Radiator Air Bleeder FAQs-2Q&A on using or fixing air bleeder valves & automatic air purging valves on hot water heating systems, set #2.
This article series explains how to diagnose and repair problems with air bleed valves and we describe methods used to remove un-wanted, air from noisy or air-bound hot water heating system pipes, radiators, convectors, and baseboards. We illustrate how to buy and add air bleeders at baseboard elbows using a baseboard tee and air bleeder valves.
Page top photo: the manually operable air vent built into this radiator valve (blue arrow) can be removed or restored using a small pipe wrench or similar tool. Such air vents are normally left in place and closed except when bleeding air.
InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers, products, or services discussed at this website.
- Daniel Friedman, Publisher/Editor/Author - See WHO ARE WE?
These questions & answers about heating system air bleeder valve installation, troubleshooting & repair were posted originally
at AIR BLEEDER VALVES - be sure to see the repair advice given there.
Also see this AIRBOUND HEAT REPAIR FAQs INDEX - to all questions & answers about fixing airbound hot water heating systems including air bleeder valves, air vents, and air removal methods.
...
Tip: See AIR BLEEDER VALVE USE PROCEDURE - how to use air bleeders on baseboard heaters or radiators
Should they be opened or closed when running normally? On 2020-02-23 by Anonymous
Anon
Thanks for asking a question about leaving hot water heating air bleeders open or closed.
The answer is, as Mark Cramer says, " ... it depends."
In my photo above we see a float type air bleeder vent labeled "AUTOMATIC AIR BLEEDER VENT" installed atop the air scoop over a hydronic heating boiler.
Normally the screw cap on float vents is left OPEN so that the vent can work to automatically remove air it collects.
If the air bleeder is a float type vent then the screw cap on the vent is kept loose about 1 1/2 turns so that the float vent can automagically vent air that it collects. (We might close that screw cap if the float vent begins leaking water continuously - to avoid a spill while we wait for the float vent to be replaced.)
The only time we close off the screw cap on float vents is if the vent is leaking water. In that case, screw down the vent cap to stop the leak and then ask your heating service tech to replace the vent with a new one.
If the air bleeder is a manual air bleeder that opens and closes by a screw or square "skate key" type wrench (shown in my photo below) then those vents are normally closed - else water would come out of the vent continuously.
Below: a screw type air bleeder valve on an elbow at a hot water heating baseboards. These manually-operated hot water heating system air vents are kept closed except when manually bleeding air from the system.
A square "skate key" tool is the proper tool to open or close this valve.
I have a bleeder valve on the top of a pipe between the joists in the ceiling of the basement (above the oil fired furnace/hot water heater). It is cracked open, like a permanent vent/bleed. Is this correct? Seems to me that they should remain closed. On 2015-10-20 by Bill
by mod - yes
Automatic or float-type air bleed valves are normally left open. That means that the little cap on that "valve stem" is left loose about 1 and 1/2 turns.
...
Tip: If there are NO air bleeder vents or valves that you can find on your hot water heating system, see NO AIR BLEEDERS or AIR VENTS FOUND on HEATING SYSTEM
Also see AIR BLEEDER COMPARED to RADIATOR ON-OFF VALVE to be sure you're not missing an air bleeder or vent
I have a baseboard boiler system in my house. Air needs to be bled out, but none of the old bleeder valves will turn.
All registers are still producing heat, but the air-lock bangs have turned into what sounds like water rushing through the lines when it calls for heat and the circulator kicks on.
I’ve noticed that that an automatic bleeder has been added to the sending pipe just before the first radiator (see pic).
My pressure is good (15), and temp as well (190).
If what’s in the pic is in fact an auto bleeder, which I’m assuming they added because of the faulty manual ones, can I safely release air from it without the system calling for water?
I ask this because it seems like something has to replace the air, and I don’t want to add any cold water to a hot boiler.
So, can I safely remove air from the system via the auto bleeder without worrying that cold water is going to replace the air? On 2020-02-05 by Paul D.
Reply by (mod) -
Paul that can with small "tire valve" cap atop in your photo is a the vent for a float type air bleeder at a strategic location on your boiler.
The cap should be loose (unless the valve is leaking water);It looks to me as if the float vent was replaced and that its predecessor leaked like mad for a long time.
OF course that bleeder as well as all of those you cannot open may need to be replaced.
When air is bled out of a hydronic heating system, IF makeup water is needed then the most common input is through an automatic water feeder/pressure reducing valve; on some boilers one may need to add water manually - when the boiler is cold, set pressure to the usual starting point of 12 psi for a residential boiler.Air bleeder vents or manual bleeder valves are commonl found at
I have heat on the first floor and heat on the second floor but the radiators are only hot in the master bedroom on the second floor - the in room bathroom radiator is cold as well as all the radiators in the upstairs bedrooms and hall bathroom.
I don't see any air bleed values anywhere upstairs. In the last few days I have to turn up the two electronic thermostats to 80 degrees to hear the furnace turn on. The pipes leaving the furnace are hot but the furnace runs for 2 to 3 minutes then stops - off for 5 minutes - then turns on for 2 to 3 minutes then off
- the radiator hot water pipes are hot on the first floor.
I keep the thermostat at 70 24/7 Mon-Fri. but last night the thermostat temp got down to 65 downstairs and upstairs until I bumped both up to 80 - then the furnace began to cycle off and on as noted above?
Any advice? Is some electronic device or sensor going bad? On 2020-02-22 by Milty
by (mod) - If hot water is not circulating through the heating zones the boiler will reach and shut off quickly at its HI LIMIT
Milty
If hot water is not circulating through the heating zones for any reason (air bound, closed valve, scale clogging, bad zone valve, circulator not running) then what happens is on a call for heat the boiler turns on but as cold water isn't returning from zones to the boiler, it quickly reaches its HI LIMIT and shuts off.
Though you haven't found air bleeder valves it's still possible to bleed air trapped in heating lines by other methods. Live links to these two articles may help you out
AIRBOUND HEAT SYSTEM REPAIR by PUMPAIRBOUND HEAT SYSTEM REPAIR by WATER FEED VALVE
Where can I find the air vent in my floor heating system in my flat? I think it is not working properly, the heating is distributed unevenly through the floor and I suspect that because of the air in the system. On 2016-12-18 by Sharif
by (mod) - where else to look for air bleeder valves or controls
Sharif:
Look at the start and end of each hot water piping run as well as at the start or end of baseboards or radiators; for older cast iron radiators look at the end-top of the radiators
I have an old warehouse-converted to house with a 4-zone hydronic heating system installed (converted?) in the 90's, long before we got the house.
The radiators upstairs are the classic, old, cast radiator style. These radiators have their supply and return lines, in addition to their bleeder valves, all mounted at the bottom ends of the units.
Two radiators (each in a separate zone - one is its own solo zone) suffer from the classic air lock situation with them staying cold at the top and warm at the bottom halves of the units. The other units work fine.
Opening the bleeder valves on these two bum ones does not let air out - of course, because they are mounted at the bottom, right?
- Am I to assume (for curiosity's sake) that these all bleeder-valve-bottom mounted units were meant for steam heat? -
And so then, how do I purge air from these two if the bleeders are at bottom? On 2017-11-08 by Phineas
Reply by (mod)
Phineas
We answered at AIR BLEED VALVE INSTALLATION - yes I suspect those were cleanouts or drains on steam radiators later converted to a hot water or hydronic heating system.Air bleeders won't be at the bottom of a hot water heating radiator - as air would be trapped at the radiator top. There are often tappings on radiators near the top that will permit installation of a manual air bleeder, or if the radiator valve is attached at the rad top such as in my photo (blue arrow) you'll find an air bleeder in a location that works.
...
Continue reading at AIR BLEEDER VALVE FUNCTIONS or select a topic from the closely-related articles below, or see the complete ARTICLE INDEX.
Or see these articles on
AIR BLEEDER VALVE DIAGNOSTIC FAQs-2 at InspectApedia.com - online encyclopedia of building & environmental inspection, testing, diagnosis, repair, & problem prevention advice.
Or see this
Or use the SEARCH BOX found below to Ask a Question or Search InspectApedia
Try the search box just below, or if you prefer, post a question or comment in the Comments box below and we will respond promptly.
Search the InspectApedia website
Note: appearance of your Comment below may be delayed: if your comment contains an image, photograph, web link, or text that looks to the software as if it might be a web link, your posting will appear after it has been approved by a moderator. Apologies for the delay.
Only one image can be added per comment but you can post as many comments, and therefore images, as you like.
You will not receive a notification when a response to your question has been posted.
Please bookmark this page to make it easy for you to check back for our response.
IF above you see "Comment Form is loading comments..." then COMMENT BOX - countable.ca / bawkbox.com IS NOT WORKING.
In any case you are welcome to send an email directly to us at InspectApedia.com at editor@inspectApedia.com
We'll reply to you directly. Please help us help you by noting, in your email, the URL of the InspectApedia page where you wanted to comment.
In addition to any citations in the article above, a full list is available on request.