Building Inspection, Diagnosis & Repair Info

Brownstone lintel in brick wall © Daniel Friedman at InspectApedia.comBuilding Facade Damage, Lintel Damage & Falling Hazards in Masonry Walls

  • POST a QUESTION or COMMENT about brick wall lintel damage cause, cure, prevention for steel lintels & brownstone lintels in masonry buildings

Steel or Brownstone Lintel Damage in Brick or other Masonry Walls:

How do caulking or improper installation cause damage at window & door openings in masonry walls: caulking a steel lintel or failure to protect a brownstone lintel from water or frost damage can result in not only damage at the lintel and wall opening but even severe cracking, settlement or failures in the wall structure.

This article series explains types of damage to structural brick walls & how that damage is identified & repaired. We explain how to recognize, diagnose, & evaluate movement and cracks in brick walls and how to recognize brick wall bowing or bulging and cracking failures.

InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers, products, or services discussed at this website.

- Daniel Friedman, Publisher/Editor/Author - See WHO ARE WE?





ADVERTISEMENT





Lintels: Water, Frost, & Rust Damage at Steel Lintels over Windows or Doors in Brick Walls

Steel window lintel in brick wall © Daniel Friedman at InspectApedia.com[Click to enlarge any image]

Our photo (above/left) shows a rusting steel lintel in a brick wall. Luckily in this case, the worst rust damage and exfoliating (flaking rusting) steel is over the window itself (at the right side of the photo).

But in the 1980's we examined a New York City high rise building that had very expensive damage to nearly all of its brick exterior walls.

Spalling and cracking had rather suddenly occurred at almost every window and door in the building not long after a new building maintenance superintendent had been employed.

The new maintenance supervisor had ordered that all window and door lintels should be caulked where he had observed a gap between the upper surface of the steel lintel and the brick above. Unfortunately that caulk job trapped water above the lintel where frost (short term rapid damage) caused severe brick spalling and cracking.

On other brick buildings whose windows and doors use steel lintels (to support bricks that must span over the opening), rusting steel lintels can also cause severe brick cracking and spalling. The lifting power of exfoliating steel (flaking rust) is very great.

Don't caulk between the bricks and the steel lintel that supports them on a masonry or masonry-veneer building.

Steel lintel in brick wall © Daniel Friedman at InspectApedia.com

On the other hand, it is usually ok to caulk on the underside of the lintel where it contacts the top of the window frame itself - our photo at left.

Steel lintel in brick wall © Daniel Friedman at InspectApedia.com

A different steel window lintel problem is shown in our photo at left. It looks as if the window lintel is too short, extending less than an inch into the brick wall to the left of the window.

Especially if there is any evidence of cracking or brick wall movement, some careful inspection and further investigation would be needed in this area (perhaps there is a hidden window lintel or support not visible from the building exterior.

Masonry & Brownstone Building Facade, Window & Door Lintel or Sill Falling Hazards, Damage & Repair

Brownstone lintel in brick wall © Daniel Friedman at InspectApedia.com

Our photo (above-left) shows spalling and cracking damage in brownstone lintels in a brick building in Hudson, New York. It appears that leaks at the roof parapet wall, itself now replaced, damaged the brownstone lintel over the white entry door.

In addition to the risk of damage throughout the brick wall as this deterioration continues there is a potential hazard from falling masonry fragments. Special installation & repair methods are needed for these water-vulnerable stone materials.

Protect People from Falling Building Facade Components

Watch out: for falling cornice parts, lintels, & window sills on brownstone buildings & all old structures. Casual inspection from ground level may fail to detect loose building facade, cornice, or window components that can fall, injuring or even killing someone. A casual inspection from ground level and even an inspection using binoculars from ground level cannot find all loose building facade components.

A close inspection from scaffolding, ladders can more thoroughly detect frost damage, rusted cast iron cornice parts, loose building facade components, or cracked, loose window lintels or sills. But even then, a complete detailed inspection of "every inch" of a building facade is cost-prohibitive.

Still, if loose components are found or even suspected on a building facade, the area below should be closed off from access to prevent injury until the urgency of need for repair can be assessed or until repairs are made.

And an experienced inspector may be able to spot conditions such as leak stains from roof defects, improper flashing, or wind-driven rain, cracks in masonry facade from rusting steel lintels, or out of plumb and level conditions that are telltale signs of an unsafe building facade.

In some cases it may be feasible to construct safety netting, or to construct scaffolding with plank or corrugated steel roofing to protect pedestrians at ground level from being struck by falling building components.

The risk of falling building facade parts is a real hazard not just a theoretical one. For example, on Sunday, 17 May 2015 a two year old girl, was killed by a falling section of a windowsill in Manhattan. On the following day she died from that injury.

The New York Times reported that Greta Greene and her grandmother, Susan Frierson, were struck by a piece of decorative terra cotta windowsill that fell from the Esplanade Luxury Senior Residences from a height of eight stories above where they were walking. The facade had been inspected and deemed safe in 2011. Terra cotta facades require special maintenance to avoid falling hazards. (Hoigard 2004).

While New York City has a law requiring the inspection of building facades for just such hazards, the law alone cannot prevent all such accidents. The New York City law requires that a facade inspection is required every five years for buildings taller than six stories. That law covers about 13,500 buildings in New York City. - The New York Times, 2015.

The same Times article reported a similar death in 1979 when Grace Gold was killed by a falling fragment of a building cornice that came away from a Morningside Heights apartment building. Nine deaths and 250 falling building facade objects occurred in New York City between 2009 and 2014.

Also see BRICK VENEER WALL LOOSE, BULGED

Research on Brownstone, Sandstone, Stone Building Restoration & Repair

...




ADVERTISEMENT





Reader Comments, Questions & Answers About The Article Above

Below you will find questions and answers previously posted on this page at its page bottom reader comment box.

Reader Q&A - also see RECOMMENDED ARTICLES & FAQs

On 2023-10-21 by InspectApedia Publisher

@James,

We're glad to assist; your questions and photos are helpful to other readers.

On 2023-10-21 by James

@InspectApedia DF, Ok thank you all for your guidance. I will likely scrape out the last bit if remaining mortar in that space and just leave it open.

On 2023-10-19 by InspectApedia DF (mod) - Should the lintel gap be filled to prevent bulk water entry in rain?

@James,

I would not fill the gap between the upper surface of a steel lintel over a window or door and a brick veneer above it: doing so can trap water in the wall leading to more-serious leak damage. Leave that gap open so that any water can drain out.

The lintel should be an L-shaped length of steel with the upper arm of the "L" extending up inside the wall behind that course of brick. So water entering the wall from rain should exit either at weep openings in the wall or above the lintel.

On 2023-10-19 by James

@InspectApedia Publisher, Should the gap be filled to prevent bulk water entry in rain?

On 2023-10-19 by InspectApedia Publisher

@James,

Looks like a common brick made with round holes in its center, nothing unusual there.

On 2023-10-18 by James

@InspectApedia Publisher, So upon further inspection, it seems this is the type of brick that was used, at least above/on the lintel.

thinveneerbrick (dot) com/sale-9247161-red-five-holes-clay-brick-hollow-clay-blocks-for-building-wall-construction (dot) html

It is hard to demonstrate with my photos, but there are 5 evenly space gaps on each brick. They do seem to be weathered, but from what I can tell most of the middle sections and all of the backsides I can see are touching lintel.

The picture I am adding demonstrates 2 of the evenly spaced gaps and light shining through to the inner portion of the backside of the brick. So what are your thoughts on this? Because I haven't the slightest idea what to think.

gap between brick veneer and lintel (C) InspectApedia.com James

On 2023-10-18 by InspectApedia Publisher

@James,

If it's a brick veneer it would normally be only one brick wide as a layer of a veneer secured to a structural wall behind and hopefully with drainage weep holes at appropriate locations.

If it's a structural brick wall then yes it'll be more than one brick in wall thickness and normally we will see bond courses every five courses or so.

On 2023-10-18 by James

@InspectApedia Publisher Thanks for the prompt response. I was planning on getting a better look when the sun goes down as it was difficult to see well in that gap due to ambient brightness in daytime.

From what I could see it seems there is another brick layer behind that gap, maybe an inch or 2 behind within the gap. Again, I need to get a better look come sundown.

I was able to probe in one spot as well and it seemed that whatever it is within the gap (brick or otherwise) was making contact with the lintel as my small flathead was unable to penetrate the the bottom corner where the two meet. Hope that makes sense. As soon as I get a better look I will update.

On 2023-10-18 by InspectApedia Publisher - how to handle a gap between the upper surface of a steel little and the bottom age of the brick veneer above

@James,

Thank you for a challenging and helpful question about handling a gap between the upper surface of a steel little and the bottom age of the brick veneer above.

We have at least two concerns that I suspect both you and I are considering:

1. Don't block and trap water atop the steel lintel or it may rust, exfoliate, and move and damage the bricks above - so allow drainage, don't caulk or seal that space

2. The lintel should support the brick veneer above lest the bricks crack, move, and even risk falling off of the building, both water damage and safety concerns.

At original construction I'd have expected the underside of the bricks to rest on the lintel surface.

At this point I'd

1. Inspect the veneer around and above the window with care, looking for any signs of cracking that might hint at veneer movement.

If are no signs of movement we'll both breathe a sigh of relief, guessing that either the back of the lintel is still supporting the veneer or the veneer is well tied to the building's supporting structural wall behind the bricks.

2. look with a good light into the gap between the underside of the bricks and the upper surface of the lintel: if you see that back in the wall the bricks are actually touching the lintel you're probably fine leaving the gap open as we're discussing.

If not, you might add some mortar in the joint, but take care to leave drain openings at no less than every other vertical brick veneer mortar joint.

But first complete the rust cleanup and priming step that you have already mentioned.

If you can get a close-up photo of the space in that gap between the lintel top and brick underside I'd like to see that, especially if with a light we can see into that gap.

On 2023-10-18 by James

I need some guidance/opinion concerning the lintel above my window on brick veneer siding. I had orginally caulked the area directly above the lintel, between the brick and lintel. That was about 5 years ago, when I knew no better.

Now, I am slightly more educated so decided to remove my caulk job. But it revealed the reason I believed it needed caulking in the first place. There is a slight gap that runs along the length of the window between the lintel and row of brick.

It seems there was mortar there at some point, I have attached an image and circled the area of concern that still has mortar. The rest has seemingly disipated over the years I assume.

I am wondering what needs to go between that space? Should I use mortar to fill the void? I am preparing to remove rust, prime/repaint the lintel as I didn't know that was a problem until recently.

Of note the rust was there 5 years ago when I caulked the gap and seemingly hasn't really gotten worse. Also of note, there is no known/evident issues on the interior of the wall. Thank you.

gap between brick veneer and lintel (C) InspectApedia.com James

On 2021-08-11 by inspectapedia.com.moderator - building has settled to one side causing masonry leaks around glass block windows

@Frederick West,

Your / our first concern has to be the safety of the building occupants.

Depending on the country an city where your building is located, you have different resources available;

In the U.S. you might want a structural or civil engineer who is familiar with masonry building construction, diagnosis and repair, perhaps with help from an experienced mason.

In the U.K. you can find a similar engineer or perhaps a member of RICS - a chartered surveyor of building condition.

Don't focus on the small problem indicators before you and building management are confident that there are no significant structural and safety concerns at your building.

Use a local search (country and city) + structural engineer, civil engineer, or in UK a chartered surveyor.

On 2021-08-11 by Frederick West

I think my building has settled to one side causing masonry leaks around glass block windows once inside the water travels on top of my lentils and causes damage to the plaster beneatrh my windows. I need a good person who can figure out just what can be done to stop this damage.

This three flat apartment building and each apaartment shows moisture damage from water or saturation. I could ue some good advice. I have caulked windows, tuck pointed the masonry, I just put on a new roof and gutters. HELP

On 2019-09-20 by danjoefriedman (mod) - builder did not use any lintels in the poured concrete walls of my home.

RE-Posting

Ken said:

It appears the builder did not use any lintels in the poured concrete walls of my home. As a result the walls have fractured and dropped down slightly above all window and door openings. Is there a fix for this problem? If yes, what type of contractors do this work'

Moderator reply:

Ken

But yes, there's always a fix, the question is more just what ought to be done and what will it cost.

I can't diagnose your exact situation by e-text (though photos would help), but most likely, if the movement that has already occurred is insignificant, it may be possible to cut out sufficient space above the windows to install a lintel of sufficient strength to avoid further problems.

The size and type of lintel needed depend on the building type, construction materials, and conditions, and might range from a steel lintel to reinforced concrete to stone or something else.

I'd like to see photos of the situation. Use the Add Image button to add one photo per comment.

[This Q&A were posted originally

at STRUCTURAL INSPECTIONS & DEFECTS]

On 2017-04-20 by danjoefriedman (mod) - be cautious about burying wood in a masonry brick wall

OPINION

I'm cautious about burying wood in a masonry brick wall - if there is the slightest chance of water or insect attack rot and damage will ensue. I'd prefer to use masonry or reinforced masonry.

On 2017-04-19 by James

I have a old brick home with 3 course brick wall. I am repairing the front entrancend brick work to install a new door. Can I use 2 L lintels with a wood 4x4 between them?is the 4x4 a problem?

On 2015-12-03 by danjoefriedman (mod) - lintels above many of the windows are warped and rusting with gaps

Ken,

You need an expert on site to help decode if lintel replacements are needed - as it sounds. Where lint els are to be replaced one may be tempted to temporarily seal them, but as water enters the wall above the result could be worse damage and leaks as water is trapped.

You might reduce the leak problem if you can find and stop leaks into the wall itself

On 2015-12-03 by Ken

Lintels

We have a home built in 1928. I believe (but not positive) the walls are constructed of brick, concrete bloc, and plaster. The outside brick wall is in excellent shape with no visible cracks, spalling,bulging, etc., but the lintels above many of the windows are warped and rusting with gaps - I would estimate up to to 1/2 inch - in places above the lintels. There are no weep holes in the brick wall that I can see.

Is there anything that could be done temporarily to stop potential water intrusion and get us through the winter. For example could a masonry and concrete caulk be used with (plastic) weep holes embedded in the caulk? Or would the admonition to not caulk above the lintel still apply? What could be done to counter the rust?

Will it be necessary to replace the lentils for a permanent solution? If replacement is necessary is there danger in replacing several (say 20) in a brick wall in a short period of time?

...

Continue reading at BRICK WALL THERMAL EXPANSION CRACKS or select a topic from the closely-related articles below, or see the complete ARTICLE INDEX.

Or see these

Recommended Articles

Suggested citation for this web page

MASONRY FACADE / WALL, LINTEL & BROWNSTONE DAMAGE at InspectApedia.com - online encyclopedia of building & environmental inspection, testing, diagnosis, repair, & problem prevention advice.

Or see this

INDEX to RELATED ARTICLES: ARTICLE INDEX to BUILDING STRUCTURES

Or use the SEARCH BOX found below to Ask a Question or Search InspectApedia

Ask a Question or Search InspectApedia

Share this article:

Search the InspectApedia website

Need to make a private comment? Email editor@inspectApedia.com. We welcome email with your website content critique, corrections, suggestions or questions. Email is monitored daily but our workload may prevent an immediate reply. For immediate results, we hope you'll first try asking your question using the search box just above.

Citations & References

In addition to any citations in the article above, a full list is available on request.



ADVERTISEMENT