InspectAPedia®

Proper eletrical outlet location in bathrooms (C) Carson Dunlop AssociatesElectrical Outlet Locations
Where should electrical receptacles be located in buildings? Electrical receptacle height and clearance restrictions

InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers, products, or services discussed at this website.


Locating electrical receptacles: where should electrical receptacles (outlets or wall plugs) be located?

This article series describes how to choose, locate, and wire an electrical receptacle in a home.

Electrical receptacles (also called electrical outlets or "plugs" or "sockets") are simple devices that are easy to install, but there are details to get right if you want to be safe.

We also provide a MASTER INDEX to this topic, or you can try the page top or bottom SEARCH BOX as a quick way to find information you need.

Recommended Wall & Countertop Locations for Electrical Receptacles (Outlets)

The Six Foot Rule for Receptacles along Interior Walls

A basic guideline for locating and spacing electrical receptacles in a residential building is that at no spot along the length of any building interior wall should the distance to the nearest receptacle be more than six feet. This means you are placing wall receptacles at twelve-foot intervals or less; some wall designs and room layouts will of course reduce this number.

TheTwo-Foot / Four-Foot Rule for Receptacles along a Kitchen Counter

Question: space between an electrical receptacle and the stove top

2018/02/14 Laura said:

How much wall space do I need between an electric stove and an electrical outlet in kitchen?

This question and answer about kitchen electrical outlets were posted originally at ELECTRICAL WIRE CLEARANCE DISTANCES

Reply: reidential kitchen electrical outlet requirements

Laura

Using the U.S. National Electrical Code (NEC) as a model, for a residential kitchen we want to have two separate 20A circuits supplying GFCI-protected electrical receptacles (aside from specialty circuits such as for refrigerator, dishwasher, electric oven or range) and separate from the microwave circuit (20A), lighting circuit and separate (non-gfci) garbage disposer if installed.

Receptacles (electrical outlets in a kitchen) should be

Watch out: you should never install an electrical receptacle over the stove or range top itself. The hazard is that the appliance cord plugged into such a receptacle is likely to pass over a stove top burner.

ELECTRICAL RECEPTACLE HEIGHT & CLEARANCES gives details about electrical receptacle heights above floor and clearance distances from other building components or features.

Clearance Spacing Rules for Electrical Receptacles

In addition to the fundamental requirement that no space along a wall is more than six feet from an electrical receptacle, an electrical outlet must be properly located on the wall, according to local electrical codes and the National Electrical Code.

Examples of proper electrical outlet locations are shown in our two sketches below, courtesy of Carson Dunlop and in the following list of electrical outlet location requirements:

Proper eletrical outlet location in bathrooms (C) Carson Dunlop Associates Proper eletrical outlet location over heating baseboards (C) Carson Dunlop Associates

Height Rules for Electrical Receptacles

Guides for height & spacing clearances for electrical receptacles are given at ELECTRICAL RECEPTACLE HEIGHT & CLEARANCES

Electrical Receptacle Wiring Clearances from Ducts & Pipes

We also don't route wires too close to places where the wires can be damaged by heat from a heating appliance or chimney, flooded, etc. as you'll see depicted in the two Carson Dunlop sketches below. Thanks to Steve for pointing out erroneous illustration link details, now fixed.

Details are at ELECTRICAL WIRE CLEARANCE FROM DUCTS & PIPES - separate article

Proper routing and support of electrical wire (C) Carson Dunlop Associates

[Click to enlarge any image]

Question: how to wire up a pair of receptacles in one electrical box

Quad plex electrical receptacle wiring (C) Daniel FriedmanI would like to wire 2 single plugins to one live wire..how do i do that? - Channing

Reply:

Channing, re Hooking up a Pair of Receptacles in One Electrical Box:

If your two plugins (two electrical receptacles) are located in the same electrical box (we call this a "quad" electrical receptacle installation since each individual receptacle provides connections for two wall plugs), you'll want to wire the hot and neutral to one pair of screws on the first receptacle, and use short black and white jumper wires to connect the the proper terminals on the first receptacle to the second one in the same box.

That's a perfectly acceptable use of the second pair of screw terminals you see on the receptacles.

The ground wire can be continuous, tying the two ground screws on the receptacles together and onwards to the circuit ground.

However a better practice when wiring up a quad-plex of electrical receptacles is to place left and right or upper and lower receptacles on separate electrical circuits - thus reducing the chances of overloading the circuit when many things are connected simultaneously. There are two approaches: you can wire the left and right duplex receptacles each to different individual electrical circuits, or you can wire the upper and lower half of the pair of duplex receptacles to different electrical circuits.

Wiring a Split Receptacle to Two Different Electrical Circuits

Electrical receptacle split receptacle wiring (C) Daniel FriedmanIf you choose to wire the upper and lower duplex receptacle openings to different circuits, we call this the "split receptacle" wiring method, because we are splitting the individual duplex receptacle upper and lower connectors onto two different circuits.

Our photo (left) shows an electrical receptacle that is being wired to a single circuit. The white neutral wire is connected to the silver screw (left side of our photo).

If we were wiring this electrical "outlet" as a split receptacle, we'd want to feed the upper and lower halves of the device from two different electrical circuits.

To do so we'd have to break away the "breakaway" connecting tab pointed to by our orange arrow.

Daisy Chaining Receptacles in Separate Electrical Boxes

If your two receptacles are in different locations and thus in different electrical boxes, your circuit that wires the second or "downstream" receptacle can be powered by those same extra terminal screws on the first or "upstream" receptacle. You'll need to run a wire from the first receptacle through the wall into the second electrical box of course.

Wiring Electrical Receptacles on a Single Circuit In Parallel

In some jurisdictions electricians to not "daisy chain" receptacles in the same box together by using the second pair of screws on each one. Rather the circuit enters the box and using twist-on connectors, short pig-tail wires are connected to each receptacle at the proper screws. This approach requires a larger electrical box as it will contain more connections, connectors, and so needs more room.

Question: how many electrical receptacles are allowed on a 20-amp circuit? How many receptacles on a 15-amp circuit?

How many receptacles can be wired To one 20 amp circuit No. 12. Wire - John K.

Reply:

20 Amp electrical outlet © D Friedman at InspectApedia.com John K:

Our photo (left) shows a 20-Amp electrical receptacle - you can recognize it by that horizontal opening that makes the left-hand slot look like the letter "T" on its side.

In general, the Electrical Code [NEC] allows

Our photo (left) illustrates an electrical receptacle intended for use on a 20-Amp circuit.

Notice that extra horizontal slot? You won't see that on a 15-Amp electrical receptacle.

...


Continue reading at NAIL STOPS to PROTECT WIRES or select a topic from closely-related articles below, or see our complete INDEX to RELATED ARTICLES below.

Or see ELECTRICAL RECEPTACLE LOCATION FAQs questions & answers posted originally at this article

Or see these

Articles on Electrical Receptacle Wiring

Suggested citation for this web page

ELECTRICAL RECEPTACLE LOCATIONS at InspectApedia.com - online encyclopedia of building & environmental inspection, testing, diagnosis, repair, & problem prevention advice.

INDEX to RELATED ARTICLES: ARTICLE INDEX to ELECTRICAL INSPECTION & TESTING

Or use the SEARCH BOX found below to Ask a Question or Search InspectApedia


...

Frequently Asked Questions (FAQs)

Click to Show or Hide FAQs

Ask a Question or Search InspectApedia

Questions & answers or comments about how to install and wire electrical outlets or receptacles in buildings.

Try the search box just below, or if you prefer, post a question or comment in the Comments box below and we will respond promptly.

Search the InspectApedia website

HTML Comment Box is loading comments...

Technical Reviewers & References

Click to Show or Hide Citations & References

Publisher's Google+ Page by Daniel Friedman