Building Inspection, Diagnosis & Repair Info

Square D Pumptrol Pressure Switch Adjustment Instructions - photo of pump switch cover label instructions -  Schenider Electric Square DPump Pressure Control Switch Adjustments

More Q&A on exactly how to adjust the pump pressure control switch - which way to turn the adjustment nut.

This article series describes how to adjust building water pressure by setting the water pump cut-in and cut-out pressure on the well water pump pressure control switch. We explain which adjustment nuts to turn and in which direction to change pump cut-in pressure or cut-our pressure settings.

InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers, products, or services discussed at this website.

- Daniel Friedman, Publisher/Editor/Author - See WHO ARE WE?





ADVERTISEMENT





Pressure Control Switch Adjustment Nut FAQs

These questions and answers abouit how to adjust the control nuts in a water pressure control switch were posted originally

at WATER PRESSURE CONTROL SWITCH ADJUSTMENTS - topic home.

Also see our index to all water pump control switch FAQs at WATER PUMP PRESSURE SWITCH REPAIR FAQs

Article Index

...

Pressure Control Switch Calibration Q&A

Do I use a pressure gauge to set the pump cut-in and cut-out?

Do you use the pressure gauge to set the psi by what it shows when the switch kicks on and off?

It says to set at 28 psi.

But there are no numbers on the switch, how do you know what you are setting it at?

Having a problem, just replaced my water pressure tank. Have a submersible pump. Problem is that when running the water the pressure switch is short cycling. it will go off and on about 4 times real fast then stop about 20 seconds then do that again. How do I adjust it ? On 2018-10-16 by Teresa Jarrell

by (mod) - how to determine the pressures at which the pump control is turning ON and OFF

Teresa

You can use an independent pressure gauge Teresa or you can see what the pressure is on the gauge that's attached to your water system.

To use an independent gauge - it's easy and inexpensive - see WATER PRESSURE MEASUREMENT - how to buy or make your own portable water pressure measurement gauge

When the pump STOPS and with NO water running in the building, read the water pressure system at the pressure gauge you'll find on or near the pump or water tank.

About the short cycling of your water pump, most likely your water tank has lost its air-charge.

But if the short cycling is extremely rapid I would look first for a closed valve on the outlet from the water system and second for problem with water not entering the tank. I've also found this problem when there is a water filter installed and the water filter is clogged.

Sometimes then a pressure tank the bladder can get stuck to the tank bottom and refuse to accept water. Both of those conditions can cause rapid short cycling.

See the diagnosis and repair steps at WATER PUMP SHORT CYCLING - home

Also see WATER PRESSURE GAUGE ACCURACY 

...

Pressure Controls for Multiple Water Pumps in Tandem

Pressure control settings when using two water pumps on the same system: ok to have manual pump cut-off?

Pump control switch adjustment (C) Daniel FriedmanI want to set our pressure switch settings for water

Pump #1 should be start on 4 kg/cm2 and stopped on 6 kg/cm2.

Pump #2 should start only 3 kg/cm2 and off manually - On 2018-02-08 by Abhimanyu Mishra

Suggestions by (mod) - each pump needs its own pressure control

Mishra

You cannot control two different pumps at different operating pressures using a single pump pressure control switch.

You need a dedicated pressure control for each water pump.

Then, if both pumps are feeding the same water system and tank, the controls need to be set to work consistently.

By your description, IF Pump #1 has adequate capacity and IF the water capacity is constant, then pressure will never fall below 4 kg/cm2 so Pump #2 would never run.

And when IF Pump #1 is capable of pumping to any pressure above its CUT-ON or CUT-IN pressure, Pump #3 will never run.

Details:

Although our pressure examples are in PSI, the principles and adjustments of a pressure switch are the same regardless of the units in which pressure is being reported.

4 kg/cm2 is about 57 psi and 6 kg/cm2 is about 85 psi (for other readers).

If your pump control switch works like the one shown in the article above you simply need to watch the pressure reading on your system's pressure gauge.

Run water, watch the pressure fall, note the pressure at which the pump starts. Adjust the switch to raise or lower the starting pressure accordingly. That's the "CUT IN" pressure.

You cannot however use the same control on the same single water system to operate at two different pressure ranges.

So I don't understand how your second pump control example would work unless you mean it's for a different system.

Watch out: In any event you should NOT set up a switch that will never turn the pump OFF since under some conditions the pump pressure could blow out a pressure tank or pipe that could in turn injure or even kill someone nearby.

...





ADVERTISEMENT





...

Continue reading at WATER PRESSURE CONTROL SWITCH ADJUSTMENTS or select a topic from the closely-related articles below, or see the complete ARTICLE INDEX.

Or see these

Recommended Articles

Suggested citation for this web page

PRESSURE SWITCH NUT ADJUSTMENT FAQs-2 at InspectApedia.com - online encyclopedia of building & environmental inspection, testing, diagnosis, repair, & problem prevention advice.

Or see this

INDEX to RELATED ARTICLES: ARTICLE INDEX to WATER SUPPLY, PUMPS TANKS WELLS

Or use the SEARCH BOX found below to Ask a Question or Search InspectApedia

Ask a Question or Search InspectApedia

Share this article:

Search the InspectApedia website

Need to make a private comment? Email editor@inspectApedia.com. We welcome email with your website content critique, corrections, suggestions or questions. Email is monitored daily but our workload may prevent an immediate reply. For immediate results, we hope you'll first try asking your question using the search box just above.

Citations & References

In addition to any citations in the article above, a full list is available on request.



ADVERTISEMENT