InspectAPedia®   -   Search InspectApedia

 a heating boiler expansion tankExpansion Tank / Compression Tank Diagnosis

Troubleshoot the expansion tank on hot water heating systems

  • POST a QUESTION or COMMENT about heating system expansion tanks: their function, size, location, maintenance, and need for draining (on some models)

Hot water heating system expansion tank / compression tank troubleshooting guide:We provide a heating system expansion tank Troubleshooting & Repair Guide.

This article series provides a heating system expansion tank (compression tank) troubleshooting & repair guide.

InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers, products, or services discussed at this website.

- Daniel Friedman, Publisher/Editor/Author - See WHO ARE WE?

Signs of Trouble with a Heating Boiler Expansion Tank

 a heating boiler expansion tankExpansion tanks on hot water heating systems can be divided roughly into two groups:

  1. Older type bladderless heating system expansion tanks (atmospheric expansion tanks) and
  2. Newer type internal bladder-type expansion tanks such as those sold by Amtrol Inc.

The behavior, maintenance, and sources of leaks or trouble are not identical with these two different types of compression / expansion tanks on boilers.

A modern internal bladder type expansion tank like this Amtrol Extrol tank (photo at left) is generally trouble free, and it's unusual for these tanks to fail. The Ex-Trol® is properly referred to as a pressurized diaphragm-type expansion tank.

[Click to enlarge any image]

Both older non-bladder type expansion tanks and even modern (and much smaller) internal bladder expansion tanks can get in trouble.

But on occasion the internal bladder in one of these tanks could rupture or develop a leak. If that happens, because the tank is not field-repairable, the "fix" is to install a new expansion tank.

But far more often, it is older non-bladder type expansion tanks on boilers, like the one below) that become waterlogged.

What Happens if an Expansion Tank Becomes Waterlogged?

When the expansion tank is no longer able to absorb this initial pressure increase, it is possible that the heating system's internal pressure would exceed 30 psi - the typical point at which a heating boiler pressure/temperature relief valve will open to spill excess pressure.

If the relief valve is forced open in this manner the heating system will first lose water each time a heating cycle starts by heating up the boiler.

Then the heating system will take in makeup water (through the automatic water feed valve) each time the system cools down.

The result would be recurrent loss and then inflow of water through the boiler, increasing the risk of system corrosion as well as wasting water and possibly causing other damage or operating problems.

Watch out: spillage at the pressure temperature relief valve is potentially dangerous: eventually minerals in the water can clog a leaky relief valve, causing it to stop leaking - which might look ok but this means that the relief valve has become clogged - the boiler is operating without this critical safety device and an explosion could occur.

Atmospheric expansion tank on hydronic boiler (C) Daniel Friedman Two Harbors MN

Shown above, an older style ceiling mounted atmospheric expansion tank on a hydronic heating boiler in Two Harbors, MN.

The drain valve shown at the left end of this expansion tank is a special valve that makes it easier for replacement air to enter the tank when the tank's water is being drained - a standard procedure during annual heating boiler maintenance. We describe that procedure separeately

at EXPANSION TANK DRAIN & AIR RE-CHARGE .

[Click to enlarge any image]

Trouble signs that could be traced to a water-logged boiler expansion tank include:

Also see HOT WATER PRESSURE EXPANSION RATE

How to Diagnose an Internal Bladder-Type Boiler Expansion Tank Needs an Increased Air Charge or Needs Replacement

Newer type heating system expansion tanks that use an internal bladder keep their water and air separated. These tanks should not need frequent service but might need a small additional air charge every few years, as we explained

at WATERLOGGED EXPANSION TANK.

But there are at least three possible conditions for which to check an internal bladder type expansion tank for trouble.

  1. Internal bladder type expansion tank air permeation loss:

    If the expansion tank has not been functioning properly but on removal you don't find that there is water trapped inside the tank bladder (as described above), check the tank's air pressure.

    If the air pressure is below the factory-set pressure, or below the pressure that you previously set when the tank was installed, the tank may have lost its air charge over a period of several years.

    This tank may be perfectly serviceable if re-charged to proper setting. That's why we put this possibility first in the list.
  2. Rapid air charge loss at the internal bladder expansion tank:

    When a bladder-type expansion tank has become waterlogged over a short interval it's most likely because the bladder has ruptured and the tank needs replacement.

    If the bladder has burst you will probably find that a little depression of the pin in the tank's air valve will send water squirting out of the valve - a sure sign that the tank bladder is burst and the tank needs replacement.
  3. Pinhole leak failures in an internal bladder expansion tank:

    But what if no water comes out of the tank. There may still be a pinhole leak of water into the air space that has begun to consume air space in the tank.

    If the tank has been removed and drained through its point of connection to the heating system, and you then shake it or feel that it has gained weight over a new empty tank of the same size and model, and if you (possilbly) hear water or feel water sloshing around inside the tank bladder, then the pressure tank had a pinhole leak, water is in the bladder, and the tank needs replacement.

Additional Diagnostic Tests for a Waterlogged Heating Boiler Expansion Tank

Airtrol expansion tank compression tank Bell & Gossett (adapted by InspectApedia)

The following tips are from Bell & Gossett's installation manual for pressure reducing valves and from their Airtrol Compression Tank [expansion tank] System Installation Manual [4][5].

Our illustration at left shows the typical location of a traditional conventional, non-bladder-type heating boiler expansion tank, and is adapted from that B&G manual.

[Click to enlarge any image]

...




ADVERTISEMENT





Reader Comments, Questions & Answers About The Article Above

Below you will find questions and answers previously posted on this page at its page bottom reader comment box.

Reader Q&A - also see RECOMMENDED ARTICLES & FAQs

After I drained the expansion tank water drips out of the boiler relief valve!

Shut off supply valve to expansion tank. Opened drain valve and air valve on tank. Drained tank. Closed both valves.

Opened supply valve to tank. .Water pressure in system dropped so added water until gauge read 20 Lbs of pressure.

Bled air from system. Pressure dropped from releasing air pressure.

Added more water until pressure read 20 Lbs. Turned on heat.

After heating awhile pressure read about 25-26 Lbs of pressure and water was dripping out of relief valve

Relief valve is a 30LB relief valve.

What have I done wrong. Should I have first bled air out of system then added water to bring pressure to 20Lbs then filled tank then bring pressure back up. I am concerned about the relief valve dripping On 2019-10-03 by Lee

Reply by (mod) -

It's possible that your heating system was at an overpressure because of a waterlogged expansion tank in the first place.

On a typical residential hot water heating system the system pressure in the boiler should be around 12 PSI when the system is cold. Take a look at the heating system pressures articles in the article index.

You shouldn't be needing to bleed air when you drain the expansion tank. If you have an air problem in your system it's a separate issue.

 

Why does my building water pressure keep changing: is it a bad expansion tank?

My water pressure keeps changing. Is this the expansion tank? On 2019-06-16 by Linda l

Reply by mod

Linda

The water pressure tank (it's not an expansion tank) smooths the pressure or delivery of water into the building and prevents short-cycling or rapid on-off pump operation.

If the water pressure tank becomes water-logged, that is if it loses its air charge, then the pump may cycle on and off very frequently, even every few seconds.

That would show up as "constantly and rapidly changing water pressure".

We explain that problem and explain how to fix it (add air to your expansion tank)

at WATER PUMP SHORT CYCLING - home

You posted this question on our page about heating boiler expansion tanks.

To understand your building water pressure and the role of your home domestic water supply expansion tank

please see WATER TANK: USES, TROUBLESHOOTING 

Someone stole part of my heating system piping, now my boiler shows zero pressure and I have no heat.

By "emergency relief valve " i mean the valve on the side of the boiler itself that is the same look as the one on my electric water heater

I have a baseboard boiler system using natural gas. this summer copper thieves hit and i had to replace a number of lines. now when the system runs the downstairs heat zone will not warm up, i have bleed the lower section twice ( second time i just opened the pipe joint and let it run till clean water)

now all of a sudden the system has no, ZERO, pressure while running and the whole upstairs zone will not bleed. i removed the whole bleeder valve on 5 sections and no water or air comes out. pump is pumping water, boiler is up to temp just no pressure. also the expansion tank is heavy and sounds full of water.

i have had no leaks from the "emergency relief valve" and the system is hooked straight to city water with no pressure reducer. didnt know it was supposed to be there, copper thieves must have taken it. please help, too close to Christmas to have no heat! On 2015-12-21 by brian

Reply by (mod) -

InspectAPedia.com has detailed diag nosis and repair advice for you

at AIR-BOUND HEATING SYSTEMS - home

but as heating controls may be missing I'd suggest a heating co. Service call too. Let us know how you made out.

Or start with some basic diagnostic and repair steps that you can take, found

at NO HEAT - BOILER

...

Continue reading at EXPANSION TANK LEAK REPAIR FAQs or select a topic from the closely-related articles below, or see the complete ARTICLE INDEX.

Or see these

Recommended Articles

Suggested citation for this web page

EXPANSION TANK DIAGNOSIS at InspectApedia.com - online encyclopedia of building & environmental inspection, testing, diagnosis, repair, & problem prevention advice.


Or see this

INDEX to RELATED ARTICLES: ARTICLE INDEX to HEATING BOILERS

Or use the SEARCH BOX found below to Ask a Question or Search InspectApedia

Ask a Question or Search InspectApedia

Try the search box just below, or if you prefer, post a question or comment in the Comments box below and we will respond promptly.

Search the InspectApedia website

Note: appearance of your Comment below may be delayed: if your comment contains an image, photograph, web link, or text that looks to the software as if it might be a web link, your posting will appear after it has been approved by a moderator. Apologies for the delay.

Only one image can be added per comment but you can post as many comments, and therefore images, as you like.
You will not receive a notification
when a response to your question has been posted.
Please bookmark this page to make it easy for you to check back for our response.


Comment Form is loading comments...

IF above you see "Comment Form is loading comments..." then COMMENT BOX - countable.ca / bawkbox.com IS NOT WORKING.

In any case you are welcome to send an email directly to us at InspectApedia.com at editor@inspectApedia.com

We'll reply to you directly. Please help us help you by noting, in your email, the URL of the InspectApedia page where you wanted to comment.

Citations & References

In addition to any citations in the article above, a full list is available on request.



ADVERTISEMENT