Hot" side of transformer or L1 |
| Red |
Rh or 4 |
Switched 24VAC to Heat |
Turn on heater |
| Red |
Rc |
Switched 24VAC to Cooling |
Turn on cooling |
| Green |
G |
Switched to Fan |
Connects to fan relay to run fan in indoor air handler.
From Thermostat FAN ON or MAN switch |
| Orange 1 |
O |
Switched to Reversing Valve |
Heat pump reversing valve energized to Cooling Mode
when TT switched from heating to cooling |
| Yellow |
Y |
Switched to Cooling |
Primary cooling system or heat pump stage 1 cooling
Connects to R or Rc on call for cooling |
| Dark Blue 1 |
B 1 |
Switched to Reversing Valve |
Heat pump reversing valve energized when TT switched between Heating & Cooling Rheem / Ruud |
| Light Blue 2 |
Y2 |
Switched to Cooling |
Connects to heat pump stage 2 cooling |
| White |
W |
Switched to Heating |
Connects to primary heating unit
In the TT this connects to R or Rh on call for heat
On heat pump may jumper to Y
May connect to heat pump stage 2 heat |
| Brown 3 |
W2 |
Switched to Heating |
Connects to second stage heat for dual-stage heaters |
Brown ?
Various |
E |
Emergency Heat |
Force backup heat on if heat pump fails |
| Various |
S1 S2 Sens |
Outdoor Sensor |
Controls heat optimizers |
| Various |
Aux or X |
Switched to Backup Heat |
Connects to backup heat control relay in indoor air handler - when low outdoor temp prevents heat pump heating mode |
| Various |
Aux or A |
Auxiliary use |
Activates any relay for various purposes |
| Various |
P |
Defrost control |
lights indicator bulb |
| Various |
X |
Malfunction indicator |
lights indicator bulb |
Notes to the table above
This table shows the most-common thermostat wire connections on modern combination heating and cooling and heat pump systems.
- O wire for reversing valves in Amana, Carrier, Ducane, Goodman, Heil, Janitrol Lennox heat pumps, may vary for othe rmanufacturers
Dark Blue wire for reversing valves on Rheem & Ruud heat pumps
Also referred to as "changeover to cooling" relay
- Y2 wire for stage 2 cooling may be colors than light blue
- W2 wire for stage 2 heating may be other colors than brown
Traditional Thermosat Wiring Color Codes
Traditional Thermostat Wire Color Codes |
| Color |
Terminal |
Use |
Details |
| Black / Blue |
C |
Common 24VAC |
"Neutral" side of transformer or L2 |
| Red |
R or V |
Switched 24VAC |
"Hot" side of transformer or L1 |
| Red |
Rh or 4 |
Switched 24VAC to Heat |
Turn on heater |
| Red |
Rc |
Switched 24VAC to Cooling |
Turn on cooling |
| Green |
G |
Switched to Fan |
From Thermostat FAN ON or MAN switch |
| Yellow |
Y |
Switched to Cooling |
Connects to R or Rc on call for cooling
May connect to heat pump stage 1 heat |
| White |
W |
Switched to Heating |
Connects to R or Rh on call for heat
On heat pump may jumper to Y
May connect to heat pump stage 2 heat |
Notes to the table above
This table shows typical thermostat color codes and connections for a traditional heating and cooling system including some heat pumps and backup-heat systems.
Tips for Successfully Wiring a Room Thermostat for Heating or Cooling
- The string in a typical recently manufactured multiple element thermostat wire is there to help an installer more easily strip off the main outer jacket without harming or nicking the individual inner wire jackets.
Once an installer has used a knife or wire stripper to expose enough of this string to be able to grab onto it with his fingers, he can then pull the string at right angles to the thermostat wire, then slicing easily a little further through the main outer jacket without having to risk any further harm to the new just freshly exposed jackets of the smaller inner wires.
An installer can then simply prune away any of the smaller wires which he may have had to nick before he was able to grab onto the string and to use it to safely strip off the outer jacket.
- It's always best to wrap a spare or unused wire around the main thermostat wire outer jacket where the outer wire jacket just starts, so that such wires, if needed, could still be used at a later time or date. C
utting such wires back instead of merely wrapping them back out of the way, may be regretted later on in the job in hindsight. We don't leave bare wire ends because we don't want to risk accidentally shorting out something inside the thermostat or other control device.
- Heat-anticipators are typically chiefly found in mechanical (non-digital) thermostats, though some new digital / programmable room thermostats like the 3M-22, discussed
at THERMOSTAT SWITCHES, INTERNAL, provide a nearly identical function referred to as an adjustable thermostat swing-rate (cycle rate or thermostat sensitivity).
Whenever installing or servicing a thermostat with a heat-anticipator, the amperage setting on the heat-anticipator should always be verified as matching the amperage draw on the gas valve or relay that it controls.
See HEAT ANTICIPATOR Adjustment
and HEAT ANTICIPATOR SET & TEST by AMMETER
Not all heating systems and buildings benefit from a heat exchanger but in some cases you want a thermostat with this feature.
See DO I NEED A THERMOSTAT WITH A HEAT ANTICIPATOR? for details.
In any event, if a heat anticipator is included in a thermostat it should be set properly. Otherwise the relay or thermostat may not function properly, resulting in too-short burner on-time (higher heating costs) or room temperature overshoot (wasted heating dollars).
Note: your fuse marked with an "E" was probably being read upside down and was a 3-amp fuse. Using a fuse one amp greater incapacity is probably not too dangerous, but it's best not to overfuse as doing so risks equipment damage. Certainly a larger fuse is asking for wiring or device burn-up should a future short circuit occur. - Ed. & reader comments
Since shorting thermostat wires can damage a circuit but can also blow the low voltage transformer, also
see LOW VOLTAGE TRANSFORMER TEST
Reader Question: possible shorted thermostat wires
Our furnace thermostat failed after an adjacent water heater installation. I noticed that wires were pinched between the water heater and the gas pipe. After I loosened the safety straps and freed the wire, the thermostat works. (I reset the furnace). Were squished wires the cause of a temporary short and will the wires keep working if they are undisturbed? - Larry 8/2/11
Reply: check for shorted wires and for thermostat transformer damage as well as for blown fuse
Yes it's surely possible that your thermostat wires were shorted.
Now a short in those wires sometimes lets you off the hook with no trouble, since the wires and thermostat are basically an "on-off" switch that calls for heat (or no heat).
But a thermostat wire short at the transformer could burn out the low voltage transformer that powers the thermostat and heating controls or maybe even damage the thermostat itself.
Find and check the low voltage transformer (often it's mounted near your furnace, on an electrical junction box, or it may be integral in your heater control unit).
See LOW VOLTAGE TRANSFORMER TEST
Question: reader comments on shorting out thermostat wires & fusing requirements
Greetings, not sure if anyone saw this or not, but whoever S.R. is above in the description about shorting out wires seems to maybe have missed the fact that the "E" they refer to is actually a "3" amp fuse and not a 4 amp fuse.
My HVAC installer of 30 years who recently installed 2 furnaces for us and is installing my heat pump agrees that it is a 3 amp fuse. We purchased an extra one just in case. Putting a 4 amp in there may not be good for the board as it may allow too much current for a relay or something and you may fry a piece on the board which is most likely not cheap. I hope this helps - D.M. - 3/12/12
Reply:
Thanks D.M., We posted your important fuse size comment right in the article
at SHORTING OUT THERMOSTAT WIRES - Leads to Loss of Heat.
...
ADVERTISEMENT
Reader Comments, Questions & Answers About The Article Above
Below you will find questions and answers previously posted on this page at its page bottom reader comment box.
What type & brand of thermostat do I buy for "heat only" ?
I see red/white/blue&white.
I need to find a thermostat to operate steam heat only.
No AC or Fan while using these wires.
Wiring from 60s, radiator is cast iron, new boiler.
The Braeburn Megaswitch was installed to replace old round Honeywell. Now no longer sets, ( coil retracts back to center and heat is coming from all radiators)
I purchased new non programmable heat only round Honeywell w/o anticipator but has on/off switch in back
Did not work
The wires - what type of brand thermostat can I use.
by (mod) - Braeburn 505 "Heat only" thermostat
Victoria
A Braeburn 505 "Heat only" thermostat will work fine for you and is very inexpensive.
...
Continue reading at THERMOSTAT INSTALLATION STEPS or select a topic from the closely-related articles below, or see the complete ARTICLE INDEX.
Or see THERMOSTAT WIRING TIPS & COLOR CODES FAQs - questions & answers about TT wiring posted originally at the end of this page.
Or see these
Recommended Articles
- THERMOSTAT INSTALLATION STEPS
- THERMOSTAT WIRE CONNECTIONS
- COMMON WIRE at THERMOSTATS
- CONVERT LINE to LOW VOLTAGE THERMOSTAT
- LINE VOLTAGE THERMOSTATS
- THERMOSTAT WIRE CONNECTIONS - 2-WIRE like the T87F
- THERMOSTAT WIRE CONNECTIONS - 3-WIRE Red, White, Blue Wires
- THERMOSTAT WIRE CONNECTIONS - 4-WIRE Red, Yellow, Green, White
- THERMOSTAT WIRE CONNECTIONS - 5-WIRE Blue/Black, Red, White, Yellow, Green
- THERMOSTAT WIRE CONNECTIONS - 6-WIRE Red, White, Blue, Yellow, Green, Orange Wires
- THERMOSTAT WIRE CONNECTIONS - 8-WIRE Black, Red, White, Yellow, Green, Orange, Brown, Blue
- THERMOSTAT WIRE SORTING to ID R W
- THERMOSTAT WIRING AZEL i-LINK
- THERMOSTAT WIRING 3M-22 FILTRETE
- THERMOSTAT WIRING AMERICAN STANDARD
- THERMOSTAT WIRING ARGO
- THERMOSTAT WIRING CHROMOLOX
- THERMOSTAT WIRING ELECTRIC HEAT
- THERMOSTAT WIRING EMERSON
- THERMOSTAT WIRING FLAIR INSTRUCTIONS
- THERMOSTAT WIRING GENERIC Control Points
- THERMOSTAT WIRING GOODMAN
- THERMOSTAT WIRING & MANUALS, HONEYWELL
- THERMOSTAT WIRING LINE VOLTAGE 120-208-240VAC
- THERMOSTAT WIRING NEST
- THERMOSTAT WIRING TRANE HVAC
- THERMOSTAT WIRING WHITE RODGERS
- THERMOSTAT WIRE TERMINAL ID CODES / FUNCTIONS
- THERMOSTAT WIRING OPENING SEAL
- THERMOSTAT WIRING COLOR CODES
Suggested citation for this web page
THERMOSTAT WIRING COLOR CODES at InspectApedia.com - online encyclopedia of building & environmental inspection, testing, diagnosis, repair, & problem prevention advice.
Or see this
Or use the SEARCH BOX found below to Ask a Question or Search InspectApedia
Ask a Question or Search InspectApedia
Share this article:
Search the InspectApedia website
Need to make a private comment? Email editor@inspectApedia.com. We welcome email with your website content critique, corrections, suggestions or questions. Email is monitored daily but our workload may prevent an immediate reply. For immediate results, we hope you'll first try asking your question using the search box just above.
Citations & Reviewers
In addition to any citations in the article above, a full list is available on request.
- [1] ...
- [2] Thanks to reader S.R. for discussing loss of heat due to a thermostat wiring mistake, October 2010
- [3] Thank to Mr. Scott Meenen , G&S Mechanical Services , for providing some common thermostat wiring codes also found at Mr. Meenen's web page Malware Deleted 12/9/2014 . Mr. Meenan provides heating, heat pump, and air conditioning repair services in Maryland, Washington D.C., and northern Virginia. He can be contacted at 301-591-1646 or by Email to Malware Deleted 12/9/2014 - 10/2010.
- [4] Azel Technologies Inc., P.O. Box 53138
10 Royal Orchard Blvd.
Thornhill, Ontario, Canada L3T 7R9
Ph: 905-223-5567 Fax: 905-223-3778
Email: info@azeltec.com, Website: www.azeltec.com.
- [5] Honeywell Controls, the company wants you to use their contact form at this web page: http://www51.honeywell.com/honeywell/contact-support/contact-us.html
Honeywell Consumer Products,
39 Old Ridgebury Road Danbury, CT 06810-5110 - (203) 830-7800
World Headquarters, Honeywell International Inc.,
101 Columbia Road,
Morristown, NJ 07962,
Phone: (973) 455-2000,
Fax: (973) 455-4807 1-800-328-5111
- Honeywell product model numbers & instruction Manuals: see http://yourhome.honeywell.com/home/Applications/FindYourModelNumber.aspx
- [6] White Rodgers Thermostats and HVAC controls,
Homeowner information: http://www.emersonclimate.com/en-US/brands/white_rodgers/Pages/wr-homeowner-info.aspx
Contractor information: http://www.emersonclimate.com/en-US/brands/white_rodgers/wr_contractor_info/Pages/white-rodgers-contractor-info.aspx
White Rodgers Product Catalog (don't misspell the company's name as White Rogers Thermostats) -
http://www.emersonclimate.com/Documents/thermostats.pdf - Thermostat Catalog
- [7] White Rodgers 1F90 Low Voltage Digital Comfort-Set thermostat Installation Instructions, PN 37-3654, White-Rodgers Division, Emerson Electric Co., 9797 Reavis Rd., St. Louis MO 63123
- [8] "Automatic Oil Burner Controls - Thermostats", Domestic and Commercial Oil Burners, 3rd Ed., Charles H. Burkhardt, McGraw Hill, 1969 (and later editions), ASIN B0000EG4Y8
- [9] Thermostat wiring color codes & conventions,
Thanks to reader "
Helpful Pointers" Regarding 24V T, 10/7/2012
- [10] Domestic Central Heating Wiring Systems and Controls, 2d Ed., Raymond Ward, Newnes, ISBN-10: 0750664363, ISBN-13: 978-0750664363, Quoting from Amazon.com:
- [11] Proliphix Corporate Headquarters [Website: proliphix.com] , 3 LAN Drive Suite #100, Westford, MA 01886 Phone: +1.978.692.3375 Toll Free (U.S.): 866-IP-LIVING (866.475.4846) Fax: +1.978.692.3378 - Sales: sales@proliphix.com Marketing: marketing@proliphix.com Customer support: support@proliphix.com http://www.proliphix.com/ - quoting from the company's website:
- [12] "Heating Control Handbook for the Installer and Service Man,Oil Burner, Gas Burner and Stoker Controls", Honeywell Corporation, March 1949 [copy on file as HoneywellControlsHandbookSA1399-2-1949.pdf] . Some of the controls discussed in detail here include the
- Honeywell T1 and T11A = Series 10
- Honeywell T21A (T2) = Series 20
- Honeywell T847A = Series 80
- Honeywell RA117A (RA1) = Series 10
- Honeywell LA101A = Series 10,
- Honeywell LA419A (LA4) = Series 40
- V155A = Series 10, V435A = Series 40, V575A = Series 50, V835A = Series 80
- [13] Trane TCONT800 Series Touch Screen Programmable Comfort Control Ownes Guide, American Standard, Inc., Troup Highway, Tyler TX 75711, January 2005, Telephone: Customer Service: 1-877-3381, website: www.trane.com
- In addition to citations & references found in this article, see the research citations given at the end of the related articles found at our suggested