Building Inspection, Diagnosis & Repair Info

 a heating boiler expansion tankBoiler Drain Procedure Damages Expansion Tank Bladder

  • POST a QUESTION or COMMENT about heating system expansion tanks: their function, size, location, maintenance, and need for draining (on some models)

While we don't usually need to flush out or drain a hot water (hydronic) heating boiler, on occasion its necessary to remove sediment or sludge from the boiler, often as a preparatory step to adding a boiler chemical treatment or antifreeze.

Here we describe cases in which the hot water heating system expansion tank was damaged by a boiler drain procedure.

This article reports damage to the internal bladder of a heating boiler expansion or compression tank. Damage was caused by use of a pony pump to speed the draining of a hot water heating boiler during service. The article includes steps in determining what went wrong and why.

The article concludes with a warning that using pumps on heating systems to speed the service drainage process may be risky.

In this article series we provide a heating system expansion tank / compression tank Troubleshooting & Repair Guide that will address just about any problem traced to this heating system component.

InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers, products, or services discussed at this website.

- Daniel Friedman, Publisher/Editor/Author - See WHO ARE WE?





ADVERTISEMENT





Boiler Drain-Down Service Procedure Using a Pump Damages Expansion Tank Internal Bladders

 a heating boiler cad cell relay switchTwo InspectApedia readers discuss with the moderator (DF) the causes of and fixed for expansion tank damage during improper boiler draining procedures.

Photo: an automatic pressure-reducer water feed valve on a hot water heating boiler.

Why wouldn't water go back into my boiler until I bypassed my water feeder/pressure reducer? Why did water keep going into my boiler after I turned off the water feeder bypass?

Great site. I have a question on a building of a larger size, the expansion tank is 180 gallons and is of a bladderless type, now the boiler was operating with under 5 psi.

After it cooled I went around looking where the feed for cold water goes to the system which led me to the Watts SB1156F..

It has the fast fill lever on it, so I opened it and noticed the pressure gauge on the boiler started to rise.

I also noticed the water level in the expansion tank rose but when I returned the lever back to it's normal position I noticed water was still flowing but at a much lesser amount on the water meter.

I have two questions about the incoming water, why did the boiler not get any pressure until I bypassed the regulator setting, and why was the flow still trickling in after I reset it back to it's normal position?

Now the expansion tank it's full of water and I'm trying to figure out how to drain it, the terms they used back in the 60's are a little different but they at least tagged each valve with a brass letter and number, one of them in question is called expansion tank guard..

it comes from the circulation pumps and it leads to the bottom of the tank, another valve is the supply to the boiler just after the watts regulator.

Should I turn off the one that's called expansion tank guard and the supply for the boiler while I drain? 11/3/2014 Mike

Reply: when draining the expansion tank you may need to bypass the water feeder to re-pressurise the boiler

Mike I've been thinking about your question and am not sure I can diagnose the issue accurately from just your e-text.

If water pressure in the boiler drops, typically there's a leak to be found and fixed.

The pressure regulator may also be improperly set or in failure if it's not keeping the boiler pressure at normal cold levels.

It could also be the case that when you lifted the bypass lever on your boiler's water feeder/pressure reducer valve, the valve didn't properly or fully re-seat when you returned it to its normal position.

If that were the case, you'd see water pressure continue to creep up - check your boiler's pressure/temperature gauge. You may need to replace the water feeder valve.

Details about hydronic water pressure-reducer / feeder valves are

at WATER FEEDER VALVE, HYDRONIC BOILER

where I also show cleaning the strainer and fixing other problems with that water feeder valve.

Reader follow-up:

Well Dan I fully drained the tank and I came back the next day and after getting the system back up everything was ok, it's a bit hard to describe over text I still don't know why the boiler before was not adding water to it and it was operating at 0 PSI.

Odd that the boiler did show pressure after I opened the fast fill (after boiler cooled) now it's fine.

I had no clue when the tank was last drained but the last date (and only date) someone wrote was it was drained back in 1988, and I don't think a tank can go 26 years without another draining?

I had no other option but to use the hose on the tank, I did have to blow into the hose and the tank would drain for about 5 min, then I would crack open the hose and air would rush in, as the tank was getting lighter the rushing air into the tank was enough to have it moving a bit. 11/5/14 Mike

 

Our boiler expansion tank bladder ruptured after the technician replaced a pressure relief valve

I just had a certified tech replace the relief valve for my boiler water. I have the Extrol (modern) tank with a bladder.

I had no problems with the relief valve that I could see, but it was 10 years old and the tech suggested replacement. After he replaced it, I had significant water and it was because the bladder was now ruptured.

The company of the tech stated that it is "common" for the Extrol bladder to rupture after replacing the relief valve - is that true?

I don't know if this was an unlucky series of events or if the tech made a mistake. They didn't charge me labor, but did charge about $170 for a new bladder. 11/6/14 Matt

Reply: sounds like a mistake

Matt

Your plumbing tech may certainly know stuff we don't, but I don't see the connection between installing a new TP valve and a ruptured pressure tank or expansion tank internal bladder. I've looked and not seen that warning among Amtrol's installation guides.

I'm also confused about why touching (to replace it) a relief valve would come anywhere near the expansion tank or its bladder.

But if your tech says that they frequently rupture the expansion tank when replacing a pressure relief valve, I have to comment

Well yeah: the tech often has that problem, perhaps because he's often making the same mistake, over and over again.

I don't know what a tech might do that would damage an expansion tank unless during system re-pressurization someone inadvertently submitted the equipment to unusually high pressures or jammed a screwdriver somewhere into an expansion tank.

Why not ask the company's service manager to help you out with an explanation of what happened and why.

Reader Follow-Up:

Matt

Thanks Daniel, and I agree. I probably should have added more info (I was in a bit of a hurry the first time).

In addition to the boiler water relief valve, I had the combo backflow preventer and air vent also replaced, so a little more work that did get near the Amtrol tank.

I don't know anything about how to service a boiler, but I'm guessing that he had to vaccuum some water and potentially perform other things that, if he over-pressurized the Amtrol® tank in starting back up, could have caused it to rupture, but I'm not sure.

Before I called back the service company, I was interested in your thoughts.

I didn't think that answer made any sense either, so I'm glad to hear that.

Now that you have the full story, any additional info would be helpful. Thanks again.

Reply:

How to use a pony pump to force-drain a heating boiler expansion tank (C) InspectApedia.com Daniel Kevin AngelaMatt,

Sometimes when a hydronic system is drained for repairs it is re-filled under pressure, even using a pony pump, as part of the procedure to purge air from the lines. Still I'd be surprised if pressures during those tasks would burst the tank bladder.

My photo shows how I use a pony pump to speed the draining of an old bladderless expansion tank but with caution and taking care not to pull a strong vacuum on the tank lest I damage it.

Vacuuming? Really?

Watch out: Indeed if the water pressure in the system were dropped rapidly and significantly, that might cause an internal pressure tank bladder to burst, tear, rupture.

I've even seen an all steel, bladderless expansion tank become damaged and concave and leak after the technician used a pony pump to try to "suck" water out of the expansion tank more rapidly than it would otherwise have drained.

Watch out: For that reason, if I use a pony pump to speed the drain of a boiler or of an older expansion tank, I pump only briefly, then I remove the pony pump hose to let air enter the expansion tank or boiler.

If I'm draining the whole boiler system I might open the relief valve to let air into the boiler top that way -

Watch out: being prepared, of course, to replace the pressure relief valve if it doesn't close fully at the end of that procedure.

Details of that procedure are

at EXPANSION TANK DRAIN & AIR RE-CHARGE

I await with interest hearing what the service manager has to offer. I'd expect that if you come across as interested and not threatening s/he should be willing to offer a more cogent explanation.

Reader Follow-Up: case closed - service tech uses vacuum to speed the boiler drain-down job - blows the expansion tank bladder

Daniel,

Spoke to service manager. He said that these "fail all the time" during valve replacements and that they routinely put negative pressure on relief valve to remove excess water.

I explained that it was working prior and failed after his tech replaced the valves, likely due to over pressure / rapid change in pressure.

He wouldn't admit that, simply kept repeating that these fail all the time and it was old (10 years) and should have been replaced anyway. My guess is that they probably pay about $20-$40 for these tanks and charge $165 to replace them (excluding labor).

Nice racket for them. I did get about 50% of my money back, but needless to say, I'm switching service companies effective today.11/7/2104 Matt

Reply: if something "fails all the time" we might want to ask "Why?"

Matt

You have to love it, right. "They fail all the time" may indeed be absolutely true, because all the time the service procedure the company is using is one that destroys a component that was not intended for the negative pressure they apply.

If we consider that an expansion tank bladder and its contents may be sitting at 12 psi or higher and that someone applies a powerful vacuum to the system such that the bladder is exposed to a strong negative pressure it's no surprise that an internal bladder might burst, particularly if the exposure were rapid.

I once inspected a brand-new home in which new gutters had been installed and it was raining. Roof runoff was pouring behind the gutter and on my head as I rang the doorbell. The builder himself answered the door.

I tried to be tactful. "Do you think this looks right for all this water to be running behind your gutters?" I asked.

"Yeah" he replied "they all do that".

Well indeed all of HIS gutters did that because his gutter installer always installed the roof drip edge improperly (behind the gutter rather than extending out over it).

I doubt the service company is being deliberately dishonest. More likely they've got an idea to speed their service procedure and don't appreciate the effects of being in a rush.

Watch out: not only can you damage a bladder-type expansion tank on a boiler, it might be possible to also damage even an old-style bladderless expansion tank when using a pony pump to speed drainage.

See EXPANSION TANK WON'T DRAIN


...





ADVERTISEMENT





...

Continue reading at AMTROL's EXTROL®, the FILL-TROL® or select a topic from the closely-related articles below, or see the complete ARTICLE INDEX.

Or see these

Recommended Articles

Suggested citation for this web page

BOILER DRAIN DAMAGES EXPANSION TANK at InspectApedia.com - online encyclopedia of building & environmental inspection, testing, diagnosis, repair, & problem prevention advice.

Or see this

INDEX to RELATED ARTICLES: ARTICLE INDEX to HEATING BOILERS

Or use the SEARCH BOX found below to Ask a Question or Search InspectApedia

Ask a Question or Search InspectApedia

Share this article:

Search the InspectApedia website

Need to make a private comment? Email editor@inspectApedia.com. We welcome email with your website content critique, corrections, suggestions or questions. Email is monitored daily but our workload may prevent an immediate reply. For immediate results, we hope you'll first try asking your question using the search box just above.

Citations & Reviewers

In addition to any citations in the article above, a full list is available on request.

  • Holohan, Dan, "Why compression tanks waterlog", HeatingHelp.com (June 2014) - retrieved 19 March 2015, original source: https://heatinghelp.com/systems-help-center/why-compression-tanks-waterlog/
  • Etherton, Mark (contractor), "Expansion Tanks 101: the facts and myths", Contractor Magazine, contractormag.com, (March 2000), retrieved 19 March 2015, original source: http://contractormag.com/hydronics/cm_column_75
  • Extrol Corporation, "Installation & Operation Instructions, Extrol (R) Hydronic Diaphragm Expansion Tanks In-Line & SX-Series", Exrtrol Corporation, 1400 Division Road, West Warwick RI 02983, Tel: 401-884-6300, Website: www.amtrol.com, retrieved 3/3/2014, original source http://www.amtrol.com/media/documents/extrol/9015183_3_11_EXTROL_IO.pdf
  • Research on permeability of rubber used in internal bladder-type heating sytsem compression tanks or expansion tanks

    • Bodell, Bruce R. "Distillation of saline water using silicone rubber membrane." U.S. Patent 3,361,645, issued January 2, 1968.
    • Ciesielski, Andrew. An introduction to rubber technology. iSmithers Rapra Publishing, 1999.
    • Fuller, James, and David M. Stedham. "Expansion tank with a predictive sensor." U.S. Patent 8,633,825, issued January 21, 2014.
    • Martinello, Ermanno, and Mark Weih. "Membrane coating for a water pressurization Bladder." U.S. Patent Application 12/498,128, filed July 6, 2009.
    • Stern, S. A., F. J. Onorato, and Charles Libove. "The permeation of gases through hollow silicone rubber fibers: Effect of fiber elasticity on gas permeability." AIChE Journal 23, no. 4 (1977): 567-578.
    • Terashita, Fumihiro, Shingo Takagi, Shinzo Kohjiya, and Yasutoshi Naito. "Airtight butyl rubber under high pressures in the storage tank of CAES‐G/T system power plant." Journal of applied polymer science 95, no. 1 (2005): 173-177.
  • [5] Bell & Gossett Airtrol® System Installation, Operating and Service Instructions, Bell & Gossett, 8200 N. Austin Ave., Morton Grove IL 60053, USA - Tel 847 966-3700 Fax 847 965-8379. Retrieved 8/9/2012, original source B&G, [copy on file as Airtrol_Installation_Manual.pdf linked in this reference]
  • National Fuel Gas Code (Z223.1) $16.00 and National Fuel Gas Code Handbook (Z223.2) $47.00 American Gas Association (A.G.A.), 1515 Wilson Boulevard, Arlington, VA 22209 also available from National Fire Protection Association, Batterymarch Park, Quincy, MA 02269. Fundamentals of Gas Appliance Venting and Ventilation, 1985, American Gas Association Laboratories, Engineering Services Department. American Gas Association, 1515 Wilson Boulevard, Arlington, VA 22209. Catalog #XHO585. Reprinted 1989.
  • "Residential Hydronic (circulating hot water) Heating Systems", Instructional Technologies Institute, Inc., 145 "D" Grassy Plain St., Bethel, CT 06801 800/227-1663 [home inspection training material] 1987
  • Boilers, Boiler Conversions, James E. Brumbaugh, ISBN 0-672-23389-4 (v. 1) Volume II, Oil, Gas, and Coal Burners, Controls, Ducts, Piping, Valves, James E. Brumbaugh, ISBN 0-672-23390-7 (v. 2) Volume III, Radiant Heating, Water Heaters, Ventilation, Air Conditioning, Heat Pumps, Air Cleaners, James E. Brumbaugh, ISBN 0-672-23383-5 (v. 3) or ISBN 0-672-23380-0 (set) Special Sales Director, Macmillan Publishing Co., 866 Third Ave., New York, NY 10022. Macmillan Publishing Co., NY
  • Installation Guide #200 for Residential Hydronic Heating Systems, The Hydronics Institute, 35 Russo Place, Berkeley Heights, NJ 07922
  • Our recommended books about building & mechanical systems design, inspection, problem diagnosis, and repair, and about indoor environment and IAQ testing, diagnosis, and cleanup are at the InspectAPedia Bookstore. Also see our Book Reviews - InspectAPedia.
  • In addition to citations & references found in this article, see the research citations given at the end of the related articles found at our suggested

    CONTINUE READING or RECOMMENDED ARTICLES.


ADVERTISEMENT