Flood Damage Repairs for Brick Veneer Walls
Repair options for homes subject to flood damage through brick veneer walls:
Area flooding sends water and mud through weep openings and into veneer wall cavities.
Here we describe three repair options for flood-damaged veneer walls built over hollow framed-wall cavities. Option 1: rebuild the first floor walls with solid masonry, Option 2: retain the exterior veneer wall but repair from the inside to create a Sealed Flood-Resistant Veneer Wall, and Option 3: repair from the inside using styrofoam insulation but making no effort to build a flood resistant veneer wall.
We also discuss options for repairing a veneer wall and modifying its weep openings or drainage when interior demolition involves only the lower portion of existing walls.
This article series discusses brick or stone veneer wall construction and flood damage repairs. Page top sketch courtesy of Carson Dunlop Associates, a Toronto home inspection, education, and report-writing tool company.
InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers, products, or services discussed at this website.
- Daniel Friedman, Publisher/Editor/Author - See WHO ARE WE?
Shown here in our photograph contributed by a reader is the interior of a Texas home flooded during Hurricane Harvey in 2017, after initial demolition has been completed: drywall was removed from the floor up four feet, and the insulating board sheathing on the exterior wall was cut away from the inside for a height of about two feet above the wall sill plate.
[Click to enlarge any image]
This article is a continuation of BRICK VENEER WALL LEAKS in FLOOD PRONE AREAS.
That article discusses the first priorities of action if your brick-veneer or brick wall home has been damaged by flooding: things to do for safety and to minimize mold contamination.
There we also describe steps to take if you anticipate flooding and want to try to reduce water entry through the exterior walls.
Here we continue our brick veneer wall design, drainage, and waterproofing topic with a discussion of approaches to re-build, repair, or modify a brick or brick veneer wall building to help resist water damage from the next flood.
Carson Dunlop Associates' [website link] sketch at page top illustrates typical brick veneer wall construction.
Speaking with an architect who is familiar with brick veneer wall troubles when exposed to flooding in homes the professional had two suggestions to reduce flood damage to brick veneer wall homes:
2017/09/25 Michelle
I flooded here in Texas in the Harvey storm and when we pulled off the first 2 ft. of drywall and insulation we found a lot of mold on the black moisture barrier paper and also on the exterior wall sheathing approx. 3"-24" the flood insurance adjuster told us to remove 4ft of drywall and also the exterior sheathing as it was wet and moldy.
Which we did and now have studs and exposed brick from 2'-4' (which also has holes in the mortar at various spots etc). The house was built in the early to mid 70's.
The problem is that no one seems to be sure how to fix the problem (everyone has an opinion) and the flood adjuster said there is a product that their report will recommend (we do not yet have the report) but of course no need to go from the brick side.
A FEMA rep. stated that the proper way to replace that is to remove the brick section by section to insert the Tyvek and sheathing board, but insurance wont want to pay for that.
What is the best way to fix this to avoid problems down the road and do I get the contractor to battle with the insurance company or is there any type of product that can be on the bricks to seal out the water? Sorry if I sound ignorant on this but I am beside myself with worry and know very little about construction and how to argue the points or if it is necessary.
I did as I was advised but no one tells you how difficult to remedy the problem. Any help appreciated.
This question was originally posted at FIBERBOARD SHEATHING MOLD CONTAMINATION
Michelle
Choosing the best repair method for flood-damaged veneer walls where an insulating board sheathing was used is difficult but there may be some approaches that are much better than the FEMA advice you cited.
Please see BRICK VENEER WALL REPAIRS in FLOOD PRONE AREAS [this article on this web page] as the best information we have to date. Take a look at the options for repairing brick veneer walls and post further questions and comments there or contact me by Email.
I would NOT follow FEMA's first response. That advice that you report is not consistent with FEMA flood damage repair and prevention documents that we cite in this article, and is in my opinion given by someone for whom money is no object - or perhaps thinking that she or he is spending "other people's money". It's advice that is safe for the advice-giver but not necessarily very nice for the recipient.
Equally troublesome is that the advice you describe offers no improved resistance to water damage from the next flood.
The argument that Texas saw a "once in a thousand years" hurricane is not one that I would trust considering the effects of global warming on the ferocity of hurricanes, particularly hurricanes developing over the Gulf of Mexico.
While it's not itself a scholarly article, Jason Samenow, writing in the Washington Post on 22 March 2017 reported well ahead of the recent and severe hurricanes striking both Texas and Florida:
The warm water temperatures in the Gulf of Mexico, in particular, could mean that thunderstorms that erupt over the southern and central United States are more severe this spring. Berger explained in his Ars Technica piece:
“While the relationship is far from absolute, scientists have found that when the Gulf of Mexico tends to be warmer than normal, there is more energy for severe storms and tornadoes to form than when the Gulf is cooler.” - The Washington Post, 22 March 2017, www.washingtonpost.com/news/capital-weather-gang/wp/2017/03/22/gulf-of-mexico-waters-are-freakishly-warm-which-could-mean-explosive-springtime-storms/?utm_term=.77583ff7e08e
If you can, use the page top or bottom CONTACT link to send me some sharp photos of the exterior of the home and details of its veneer wall, and the interior of the home and the exposed veneer wall and I can offer more specific advice.
Also, the advice to remove four feet of material might be incorrect and arbitrary, depending on the depth to which your home was flooded.
You need to remove material that was soaked and /or is mold contaminated. Typically we remove material until we have at least 12" of clear margin - mold free material remaining. Do NOT forget to inspect the cavity side of the drywall for mold.
If you are re-building a flood-damaged home in a flood prone area, you should consider replacing the lower floor walls with a high-lime-mortar based solid masonry structure that can withstand flooding with much less damage.
Other sources suggest alternative strategies that we consider less reliable but probably less costly than a re-build of the structural wall.
Suitable where flood depths are no more than two feetHere we describe flood damage prevention to a brick veneer wall home by working only from the interior, preserving the original exterior brick veneer.
FEMA's similar proposal, illustrated in our sketch adapted from FEMA's information cited below, presumes that the building exterior must be demolished and re-built - a more costly approach that results in about the same situation as what Option #2 describes.
[Click to enlarge any image]
First damaged drywall, insulation and insulating board or gypsum board exterior sheathing are removed by working from the building interior.
Use closed cell foam in the wall cavities and other waterproof or water resistant materials such as cement board instead of drywall to minimize future water entry into the wall cavity itself and to reduce water damage to wall covering on the interior in future flooding.
Done with care this approach may improve the resistance of the building to future flood damage.
Watch out: this approach alone cannot assure that flood waters will not enter a home exposed to standing floodwater: water enters at windows,doors, openings and perhaps under the wall sill plate or through penetrations.
The object here is to reduce future flood damage by repairing a flood-damaged veneer wall with materials that keep water out of the wall cavity. We use only materials that are themselves waterproof or water resistant such as closed cell foam insulation in the wall and cement board on the interior wall surface.
Discuss with the foam manufacturer the tolerance of their product to future flood conditions.
For option #2 (Sealed Flood-Resistant Veneer Wall ) two situations must be considered:
Watch out: as FEMA warns in the document cited just below,
Adding a waterproof veneer is appropriate in areas where the flood depth is less than 2 feet. When flood depths exceed 2 feet, the pressure on waterproofed walls increases greatly, usually beyond the strength of the walls. If greater flood depths are expected, consult with a licensed civil or structural engineer before using this method.
This building flood damage resistant construction advice from U.S. FEMA recommends a design very similar to this Option #2 flood-resistant brick veneer wall design. The essential difference is that the FEMA description presumes you are removing and rebuilding the walls from the building exterior.
Watch out: The most-expert brick construction people in the U.S., represented by the BIA, do not agree with the FEWA nor the Option 2 approach described above.
Mr. Z. Booker was kind enough to respond to a request for technical review of this article. We report his advice below:
The proposed repairs that recommend filling the air space/drainage cavity with closed cell spray foam do not meet code-mandated requirements nor do they conform to BIA recommendations as noted in the BIA Technical Notes linked below. These proposed repairs may severely impact the performance of the wall by eliminating or compromising the following critical components of the wall assembly: air space/drainage cavity, flashing, sheathing, water-resistive barrier, and brick ties.
BIA Technical Notes -
http://www.gobrick.com/Technical-Notes
The best approach to repair damaged sheathing in a brick veneer/wood stud wall involves replacing the sheathing from the exterior in order to ensure that repairs to all components conform to code-mandated requirements or better.
Whatever approach is implemented, the local building code official should be consulted before a contractor is engaged to begin repairs as some jurisdictions require a building permit for these types of repairs.
Be advised that if the proposed repairs differ from code-mandated requirements, the local building code official will need to determine whether they are acceptable. Most local jurisdictions can advise on methods they have approved for these types of repairs.
If you have any further questions, feel free to contact me directly.
Zachary J. Booker, EIT
Engineer
Brick Industry Association
cid:image004.jpg@01D1BC0E.85825410
12007 Sunrise Valley Drive, Suite 430
Reston, VA 20191
Office: (703) 674-1547
Email: zbooker@bia.org
This approach combines cleaning water-damaged brick veneer walls from inside and more-traditional repairs, changing only the wall insulating materials: eliminate fiberglass and use styrofoam.
According to some of our readers corresponding by private email, this is the Brick Industry Association (BIA)'s recommendation.
Some insurance adjusters recommend removal of wet drywall, exterior sheathing board, insulating board or gypsum board (plywood that is not delaminated might be left in place), cleaning the wall cavity, installing 1" styrofoam against the veneer wall, and use of traditional insulation or more loose-fit or custom-cut styrofoam and drywall to complete the wall repair.
Watch out: Adjusters or contractors who recommend this approach do so out of a an important concern: drying out an Option #2 Sealed Flood-Resistant Veneer Wall after future flooding will be difficult. That's correct if Option #2 is not implemented correctly.
For example if a builder uses conventional drywall on the wall interior or if they do not properly prepare, clean, and insulate the wall cavity to fill it with closed cell foam water may penetrate and sit in the wall cavity after flooding.
Watch out: however this approach means that the same veneer wall repair will be required in every future flooding event - an event more-likely in view of global warming and changing weather patterns. This approach foregoes an effort to re-build with a flood-damage-resistant approach.
Question: how should I restore this flood-damaged brick-veneer-walled homeI'm single mom to a one year old and just recently had 18 inches of water in my house due to Harvey in Dickinson, Texas.
The restoration company, after remediating and dehumidifying for 2 weeks said the blackboard between the studs and the brick needed to come out.
We called the insurance adjuster and he agreed.
[Click to enlarge any image]
My question moving forward is how do we rebuild things.
I'm getting different answers from contractors and given I'm a woman on my own, I don't want to be taken advantage of and want to ensure the safety of my daughter and I in the future.
I read some of your articles but still unsure the best way to rectify this situation to make this right.
I appreciate your help. - Anonymous by private email 2017/09/17
There are several options, depending probably on cost, what the insurance company will pay-for, and what resources are available, as well as depending on who is available to do the work.
Details of our discussion with this homeowner and a description of each repair option for this home have been moved to BRICK VENEER WALL FLOOD DAMAGE REPAIR
As climate change and increased storm severity will continue to increase the extent of flood damage to buildings other countries will want to study more-closely what flood damage control measures have been developed by the Netherlands, England, and Venice, Italy.
In the Netherlands a combination of dams, dikes, floodgates and natural sand dunes prevent flood water entry, an approach that combines with a combination of drainage canals and pumping stations to keep water out of low areas.
In the U.K. a combination of natural measures such as tree planting have been shown to reduce flooding but in 2016 the Department of Environmen t, Food and Rural Affairs (DEFRA) reported that there is no funding specifically for flood management.
In north-eastern Italy, where the Venetian Lagoon has been settled since around 400 A.D., flooding has been a recurrent condition.
Venice in fact includes among its sobriquets the name "Floating City" as the city of Venice on its main "island" is actually comprised of many small islands connected by bridges and sports large stone structures as well as stone paved streets built atop pilings.
In 2017 we visited Venice to photograph flood conditions and the measures taken by Venetians to cope with flooding.
Venetians cope with annual flooding or Aqua Alta [high water] that arrives in Venice each year between September and April, with particularly severe flooding during October through December.
Aqua Alta in Venice is caused by a combination of rising sea levels, unusally high tides (typically during a new moon or a full moon), low barometric pressure, and a sirocco wind that blows waters from the Adriatic Sea into the Venetian Lagoon.
Aqua Alta occurs (currently) whenever the tide is about three feet (90cm) above normal.
Venetians have coped with flooding by a variety of measures including raising the first floor level, moving living spaces to the second floor of buildings, using flood-damage-resistant solid masonry (no mold and water-damage friendly drywall nor hollow frame wall construction) on lower floors, and the installation of a combination of flood vents in foundations and wall drain openings that allow water back out of masonry and cavity walls.
The MOSE Project (MOdulo Sperimentale Elettromeccanico, Experimental Electromechanical Module) to install flood gates at the Venice Lagoon entrance and raised pavement areas in lower areas of the city also attempt to address Aqua Alta flooding in Venice. Construction of the MOSE flood gates, though not without considerable controversy is expected to be complete and operational in 2018.
Our photo above shows the equivalent of flood vents at the bottom of a masonry wall in Venice, Italy. In the last centry the arrival of aqua alta in Venice has increased from about ten times a year to more than 60 such flood events each year.
Below, also a building in Venice, Italy, we see both foundation flood vents used where the building structure includes open space below grade and elevated drain openings in the brick cavity wall.
This information is now found at BRICK VENEER WALL FLOOD REPAIR CODES & STANDARDS along with a list of technical reviewers of this article series. CONTACT us to suggest additions or corrections to this article.
...
Continue reading at BRICK WALL DRAIN, FLASHING, VENT SOURCES or select a topic from the closely-related articles below, or see the complete ARTICLE INDEX.
Or see these
BRICK VENEER WALL REPAIRS in FLOOD PRONE AREAS at InspectApedia.com - online encyclopedia of building & environmental inspection, testing, diagnosis, repair, & problem prevention advice.
Or see this
Or use the SEARCH BOX found below to Ask a Question or Search InspectApedia
Search the InspectApedia website
Need to make a private comment? Email editor@inspectApedia.com. We welcome email with your website content critique, corrections, suggestions or questions. Email is monitored daily but our workload may prevent an immediate reply. For immediate results, we hope you'll first try asking your question using the search box just above.
In addition to any citations in the article above, a full list is available on request.