Building Inspection, Diagnosis & Repair Info

Photograph of ice on an electric meter and ice on the service entry cable at a building in Rhinebeck NY (C) Daniel FriedmanWinterizing Guide, Heat Turned Off

Winterizing a building: how to freeze proof a building when heat will be turned off:

This article explains with a step by step guide just how to winterize or freeze proof a building when the building's heating system is going to be turned off completely.

We discuss turning off water supply, draining piping and plumbing fixtures, turning off and if necessary winterizing a heating system, and other steps to avoid freeze damage or water, leaks, and mold damage to buildings that are being left in a "shut down" condition.

The articles at this website will answer most questions about freeze protection for piping and other building plumbing and heating system components: how to winterize a building to avoid frozen pipes, and how to thaw frozen water supply & drain piping, wells, & water tanks.

InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers, products, or services discussed at this website.

- Daniel Friedman, Publisher/Editor/Author - See WHO ARE WE?





ADVERTISEMENT





How to Winterize a Building If you are Turning the Heat Off - 10 Steps to Freeze Protection

Outdoor plumbing faucet schematic (C) Carson Dunlop Associates

[Click to enlarge any image] Sketch above courtesy of Carson Dunlop Associates.

Is the building heat going to be left "on" or "off" - the answer determines the extent of freeze-proofing needed.

 

Steps to Winterize a Building with Heat Off

If you have decided to shut down the building's heating system, some steps to protect the building from freeze damage are simple (you don't worry about figuring out the thermostat set-temperature nor about finding "cold spots" where pipes may freeze).

Incidentally, don't make this common mistake: never leave a garden hose attached to your outdoor faucet in winter as water in the hose may add to the risk that the faucet will be freeze damaged. See details about outdoor faucets, hose bibbs, sillcocks

at FAUCETS, OUTDOOR HOSE BIBBS and

at FAUCET, SILLCOCK ANTI SIPHON / FROSTPROOF LEAK REPAIR.

But other critical steps need to be performed if you are going to avoid frozen pipes and future leaks and water damage in a building to be winterized with the heat left off (such as an empty summer cabin, vacation home, or an unoccupied residence.)

  1. Close the main building water supply valve.

     Check that the valve really closed fully during the process of draining the piping. Be careful: some valves that are seldom used or which are old may not close off completely.

    You just think you've turned off the water supply, but really your water main valve may still be slowly feeding water back into the supply piping.

    Details on how to find and use water shutoff valves is

    at WATER SHUTOFF VALVE LOCATION, USE.
  2. If a water pump and pressure tank are installed, 

    turn off electrical power to the water pump. (Draining the pump and water tank are discussed below.)
  3. Drain the building water supply piping;

    because most homes other than some vacation cottages are not built with piping intended to be periodically drained, there may be long horizontal pipe runs that will not easily drain out all of their water by gravity, or even some supply pipes that slope "backwards" and refuse to drain.
    1. Use air to remove water: 

      Some plumbers try blowing air through the piping to force out water, or they may install multiple points at which piping can be drained. Below we address some steps to check for frozen, burst piping when turning the water supply back on.
    2. Cut pipes to remove water:

      Other plumbers will simply cut open any water supply pipe that may not be draining properly, figuring that it's a much smaller repair to later close that cut connection than to fix a building that has been flooded.
    3. Use the building drain: 

      Most buildings include a building drain valve located at or near the lowest point in the building supply piping, but "inside" the building or past the main building water supply shutoff valve.
  4. Drain the building plumbing fixtures, tanks, faucets, such as
    • Winterize hot tubs, spas, whirlpool tubs

      : remove all water from the fixture if possible:

      see SPA / HOT TUB DRAIN / WINTERIZING PROCEDURE
    • Winterize toilets,

      and remove all toilet water from bowls and toilet tanks. Some winterizing companies pour an anti-freeze mix into building toilets and traps. Some anti-freeze chemicals are toxic and should not be discharged into a septic system. See notes below about use of antifreeze in buildings.
    • Winterize heating boilers, water heater, water softener

      Below on this page we give more detail on draining the water heater, water softener and hot water heating boiler.
    • Winterize well water tanks and pumps:

      need to be completely drained of water - a frozen burst in-building water pump adds an expensive repair later
    • Winterize all building faucets: after water supply has been turned off, open every faucet and leave it open - water left in a faucet can freeze and break it.
    • Open outdoor faucets:

      be sure also to remove any garden hoses on outside faucets. A garden hose left connected to its outdoor hose hook-up point (the hose bibb) can retain water that freezes and damages the outdoor hose bib (faucet) and can lead to burst piping, leaks, and building damage.
    • Winterize the building supply piping:

      above we recommended removing all water from the supply pipes, cutting pipes if necessary.

      To be sure that you have not left water in a hidden corner of supply piping somewhere, if you have not done so, see our tips

      at FIND & FIX WATER PIPE FREEZE-UP POINTS discussed under the "heat-on" winterization notes.

      If your incoming municipal water supply piping is not well below the frost line it may be necessary to find or even install a water shutoff valve closer to the connection of your building's water piping to the municipal water main. Private water supply systems are easier to shut down but also need to be drained.

Old water softener needs to be winterized (C) Daniel Friedman

  1. Turn off and drain the water softener or other water treatment equipment.

    See details at WINTERIZE WATER SOFTENER & WATER TREATMENT EQUIPMENT.

    This article explains water softener shut-down procedure, explain why we use the water softener bypass valve, and how that can reduce the risk of freeze damaged pipes, leaks, and even indoor mold growth.

    A separate article WATER SOFTENER / TREATMENT TURN-ON provides details on returning a shut-down water softener to operation after it has been shut down.

  2. Winterize all building drains:

    if you have not already done so, review our tips

    at DRAIN FREEZE PROTECTION which was discussed under the "heat-on" winterization notes. Further steps include removing traps and use of a non-toxic antifreeze in traps or toilets that cannot easily be removed or emptied of all water.

    Empty or remove building fixture traps; see our note below about use of antifreeze.

    Use of antifreeze to winterize a building: Be careful: unless the anti-freeze is specifically designed for winterizing a building it could be highly toxic (such as automobile antifreeze).

    We do not recommend using toxic antifreeze to winterize a building since later you're moving that contaminant into the public sewer or into soils (and possibly ground water) around a private septic system. Only inside of closed water systems such as a heating boiler do we recommend use of anti-freeze mix in a building.

Water heater showing drain valve (C) Carson Dunlop Associates

This sketch of a gas-fired water heater and its control valves is provided courtesy of Carson Dunlop Associates, a Toronto home inspection, education & report writing tool company [ carsondunlop.com ].

Warning: do not drain a water heater tank before first turning off its energy source: oil, gas, or electricity.

Heating an empty water tank is very dangerous and is likely to quickly destroy the tank or its heating elements.

  1. Drain the hot water tank, well tank, & other building water tanks:

     the hot water tank and drain the water pressure tank and pump itself if a private well and tank system are installed.

    See WATER TANK & PUMP DRAIN & WINTERIZE - how to drain the water tank or well tank and if your water pump is above-ground how to drain the pump itself

    See WATER SOFTENER / TREATMENT TURN OFF - about turning off water softeners and, if heat is to be turned off, drain the softener and any other water treatment equipment.

    See WATER HEATER DRAIN PROCEDURE 
  2. Protect well piping from freezing:

    If your water supply system's piping is not below the frost line your water system should include protection against well or lake water freeze-ups. But sometimes a building's water supply piping that has never frozen before will freeze when no water is run during long periods of freezing weather.

    See SNIFTER & DRAIN BACK VALVES
  3. Shut down & drain or freeze-protect the heating system 

    when all other steps to protect the building have been completed:
    • Winterizing forced warm air heating systems:

      as long as your heating system does not use any water piping (such as a water-to-air system) you can shut off the furnace when leaving a building shut down.
    • Winterizing hot water heating systems:

      Drain the building heating boiler and heating supply and return piping, radiators, baseboards, etc.

      See BOILER DRAIN PROCEDURE

      Opening manual air bleed valves can help drain water out of the heating system piping.

      See AIR BLEEDER VALVE USE STEPS

      Notify your oil heat supplier if you are turning off heat in the building, and remember to notify them again when it is turned back on.

      OR install an anti-freeze mix in the heating boiler and its supply piping.

      See ANTIFREEZE for BOILERS

    • Winterizing steam heating systems:

      drain the heating boiler and condensate lines and condensate pump if a pump or pumping station are used.
    • Winterizing electric heat or warm air furnaces:

      can simply be turned off.

    Watch out: for all oil or gas fired heating equipment (furnaces, boilers, water heaters) we recommend having the heating equipment cleaned before shutting it down - a step that will avoid corrosion, clogs, and trouble when heat is later turned back on.

 

Other Steps to Reduce the Cost of Heating Left On to Avoid Frost Damage

An alternative to turning heat off in the building entirely is to continue your practice of leaving heat on at a low setting (4 C or about 40 F) but take measures to protect the building from damage (possibly allowing a slightly lower heat setting) and to reduce heating cost by finding and fixing drafts, air leaks, or by improving building insulation.

See WINTERIZE - HEAT ON PROCEDURE

...




ADVERTISEMENT





Reader Comments, Questions & Answers About The Article Above

Below you will find questions and answers previously posted on this page at its page bottom reader comment box.

Reader Q&A - also see RECOMMENDED ARTICLES & FAQs

How Long Can You Safely Leave a Building Winterized?

Can a building be left winterized and shut down for several years?

For example, if our building is winterized with RV solution, can it continually be winterized and shut down for several years? Mark George On 2021-12-07

Moderator reply: no time at all, or several years. It depends...

When a building is shut down as we describe on this page, nothing in that technical shut-down is causing direct or active harm to the building or its mechanical systems.

So in that sense it could be left shut down for years. Just below I've written more details on risks and risk managment when leaving a building winterized for long periods.

Sources of Damage to a Winterized Building

Home destroyed by mold following a burst pipe (C) Daniel Friedman at InspectApedia.comBut, and this is a big concern:

Watch out: When a building is left absolutely un-attended, even simply over the course of days, much less months or years, it is at risk of serious damage from the following:

And any of these can leave a building so damaged that it deteriorates so rapidly that even in a few days the damage can be so extensive and so serious that the building has to be gutted before it can be restored.

The photo that I attach here is from an insurance claim investigation I performed for a large insurance company. You can see that the home's interior is badly contaminated by mold - so badly that the home had to be gutted to the raw framing before it could be restored.

The cause: a burst pipe in the basement flooded the building. A burst and un-drained pipe in the basement flooded that space.

The result was a soaking wet building up-state New York that was left un-attended, un-inspected, for three months.

But a water leak can occur even in a well-winterized building if a window breaks and snow blows-in, or if shingles blow off of a roof or a branch punctures a hole in it. Something as un-expected as a bird flying-into and breaking a window can expose a home to significant water entry and damage.

Best solution to long term winterized building: set up building monitoring

How Often to Check on a Winterized Building

The frequency needed for live on-site monitoring visits and inspections depends on the specific building's properties, site, and geographic location, and a risk-assessment by an experienced building professional. Some example questions:

- what is the range of weather conditions like rain, heavy snow fall, high wind? Wildfire? Storm damage? Proximity to large bodies of water or other geographic hazard or damage sources?

A building in Grand Marais Minnesota, close to Lake Superior is more vulnerable to storm damage than a building in downtown Camden, New Jersey.

- what is the risk of malicious mischief? Downtown Camden, New Jersey has a different risk of break-in than downtown Grand Marais, Minnesota.

- what are the condition of the building's roof, windows, doors, flashings

- what is the building's leak history?

- what are the building's materials and how vulnerable are they to water damage

Examples of How Buildings are Managed when Left Shut Down for Years

Example1: In the Hudson Valley of New York State if a home in a residential neighborhood is to be left empty for a month, and if the home has a bulletproof roof (standing seam metal) and no history of water entry, and if we're leaving the home with water turned off and winterized, we'd still want an inspection once a week and if there were a neighbor who would make a walk-around, even just outside or peeping into windows every few days that'd be better.

Example 2: In a small peaceful town in central Mexico, a home in a residential neighborhood and constructed of adobe - materials less-likely to be destroyed by water entry or mold - may need to be monitored for security, break-in's and if water is not turned off, for burst-pipe water damage.

We'd install security cameras and depending on their extent we may want regular inspections for security and damage detection as well.

 

How can we check for foundation damage if we leave our home with the heat off?

Sketch of frost heave damage to a slab in an unheated house (C) Carson Dunlop Associates

We built our home 15 years ago. It is a split level with concrete foundation. When we retired we stated to spend our winters in a warmer climate (we live in N. Ontario). Every winter we have left some heat on the lower level of the house keeping the temperature around 4c.

However with the increase in the cost of oil and our dwindling income buying power, we have been thinking of ways we could cut off both the hydro and the oil heater. Is there any way of us testing what effect this might have on the concrete foundations?

The foundation is covered with a layer of ceramic tiles which we later covered over with a laminate flooring. Thank you. - C.W., northern Ontario

Our sketch (above, courtesy of Carson Dunlop Associates ) shows what happens when a home is left with heat off in a freezing climate.

Reply: Tests for possible frost damage to foundations?

Sketch of the effects of frost on footings, foundations, slabs (C) Carson Dunlop Associates

I don't know of an actual test that you can perform to predict foundation damage if the heat is left off completely in your building, since testing would require creating the actual freezing conditions and would itself risk building damage.

Sketch above, showing evidence of frost heaving is provided courtesy of Carson Dunlop Associates, a Toronto home inspection, education & report writing tool company [ carsondunlop.com ].

At "A Common Source of Vertical Frost Heave - Un-heated Homes" found in our article

VERTICAL MOVEMENT IN FOUNDATIONS
we discuss the problem of foundation damage in un-heated homes.

And at FROST HEAVE / Expansive Soil Cracks in Slabs we provide more details.

Sketch (left, courtesy of Carson Dunlop Associates ) shows upwards as well as horizontal frost pressure on a building and it indicates where cracks and dislocation commonly appear.

Here are some things you can check:

Frost push damage to a foundation (C) Daniel Friedman

Watch out: other factors can still cause slab or foundation damage due to frost.

Can I move a drain valve to protect the pressure regulator valve from freezing?

I have a lake house in northern Ohio. Each winter we turn off heat and drain pipes. This year my pressure regulator cracked.

Here's the setup: Water pipe enters house about 3 ft below ground level into my crawl space. 18" of water pipe and there is a a cut-off valve to turn water off completely from rest of house; 18" later is my pressure regulator.

Above the pressure regulator is another cut-off valve, which I use to drain the cold water lines of the house; since it is above the pressure regulator, it's guaranteed that there will be water in the regulator all winter..

My question is: Can I move the drain valve to below the pressure regulator; would water, not under pressure, drain "backwards" through the regulator, so I can drain all the water and simultaneously drain the pressure regulator? On 2019-02-23 by Bob Worthington

Reply by (mod) -

Bob that should work, as long as the piping is pitched enough that water doesn't simply sit in horizontal piping or regulator or valve.

How do I protect the building's main water shut

Where do I install the water shut off valve for cabin on a slab hooked to main water line. And how to drain? On 2017-12-18 by robert

by (mod) -

Robert

In a freezing climate people like to install the main shutoff inside of the structure as close to the point of water main entry as feasible.

The valve is drained by installing a shutoff that includes a small screw cap outlet intended for draining water out of the valve itself.

The main building piping, if it needs to be drained, should be sloped to drain down to a low point where a stopcock is installed to permit draining.

On most buildings constructed in freezing climates, the entering water line is buried below the frost line. If that's your case, you should not have to freeze- protect the entering water main outside the building.

But if you did have a freeze problem in the outside municipal water line, you'd need to shut off water to the building at the (usually buried) water line shut-off at the street side of the entering water line.

If we drain our plumbing and add antifreeze will our southern Ontario home be safe against all kinds of freeze damage?

Our home is located in southern Ontario & is built over a crawl space. Foundation walls are cement block, below frost line & have blown in insulation.

We go south for the winter & want to turn off the heat. Plumbing will be totally drained & antifreeze. Windows are new.

Will the wooden furniture & floors be ok? On 2016-10-21 by Wally

Reply by (mod) -

Wally,

I'm too scared to bet your house and money on a promise that wood floors in will be okay in a home about which I know almost nothing.

Certainly by proper winterizing as described in this article series you can minimize the risk of damage from leaks or from frozen, burst piping. However in my OPINION, there is always a risk of some cracking or unexpected movement in building materials, especially drywall and sometimes flooring, both wood and tile flooring, when a building is left to below-freezing temperatures.

The best you can do is to properly drain everything. Better would be regular inspections to check that nothing surprising has occurred, like a broken window or a blown-off roof shingle and concomitant leaking. In many areas of southern Ontario there are people living year round in areas where many homes are closed-up for winter and who will for a fee make regular checks on the homes for damage.

Which indoor plumbing valves do I turn OFF to winterize my building?

Which indoor water valves to switch off for winterization? On 2015-11-23 by Wade

Reply by (mod) -

Wade if you are turning heat OFF then you want to OPEN all valves and DRAIN all piping in the building.

If you are leaving the heat ON in an otherwise winterized building, make sure that the heating boiler (if your heat is by hot water) is assured of having a working water supply.

Other supply valves to other parts of the building can be shut off - that reduces the chance of an extensive flood should one of the water supply pipes burst.

For winterizing, Should I drain the outdoor culvert that feeds water to my home in Mexico

I have gravity feed water system,the water comes out of the creek as needed and fills a five foot in diameter culvert which feeds into a two inch water line, I am away for the winter and have drained and put recreational antifreeze in all the drains and toilets in the house, should I drain the culvert reservoir as well?
Thanks so much,
worried in Mexico On 2015-11-22 by Lynda Caton

Reply by (mod) -

Lynda, few places in Mexico suffer from hard freeze conditions - tell me where you are located. In general if you are not leaving water filled pipes or drains that are subject to freezing you should be fine. That is to say water and an open culverts that freezes should not damage system.


Do we need to blow all the water out of our New Jersey Shore Home for Winterizing with heat off?

We have a vacation house on the extreme southern end of the Jersey Shore.

This year we are planning to winterize without heat. (It has a hot-water boiler with baseboard and radiators.)

Are we far enough south that draining all the pipes would be enough, or do we need to blow them out? Thanks On 2015-10-30 by Brad

Reply by (mod) -

Good question, Brad and I'm sorry to have to equivocate; as Mark Cramer says ... it depends.

If the home was constructed to be winterized then all of its pipes would slope down to drain points;

Watcch out: if not the risk is that even when you open lines to drain, enough water may remain in an upwards sloping section to freeze and burst a pipe.

If you hear gurgling at the *end* of your manual drain-effort I'd be worried as that suggests that there's still some water in the water pipes.

by Brad

Dan, that's very helpful.

I have heard gurgling in the past when I've shut the water supply off and opened faucets.

Can you recommend a minimum psi/volume for a compressor to blow the pipes out? Thanks!

Reply by (mod) -

I would not use a PSI above the maximum PSI that your water system can deliver - that should be more than enough to reach the highest water in highest pipe in the building.

I would consider installing a suitable fitting and blowing "down" through the structure from a convenient high point or points.

by Brad

Thanks! I'm heading down this weekend, so I'll give it a try.

Reply by (mod) -

Keep us posted; if you like send me some photos of the set-up via our email found at the page bottom CONTACT link and I may be able to comment further.

DF

Leaving Maine home with heat off for the winter, will my glass jars of food explode?

We are planning to completely shut down our house this winter and have hired a knowledgeable plumber to drain the entire heating and water systems and treat all the traps. My question has to do with food in my pantry.

Will all my glass jars of food explode because of the freezing? And my canned goods - will they all push out damaging the seals? I figure any liquors are safe, but what about wines? We are leaving soon, so a quick reply is greatly appreciated. On 2015-10-27 by Leaving Maine

by (mod) - yes

Leaving: in my OPINION, there is certainly a risk that your canned goods or glass jars, especially those containing liquid (which is most of them) are at serious risk of freezing and bursting in the dead of a cold Main winter.

It's common for January low temperatures in Maine to get down to 0°F, but really it depends on where you live. In Portland the average low gets down to about freezing or 32°F while in Caribou Main where my friend Lance Johnson grew up, winter temperatures often dropped to just 3°F.

The coldest winter temperature recorded in Maine was back in 2009 when up near the Canadian border Main temperatures reached -50°F (-45.6°C). 

Winterizing the heating system: Is it OK to drain un-used heating zone piping, baseboards and radiators?

I have a boiler with 5 heating zones. I am living alone in a big house and do not use the rooms for 3 of the zones. I would like to know if I can drain those zones so they don't freeze and just use the 2 remaining zones for heat.

Thank you - Anon

Reply:

Sure, provided your heating zones are individual piping loops, and that you have control valves at both ends of the un-used heating zones, you can drain them and leave them turned off.

At AIR BLEEDER VALVES we describe air bleed valves found on hot water heating systems. These valves, normally used to purge trapped air that can cause cold radiators or baseboards, can also be opened to make it easier to get water out of the heating system piping when the building is being drained so as to leave heat off completely.

Watch out: to get all of the water out of the piping. It can be difficult to get water out of long horizontal pipe runs without blowing air through the system. For this reason some winterizing companies actually cut the heating pipes, planning to repair them when the building heat is restored. Don't forget to check for cut or burst heating pipes later when de-winterizing the building.

More details about how to winterize the heating system when you are going to leave heat "OFF" are found

at Winterize- Heat Off Procedure.

Also see how WINTERIZE A BUILDING

Winterizing the heating system: Can I put antifreeze in the heating system instead of draining it?

I've read the other parts of your website as you suggested and I hope you don't mind more questions.

Instead of trying to drain the heating zones I don't need, can I just put a non-toxic antifreeze in the whole boiler system? It sounds easier if it is a good solution.
Thanks again!

Reply: use an antifreeze intended for use in heating boilers and piping

Sure, there are specific antifreeze products intended for use in hot water heating systems.

See ANTIFREEZE for BOILERS.

Also see WINTERIZE A BUILDING

Winterizing the heating system: Can I shut off the first radiators in the heating zone without losing heat in the rest of the house?

I have such a system, and only one zone. The thermostat is located in the warmest room in the house. Causing frigidity and numbness of extremities in other areas of the home.

Since the location of the thermostat is also where the first radiator is in the home, can I "shut off" that baseboard radiator, and the next one, without losing heat to the rest of the home? - Jacke

Reply: It depends ... on how heating piping is arranged

Jacke

Whether or not you can shut off or turn down the first two radiators or baseboards in your home to improve heat distribution depends on how the piping is arranged.

If all of the baseboards are piped in series (which is usual for single-zone hot water baseboards) then the input of each baseboard is fed directly from the outlet of the one prior. In that case you can't turn off any baseboard because 1. you have no shutoff valve installed and 2. more important, you'd be shutting off all hot water flow through the system.

If you have radiators, heating convectors, or even some baseboard installations that are piped in parallel, that means that there will be a loop of hot water heating piping that runs through the buildings and that off of that loop, individual risers and returns feed individual radiators or convectors (heating baseboard is not usually piped this way).

In this second case it would be possible to turn off an individual radiator or convector.

So part of my long answer is due to confusion on my part - you use the terms radiator, then baseboard radiator - so I'm not sure what you've got.

Let us know the details - what we learn will assist others.

How do I Add antifreeze for hot water heating piping

How do I add antifreeze to my boilers baseboard heating system - Gene Griswold 7/22/12

Reply:

Gene, please search InspectApedia for

AIR BOUND HEAT SYSTEM REPAIR by PUMP and you will see an article on how a service tech uses a pony pump and fittings to place antifreeze into a hydronic heating system.

Tell me emergency steps to avoid freeze damage - I've just got 3 hours

Help! NE North Carolina, 9-12" snow expected, possible power outages & probable road closures so leaving b4 we CAN'T leave..planning to drain piping but leave heat on...if I don't drain water heater & power goes, how long might it be safe b4 water in heater to freeze & should I leave wh breaker on or off? PLEASE HELP QUICKLY! I HAVE ONLY 3 HRS TIL LEAVE TIME! (Jan 28, 2014) Tracy

Reply:

Review the checklist at WINTERIZE - HEAT ON PROCEDURE

You don't have time to safely use a winterize heat-off procedure.

But at a bare minimum: if you expect power to be off, turn off the building water supply.

That should minimize the extent of leakage that can occur if a supply pipe breaks.

Then on return to the home go through our De-Winterizing checklist - basically you will turn heat on and water on and check for leaks.

 

Should we leave some heat ON to avoid interior cracks

I wonder if it is true that in an unheated home that damage can occur to the walls and floors caused by the extreme cold? WE plan to not waste $$ on heating this year. my smart hubby has done all that is needed to protect the water supply. thank you. (Nov 5, 2014) Deborah Frenette

Reply: if you can leave heat on

Yes Deborah, in extreme cold some building materials may show signs of cracking or movement. I've seen this show up as drywall cracks and on a few occasions fine cracks in ceramic tile floors on a concrete slab.

For this reason, while it is still possible and even reasonable to leave heat off completely (with proper winterizing) for modern construction and where a building is not being left for an extended period such that we are trying to eliminate heating costs completely, I prefer to keep some low heat in the building to try to keep it a bit above freezing.

Deborah said:

Thank you! WE are not using the building (my office, it is attached to our big house) and that is why we are turning off the heat. I will show this to my hubby. The heating bill for an empty building is getting too high. But we do not want to have to repair cracks in the walls!

Reply:

Deborah

You might see no cracking at all - a lot depends on the particular details of construction including materials, connectors, foundation type, basement vs slab, and importantly, water under and around the building.

If the building is more than a decade old you might have some clues by noting whether or not settlemnt or other cracking has ever occurred.

 

Using antifreeze for traps and toilets vs. the worry of environmental contamination

We have a camp that we regularly dump antifreeze into the traps and toilets because it is left unheated. I absolutely hate this, so I've been looking for a way to get around it, or at least minimize how much is needed.

Would love to eliminate some traps if possible, but does anyone have a recommended non-toxic antifreeze, until I get around to finding a solution? I think I'll just buy a bunch of that to keep there. We try to use RV antifreeze as it's supposedly bio-degradable, but we've allowed people to bring their own, and they don't always comply. I hate to be dumping toxins into the ground. (Feb 3, 2015) Crafty said:

Reply:

Crafty there are food grade antifreeze products used in RVs and water systems. Those products should not be harmful. If you let visitors use whatever they bring we've lost control of the problem and may be killing off the septic system to boot.

...

Continue reading at ANTIFREEZE for BOILERS or select a topic from the closely-related articles below, or see the complete ARTICLE INDEX.

Or see these

Building Freeze Protection Articles

Suggested citation for this web page

WINTERIZE - HEAT OFF PROCEDURE at InspectApedia.com - online encyclopedia of building & environmental inspection, testing, diagnosis, repair, & problem prevention advice.

Or see this

INDEX to RELATED ARTICLES: ARTICLE INDEX to BUILDING FREEZE PROTECTION

Or use the SEARCH BOX found below to Ask a Question or Search InspectApedia

Ask a Question or Search InspectApedia

Share this article:

Search the InspectApedia website

Need to make a private comment? Email editor@inspectApedia.com. We welcome email with your website content critique, corrections, suggestions or questions. Email is monitored daily but our workload may prevent an immediate reply. For immediate results, we hope you'll first try asking your question using the search box just above.

Citations & Reviewers

In addition to any citations in the article above, a full list is available on request.

  • "New Electric Heat Tapes Help Prevent Fires," US Consumer Product Safety Commission (CPSC) #00936
  • Mark Cramer Inspection Services Mark Cramer, Tampa Florida, Mr. Cramer is a past president of ASHI, the American Society of Home Inspectors and is a Florida home inspector and home inspection educator. Mr. Cramer serves on the ASHI Home Inspection Standards. Contact Mark Cramer at: 727-595-4211 mark@BestTampaInspector.com
  • John Cranor [Website: /www.house-whisperer.com ] is an ASHI member and a home inspector (The House Whisperer) is located in Glen Allen, VA 23060. He is also a contributor to InspectApedia.com in several technical areas such as plumbing and appliances (dryer vents). Contact Mr. Cranor at 804-873-8534 or by Email: johncranor@verizon.net
  • "Freezeproof Your House," Mike McClintock, Rodale's New Shelter, p. 30, October 1985 (approximate date)
  • "How to Winterize Your Pipes," Mike McClintock, Homeowners How-To Magazine, p. 59-62, Nov-Dec 1979.
  • In addition to citations & references found in this article, see the research citations given at the end of the related articles found at our suggested

    CONTINUE READING or RECOMMENDED ARTICLES.


ADVERTISEMENT