Heating System Circulator Pump Location, Mounting, Wiring
How to install the circulator pump on hot water heating systems.
Here we explain where the circulating pump can or should be mounted on a hot water or hydronic heating boiler.
We show various mounting locations for heating zone circulator pumps.
InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers, products, or services discussed at this website.
- Daniel Friedman, Publisher/Editor/Author - See WHO ARE WE?
Our photo shows the heating zone circulators mounted on the return-side of a Weil McLain heating boiler. If you click to enlarge the photograph you can see the supply and return piping in more detail.
Similarly, the heating boiler piping diagram at page top, courtesy of Raypak® shows the heating system circulator pump assembly (red in our sketch) on the return or inlet side of the heating boiler.
...
We often receive the question "Where should the heating boiler circulator pump be mounted: on the supply or boiler outlet side (the hot side) or on the return or boiler inlet side (the cool side) of the heating piping loop?"
Read the instructions:
The short answer is, mount the circulator and arrange all other piping and controls according to the boiler manufacturer's installation and operating instructions and you won't go wrong.
A sample boiler installation and operation manual that is particularly clear and easy to follow is provided by Raypac® but of course you should obtain and follow the instructions from the maker of your particular boiler maker.
Download a free PDF copy of your circulator pump's IO manual
On the boiler return or inlet side:
most but not all residential heating boilers and probably most commercial heating boilers mount the circulator pump on the return or inlet side of the heating boiler.
This location is a traditional one preferred by some old-school boiler installers and service people, dating from a time when a boiler came from the manufacturer without the circulator pre-installed on piping attached to the unit.
Some heating service technicians (including the web publisher) opine that the cooler heating water temperature on the return side of the boiler means that the circulator pump and its bearings may have a longer life than if installed on the hot side.
Typically heating water returning to a boiler after circulating through a building is about 20 °F. cooler than water leaving the boiler.
The heating boiler piping diagram at page top, courtesy of Raypak® shows the heating system circulator pump assembly (red in our sketch) on the return or inlet side of the heating boiler.
By piping convention the triangle (which we surrounded in red for emphasis) points down, showing the direction of water flow.
On the boiler supply or outlet side:
as we explain just below at Air Exit Tanks, in some heating boiler installations that use an air exit tank to combine the EXPANSION TANK function
with the AIR BLEEDER VALVE or air purge valve function on a heating system, the air exit tank is mounted on the header piping on the supply side of the boiler and the installer may prefer to place the circulator pump below that tank to improve the air purge function of the system.
Air exit tanks are not common on residential heating systems, but the can occur, often accompanied also by water leaks. .
It does not matter which side of the boiler gets the circulator pump?
Ultimately, from a functional viewpoint, it does not matter one bit which side of the heating boiler has the circulator pump mounted, supply side or return side.
That is, the pump will work in either location and will move water through the heating piping loop(s).
That is because in a hydronic heating system the circulator is pushing water around a closed loop: the boiler and boiler piping are filled with water and there is (or should be) no air in the system. (If a hot water system piping or boiler contains more than a few bubbles of air the system is likely to
become AIR BOUND and heat will be lost or missing in all or part of the building.
Watch out: from a service-life viewpoint, however, traditional best practice puts the circulator on the cooler side of the boiler's heating loop where many technicians opine the lower heat gives longer equipment life. We say more about circulator pump location below.
But at least some manufacturers say it doesn't matter.
Here is Taco's position on circulator pump position:
All of the "00" pumps can be used on the supply side or the return. It is preferable to put a circulator on the output of a boiler, but the expansion tank should be between the boiler and the pump section. Most of our "00" iron pumps have a max water temperature of 230ºF.
The max for the bronze is 220ºF. 160ºF is cold. No matter what the water temperature is, the motor housing will be hot. There will be no change in performance or life. - Taco FAQ
Also see these CIRCULATOR PUMP LOCATION FAQS
...
The circulator pump is only a water mover, not a water lifter. The hydronic heating system is relying on the starting water pressure in the heating system to provide enough lift to get hot heating water into baseboards, convectors, or radiators in the upper floors of the building.
Typically the cold starting pressure in a heating system is 12 psi, provided by
the Water Feeder Valve On the boiler.
On tall buildings higher pressures are needed - we provide a chart of pressure reducer/water feeder valve settings
at WATER FEEDER VALVES, HYDRONIC BOILER.
...
Circulator pump position:
Watch out: as we explain at our home page for this topic be sure that the circulator pump is installed as the manufacturer describes. While most circulator pumps can pump heating water in just about any position, there are some positional constraints. For example, quoting from B&G:
The Series LR Circulator can be installed to discharge up or down, horizontally, left or right, but the motor shaft must remain in the horizontal position, the arrow on the body must point in the direction of the flow, the conduit box must be positioned on the top or to the side of the motor housing. - "Instruction Manual, Bell & Gossett Series LR Circulators" [see References]
This article series discusses hot water heating system circulator pumps: how to find, inspect, diagnose, and repair problems with Hot Water Heating System Circulator Pumps or circulator pump relay switches and controls.
See circulator mount position and location recommendations in the installation details at CIRCULATOR PUMPS & RELAYS - home
Also see these CIRCULATOR PUMP MOUNT POSITION FAQs
...
Tip: see the wiring diagrams in the IO manual for your circulator pump; if you don't have the manual, download a free PDF copy
See also CIRCULATOR PUMP RELAYS & OTHER CONTROLS for wiring diagrams for the circulator relay used to turn the pump on or off.
Our reader asked:
Does the TACO baseboard heater system require a 'ground' & where would that be found?
Can the system generate static electricity if the 'ground' is not functioning normally. I'm concerned about excess static electricity & 'hot' de-humidified heat which is very uncomfortably drying to skin.
This system is connected to another heating system (I think) controlled by a wall thermostat.
Temperatures set do not seem to synchronize with thermostat set temperature or temperature output at Honey Well temperature which does not synchronize with actual room temperature, or outside temperature as stimulus for running baseboard at a high temperature.
Do you think there is a major problem? The TACO begins to heat at the 'activator' at very high outer thermostat settings.
(Big white outer ring thermostat around a small HoneyWell supposed room temperature thermostat which is almost always 69-70 degrees.) On 2022-01-11 by Mary
by Inspectapedia Com Moderator - Electrical grounding requirements for heating zone circulators
@Mary,
Apologies but I'm confused by your question.Hot water heating circualtor pumps like those made by Taco do not generate static electricity nor would electrical grounding be included in a circulator pump wiring just to address static electricity.
Watch out: however, as proper electrical grounding of the electrical circuit powering the Taco circulator pump is absolutely required. Here's a quote from an example Taco zone circulator pump that I'll cite below:
[Electrical] Grounding connection is essential for safety and should be connected first. System piping should be grounded separately.
Typically a green ground wire is connected to a green grounding terminal screw in the circulator pump and in the electrical box where it's also connected to the electrical circuit grounding conductor.
The basics of electrical grounding might help you understand what's happening.
See ELECTRICAL GROUND DEFINITIONS
The room thermostat is essentially a call for heat that turns on a circulator pump in what I take to be your case.
Other temperature controls such as on the boiler or at a compensator for outdoor temp control when the boiler runs.Instructions for your TACO circulator that powers your hot water baseboard heating system can be found at
TACO DIAGRAMS, MANUALS, PARTS, CONTACT
Here is a typical manual (we don't know which Taco circulator you have installed).
See also these
...
...
Below you will find questions and answers previously posted on this page at its page bottom reader comment box.
I certainly wouldn't say that the circulator position is inconsequential.
The good science on this is to pump away from the area of no pressure change which is wherever your expansion tank is piped into the system.
If you follow good practice the expansion tank ought to be on the supply side and as close as possible to the hottest available temperatures which is also (and for the same reason) where your air separator should be located.
This also happens to be a great location for your water make up to enter the system to allow any make up water to heat up through the system before it gets to the boiler return side.
The circulator operates on a pressure differential and is sized to deliver
A: the correct amount of flow (GPM) to meet the heat demands of the system and
B: overcome the head losses through the system created by pipe, fittings, valves etc.
If this principle is understood then it makes the most amount of sense to pump away from the expansion handling device as it's job is to regulate pressure in the system which means it controls pressure fluctuations created by expanding and contracting water as it moves through the temperature differentials.
So in short, the pump is designed to create enough pressure on its outlet side to overcome the inevitable pressure losses it will experience throughout the system, so pumping into the area of no pressure change (expansion tank) would defeat the work of the pump. Put simply, always pump away from your expansion tank.
So if you've correctly positioned your expansion device on the supply side of the system then your circulator will always be on the supply side as well, albeit downstream.
There are several other factors to consider in the myriad of piping possibilities but generally speaking if you follow this rule then you won't go wrong. On 2020-01-30 by Marty -
Reply by (mod) - importance of circulator pump location & position - on the return side of the heating zone loop
Very informative, Marty, thank you.
Standard good practice among heating techs is to install the circulator pump on the return side of the loop where cooler temperatures can extend its life.
My burnham oil boiler has the circulator pump on the return pipe with the arrow and flow going toward the boiler will it work OK ? On 2019-10-18 by dennis
by (mod) - Yes
That's the correct installation position
Hello -
I recently purchased a house with an outside hydronic boiler which I guess heats my faucet/shower water as well as my heating system via hot water radiators.
As of right now - there's a noise that sounds like a humming/whistling noise which every 5 minutes.
It usually lasts about 1 or 2 minutes and then after several minutes I hear it again.
My circulating pump is inside one of my kitchen cabinets and its hard to tell if its the pump or if the boiler unit has its own pump inside the housing.
The boiler I have is a Raypak (raytherm) which has a sticker that says it heats up to 108,800 BTUH.
I believe the model is a the 133 size boiler from what I can tell from the internet but I'm not 100%.
Can someone please help me determine what this noise might be? and about how much will a plumber cost to replace the pump. if its truly that piece thats defective? On 2012-11-06 Anonymous
Reply by (mod) -
Noise from Raypak
First: listen right at the circulator pump. If it's noisy you should hear it right at the pump, though
Otherwise, rather than further wild guessing, I suggest tracking down the noise to the offending part. Use someone with good hearing, notice when equipment is turning on and off and just what's running; try a mechanic's stethoscope.
Details about noise track down procedures begin at NOISE / SOUND DIAGNOSIS & CURE
if so what can be done to fix this problem?
i have brown water coming from the water heater which has a circulation pump on it. i have opened all related facuet and let them run for long periods of time but doesn't go away. is this a circulation pump issue? On 2011-07-13 by harley
Reply by (mod) -
Harley:
First we need to understand what setup you have. Is this an indirect-fired water heater?If so then the circulator pump would be cycling heating boiler water through a coil that is heating physically separate water heater water and you'd only get brown dirty water (from the heating system where that is normal) leaking into the domestic hot water (in the water heater) if there was a leak in that coil.
(Usually leaks go the other way - from the higher pressure water heater water into the lower pressure heating system water).
If your system is using a circulator pump to provide "instant" hot water at all plumbing fixtures by constant cycling of water heater hot water through the building piping loop, then if your outcoming hot water is dirty you need to drain the water tank, probably clean it, and probably replace a deteriorated sacrificial anode.
...
Continue reading at CIRCULATOR PUMP MOUNT POSITION or select a topic from the closely-related articles below, or see the complete ARTICLE INDEX.
Or see these
CIRCULATOR PUMP MOUNT LOCATIONS at InspectApedia.com - online encyclopedia of building & environmental inspection, testing, diagnosis, repair, & problem prevention advice.
Or see this
Or use the SEARCH BOX found below to Ask a Question or Search InspectApedia
Search the InspectApedia website
Need to make a private comment? Email editor@inspectApedia.com. We welcome email with your website content critique, corrections, suggestions or questions. Email is monitored daily but our workload may prevent an immediate reply. For immediate results, we hope you'll first try asking your question using the search box just above.
In addition to any citations in the article above, a full list is available on request.