Building Inspection, Diagnosis & Repair Info

Pony pump used to force water through a boiler (C) Daniel FriedmanGuide to Fixing an Air-Bound Hot Water Heating System

  • POST a QUESTION or COMMENT On how to get rid of air in an air-bound heating systems by using a pony pump and the boiler supply and drain piping

Air Bound Hot Water Heating System Repairs:

How to remove un-wanted, air from noisy or air-bound hot water heating system pipes, radiators, convectors, and baseboards using a portable pump and drain valves on the heating boiler.

Here we detail exactly how to hook up a transfer pump to force water through and air out of an airbound or air-logged hot water heating system. This pumping procedure is also used to add antifreeze to hot water heating boilers.

InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers, products, or services discussed at this website.

- Daniel Friedman, Publisher/Editor/Author - See WHO ARE WE?





ADVERTISEMENT





How to to Fix an Air-Bound Hot Water Heating System

If a hot water heating system develops too much air in the piping you may hear bubbling or gurgling in the heating pipes when the heating system is operating, or worse, so much air may be in the heating piping, radiators, or baseboards that heat may simply not circulate at all.

Airbound Heating System Relief Procedure #2 Using a Pony Pump

Pony pump used to force water through a boiler (C) Daniel Friedman

The following procedure is most useful when a heating system is already hot (we don't want to introduce cold water that might damage a hot boiler), or when a hydronic (hot water) heating system has been filled with antifreeze (we don't want to spill and waste the antifreeze filler).

Most newer heating systems using forced hot water include a service drain at the hot water riser pipe leaving the boiler or if the system is divided into multiple zones using individual zone valves, each heating zone should have a service drain installed, usually near the zone valve.

This procedure for repairing an air-bound hot water heating system is similar to method #1 above except that we connect our boiler drain to a 5-gallon bucket, and we use a pony pump with a short garden hose in the bucket to pump heating water from the boiler bottom service drain into a service drain on the hot water riser pipe or heating zone water pipe.

Forcing water in this manner uses a pump that can produce higher pressures than a heating system circulator pump - it pushes air through and out of the airbound heating system.

Note: this same procedure is used to add anti-freeze to hot water heating boilers & systems for freeze protection.

Details of that procedure are at ANTIFREEZE for BOILERS.

Step 1: Confirm that the heating system appears to be air-bound:

 heat is on and boiler temperature is up and the circulator pump is running; by touch the technician confirms that one or more sections of radiator, convector, or heating baseboard remain cold even though all radiator or convector or other circulating system valves are in the open position.

Step 2: Turn off the heating boiler,

using the service switch. If necessary,

see ELECTRICAL POWER SWITCH FOR HEAT.

Electric power switch for heat (C) Daniel Friedman

Thanks to reader Gene Friedman for pointing out that we ought to check to confirm that the system is air-bound before shutting the boiler off to begin the air purge process.

Also, as you'll note below at step 6, you may have to turn the boiler back on and set all thermostats to call for heat in order to open the heating system's zone valves and check valves if your system uses those devices.

Watch out: still we'd like to shut down and cool down the boiler before messing with buckets, hoses, and pumps, both to avoid a scalding hazard and to avoid running too-hot water through that cheap pony pump you bought.

So let's cool down the boiler even if later we have to turn it back on to complete the air purge procedure.

Step 3: Connect hose from pony pump output side to boiler hot water riser service drain:

Input feed to a heating boiler riser pipe (C) Daniel Friedman

Our photo shows a hose connected to the hot water riser pipe at the top of a heating boiler.

Connect the other end of this hose to the output side of a pony pump.

The pump will push high pressure water from the boiler bottom drain into the heating system distribution piping through this heat riser service drain, forcing water and air through the heat distribution piping and radiators and back down through the boiler and out at the boiler bottom.

(Some airbound heating system service procedures may reverse the direction of these flows.)

Step 4: connect a short hose from the pony pump input side to a 5-gallon bucket.

Pony pump used to force water through a boiler (C) Daniel Friedman

This photo shows the black hose connecting the boiler hot water riser pipe to the pony pump output side.

The pony pump's green hose will be connected to the pump's input side and the other end of the green hose will be placed into the blue bucket.

If you are using this procedure not for air removal but to install antifreeze, the bucket connected to the pump's input side contains the antifreeze product.

See ANTIFREEZE for BOILERS

Step 5: connect one end of a short garden hose length to the boiler drain valve. 

Heating boiler drain (C) Daniel FriedmanPlace the other end of this hose into the same 5-gallon bucket. The black hose (inside the blue bucket in our photo above ) will be connected to the boiler drain (photo at left).

Step 6: make sure that the heating zone valves and check valves are open, then open the boiler drain -

Watch out: At step 2 we turned off power to the boiler and we let it cool down enough to avoid getting scalded. Did you wait for things to cool down?

When you open the boiler drain you should see boiler water flowing into the bucket, covering the ends of both the input hose (from the boiler drain) and the output hose (connected to the pony pump input side).

Watch out: if the boiler drain is horribly corroded or very stiff, maybe you want to buy a replacement along with a roll of teflon tape so that if you're sorry you've ever touched the boiler drain (you opened it and now can't shut it off) you can fix that problem.

If you have boiler drain troubles you'll have to finish draining the boiler before you can replace the valve.

No water flowing? Check for closed zone valves or check valves

Watch out: While a motorized zone valve (below left) should open automagically if you set the room thermostat for each zone valve to well above room temperature and if the boiler is turned on.

But if you are working with the boiler power off (as we advised at step 2), on heating systems using motorised zone valves you will need to place the zone valve in manual-open position.

See ZONE VALVES, HEATING

- be warned that some zone valves don't have this manual-open lever,l in which case we may have to perform this procedure with the heating boiler turned back ON (that's what my service technician does) or worse, one may have to fall back to adding heating zones or installing zone valve bypass piping.

But if you waited for the boiler to cool down to a safe low temperature, as I've been begging you to do, when you turn it back on the zone valves will open up but you won't be dealing with scalding water.

You may also have to open the boiler's check valves (below right) on the zones being purged of air.

See CHECK VALVES, HEATING SYSTEM if you need to manually open these valves.

Below we show the operating lever on a boiler zone valve.

Pulling the lever all the way to the left and pushing it down will latch this zone valve into its "open" position. That's what you need to do, but don't forget to un-latch it when you've finished purging air from the system.

Zone Valve manual control lever (C) Daniel Friedman

And in the next photo below, a flow control check valve. Normally you won't have to mess with this valve but if you're having trouble pushing water through the system you might check that the valve is in the open position.

Thanks to reader GITOBY for reminding us to add these details - Feb. 2015.

Boiler check valve or flow control valve (C) Daniel Friedman

Step 7: open the service drain on the boiler heat riser pipe.

Step 8: turn on the pony pump. Be sure to keep the ends of hoses in the bucket always covered with heating system water (or antifreeze mix)

Step 9: watch for air bubbles appearing in the bucket. After you see air appearing as bubbles in the bucket, watch for the air to stop.

Also, if you are adding antifreeze to the heating system, this is the point at which you'd use the hygrometer to test the level of freeze protection in the mixture obtained so far.

Step 10: turn off the pony pump when no more air appears in the bucket,

Step 11: close the service drains on the heat riser pipe and at the boiler drain at the bottom of the boiler.

Step 12: Set the proper boiler cold water pressure: The automatic water feeder will put additional water into the boiler until it reaches its starting pressure.

If the boiler pressure is below its normal level the automatic water feeder should correct this problem. Watch the boiler pressure fill up to its normal cold pressure setting - typically this is around 12 psi on a two story home.

If the boiler pressure is too high and the boiler is cold, use the boiler drain to drop the boiler pressure to the proper starting level.

See WATER FEEDER VALVES, HYDRONIC BOILER

for a description of the typical pressures needed in residential hot water heating systems depending on the height of the highest radiator or baseboard above the heating boiler.

Step 13: turn on the heating boiler

 and assure that the thermostat is calling for heat. When the system has reached normal operating temperature and pressure, check the radiators, convectors, or baseboard sections that were previously cold - they should now be warm.

If the previously cold radiator (etc) still remains cold, either you have not removed enough air from the system or there is another problem causing loss of heat. In that case

see HEATING LOSS DIAGNOSIS-BOILERS.

Step 14: Check the boiler drain valve 

and the boiler heat riser service valve to be sure nothing is leaking. In an emergency we screw a garden hose cap on the end of a leaky heating boiler drain or service drain valve.

Step 15: Monitor heating system operation:

we never leave a property where we have worked on the heating system without first checking for leaks, inspecting for obvious safety hazards (such as a bad relief valve, blocked flue, improper oil or gas burner operation), and confirming that the heating system runs through it's on-off cycle normally.

How Do we Know That the Air Bleed Valve Operation Has Been Successful?

What size (horsepower) of Pony Pump do We Need to Force Air out of an Air Bound Heating System?

You should not need a very powerful pump to force water through an air-bound hydronic heating system, since the fact that nearly all of the heating pipes are already full of water means the pump does not have to have enormous lift capacity.

Little Giant pony pump The Little Giant™ MPFVK115 Portable 115 Volt Non-Submersible Steel Transfer Pump is one that we have used successfully in this application.

This is a non-submersible transfer pump made of stainless steel, operating on 115 Volts, and rated for 365 gallons per hour (some sources cite 1365 gph at 0 head or lift), produced by manufacturer Little Giant. Part No. MPFVK115.

Thanks to reader David Gould for discussing pump requirements (2010);

Contact us if you have other suggestions for improving this procedure. We are pleased to give credit and links to contributing reviewers, authors, or critics.

 

Thank you to our readers for their generous comments

Nice job you do describing how to purge hydronic heat system; I refer friends to InspectApedia now as I describe it about the same way, but it's easier for people to understand if they can read and refer back to this article. Thanks. Myron K Lochridge (Nov 8, 2011)

Awesome article! (Dec 29, 2012) Gene Friedman

...





ADVERTISEMENT





...

Continue reading at AIRBOUND HEAT SYSTEM REPAIR by WATER FEED VALVE or select a topic from the closely-related articles below, or see the complete ARTICLE INDEX.

Or see AIR BOUND HEAT SYSTEM REPAIR by PUMP FAQs - questions & answers about getting air out of air-bound heating pipes, posted originally at the end of this page.

Or see these

Recommended Articles

Suggested citation for this web page

AIR BOUND HEAT SYSTEM REPAIR by PUMP at InspectApedia.com - online encyclopedia of building & environmental inspection, testing, diagnosis, repair, & problem prevention advice.

Or see this

INDEX to RELATED ARTICLES: ARTICLE INDEX to HEATING RADIATORS

Or use the SEARCH BOX found below to Ask a Question or Search InspectApedia

Ask a Question or Search InspectApedia

Share this article:

Questions & answers on how to get rid of air in an air-bound heating systems by using a pony pump and the boiler supply and drain piping

Search the InspectApedia website

Need to make a private comment? Email editor@inspectApedia.com. We welcome email with your website content critique, corrections, suggestions or questions. Email is monitored daily but our workload may prevent an immediate reply. For immediate results, we hope you'll first try asking your question using the search box just above.

Citations & References

In addition to any citations in the article above, a full list is available on request.



ADVERTISEMENT