InspectAPedia.com InspectAPedia®
Google
InspectAPedia
 

Free Encyclopedia of Building & Environmental Inspection, Testing, Diagnosis, Repair

Ask a Question or Search InspectAPedia

  • HOME
  • AIR CONDITIONING
  • ELECTRICAL
  • EXTERIORS
  • HEATING
  • HOME INSPECTION
  • INTERIORS
  • PLUMBING
  • ROOFING
  • SEPTIC SYSTEMS
  • STRUCTURE
  • WATER SUPPLY
  • ENERGY SAVINGS
  • ENVIRONMENT
  • INDOOR AIR IAQ
  • INSULATION
  • MOLD INSPECT TEST REMOVE
  • NOISE
  • ODORS
  • SOLAR ENERGY
  • VENTILATION
  • EXPERTS DIRECTORY
  • CONTACT US



Mobile Phone/PDA website viewMobile View
AIR CONDITIONING & HEAT PUMP SYSTEMS

A/C - HEAT PUMP CONTROLS & SWITCHES
A/C DATA TAGS
A/C - HEAT PUMP CRITICAL DEFECTS
A/C DIAGNOSTIC FAQs
A/C REFRIGERANTS
A/C TYPES, ENERGY SOURCE
AGE of AIR CONDITIONERS & HEAT PUMPS

AIR CONDITIONER BTU CHART
AIR CONDITIONER COMPONENT PARTS
AIR CONDITIONER TYPES, ENERGY SOURCES
AIR CONDITIONER NOT WORKING
AIR FILTERS for HVAC SYSTEMS
AIR HANDLER / BLOWER UNITS
APPLIANCE EFFICIENCY RATINGS

BACKUP HEAT for HEAT PUMPS
BLOWER DOORS & AIR INFILTRATION
BLOWER FAN CONTINUOUS OPERATION
BLOWER FAN OPERATION & TESTING
BOOKSTORE - Air Conditioning "How To" Books

CAPACITORS for HARD STARTING MOTORS
CAPILLARY TUBES
CHINESE DRYWALL HAZARDS
CIRCUIT BREAKER SIZE for A/C or HEAT PUMP
CLEANING & Legionella BACTERIA
CHINESE DRYWALL HAZARDS
COMBUSTION GASES & PARTICLE HAZARDS
CONDENSATE HANDLING, A/C
CONDENSATION or SWEATING PIPES, TANKS
COMPRESSOR & CONDENSING COIL, A/C
CONDENSATE HANDLING, A/C
CONDENSATION or SWEATING PIPES, TANKS
COOL OFF HEAT Thermostat Switch
COOLING CAPACITY, RATED
COOLING COIL or EVAPORATOR COIL
COOLING LOAD REDUCTION by ROOF VENTS
COMBUSTION GASES & PARTICLE HAZARDS
CONDENSATE HANDLING, A/C
CONDENSATION or SWEATING PIPES, TANKS

DATA TAGS on AIR CONDITIONERS
DEFINITION of Heating & Cooling Terms

DEHUMIDIFICATION PROBLEMS
DEW POINT CALCULATION for WALLS
DEW POINT TABLE - CONDENSATION POINT GUIDE

DIAGNOSE & FIX AIR CONDITIONER / HEAT PUMP
DUCT SYSTEM & DUCT DEFECTS
DUCTS - Asbestos
DUCT INSULATION, Asbestos Paper
DUCT INSULATION for SOUNDPROOFING
DUCT SYSTEM NOISES
DUCTS, Asbestos Transite Pipe
DUST CONTAMINATION FROM HVAC?

EDUCATION, HVAC SCHOOLS
ELECTRIC MOTOR DIAGNOSTIC GUIDE
ELECTRIC MOTOR OVERLOAD RESET SWITCH
ELECTRICAL POWER SWITCH FOR HEAT
EVAPORATIVE COOLING SYSTEMS
EVAPORATOR COIL or COOLING COIL
EXPANSION VALVES, REFRIGERANT

FAN, AIR HANDLER BLOWER UNIT
FAN AUTO ON Thermostat Switch
FAN, COMPRESSOR/CONDENSER UNIT
FAN CONVECTOR HEATERS - HYDRONIC COILS
FAN LIMIT SWITCH
FAN NOISES
FURNACES WARM AIR HEATING SYSTEMS

GAS EXPOSURE EFFECTS, TOXIC
GAS DETECTION & MEASUREMENT
GAUGE, REFRIGERATION PRESSURE TEST

HEAT LOSS (or GAIN) in buildings
HEAT PUMPS
HUMIDITY LEVEL TARGET

INDOOR AIR QUALITY IMPROVEMENT GUIDE
INSPECTION LIMITATIONS
INSPECTION CHECKLIST - OUTDOOR UNIT
LOST COOLING CAPACITY

MANUALS & PARTS GUIDES - HVAC
MOTOR OVERLOAD RESET SWITCH

NOISE AIR CONDITIONER / HEAT PUMP
NOISE / SOUND DIAGNOSIS & CURE

OPERATING COST
OPERATING DEFECTS
OPERATING TEMPERATURES

PORTABLE ROOM AIR CONDITIONERS
PRESSURE READINGS, REFRIGERANT

REPAIR GUIDE, AIR CONDITIONERS / HEAT PUMPS
REPAIR & DIAGNOSTIC FAQs for A/C
REFRIGERANTS
  GAUGE, REFRIGERATION PRESSURE TEST
  REFRIGERANT CHARGING PROCEDURE
  REFRIGERANT DRIERS & FILTERS
  REFRIGERANT LEAK DETECTION
  REFRIGERANT LEAK REPAIR
  REFRIGERANT METERING DEVICES TEVs
  REFRIGERANT METERING CAPILLARY TUBES
  REFRIGERANT PIPING & DISTANCES
  REFRIGERANT PRESSURE READINGS
RETROFIT SIZING for A/C or HEAT PUMPS

SEER RATINGS & OTHER DEFINITIONS
SOLAR ENERGY SYSTEMS
SPLIT SYSTEM AIR CONDITIONERS & HEAT PUMPS
SWAMP COOLERS
SYSTEM OPERATION

THERMOSTATS, HEATING / COOLING
THERMOSTATIC EXPANSION VALVES

WATER COOLED AIR CONDITIONERS

More Information

Air conditioner refrigerant lines (C) Daniel Friedman Air Conditioning Refrigerant Line Installation Procedure, Specifications, and Mistakes to Avoid
InspectAPedia®  -      

  • Air conditioning refrigerant line defects
  • Refrigerant line insulation requirements & common temperatures
  • Refrigerant line mounting requirements & mechanical damage risks
  • Air conditioning refrigerant piping distances and diameters required
  • Allowable distances between air conditioning compressor and air handler
  • Why & where you will see refrigerant line brazing or soldered together at the Low Pressure & High Pressure lines
  • Questions & Answers about HVAC system refrigerant piping or tubing routing, connections, materials, charging

This air conditioning repair article discusses the refrigeration piping requirements, insulation, mechanical fastening, and allowable distances as well as errors in air conditioning refrigerant piping installations that risk future refrigerant leaks or malfunction in the cooling equipment.

InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers nor with topics or services discussed at this website.

© Copyright 2012 InspectAPedia.com, All Rights Reserved. Information Accuracy & Bias Pledge is at below-left. Use page top links to major topics or use links at the left of each page to navigate within topics and documents at this website. Green links show where you are in a document series or at this website.

Air Conditioner Refrigerant Line Installation Requirements & Refrigerant Line Defects

Refrigerant line leak points (C) Carson Dunlop Assoc.

Also see REFRIGERANT LEAK DETECTION and INSTALLATION ERRORS, COMPRESSORS. Contact us to suggest text changes and additions and, if you wish, to receive online listing and credit for that contribution.

According to Carson Dunlop Associates Home Reference Book,

The copper refrigerant lines move the refrigerant between the condenser and the evaporator. Refrigerant lines are normally arranged in pairs, with the larger diameter line carrying gas and the smaller one carrying liquid. The larger refrigerant pipe containing cool gas is typically insulated to prevent condensation and increase efficiency.

The most common problems with refrigerant lines are mechanical damage, leakage and corrosion. Refrigerant lines are frequently damaged where they pass through the house wall. Leaking refrigerant lines are usually identified by oil deposits on the line.

Illustration, left, courtesy of Carson Dunlop Associates.

Refrigerant Line Mounting Requirements

Absence of slack in the air conditioning system coolant lines at the compressor units can cause leaks: should the compressor move, perhaps because its supporting pads settle, there will be likely leaks at these lines. You should review this question with your HVAC service person. This item may be deferred until next maintenance or service.

Our refrigerant line photo (below left) shows worn insulation and a crimped condensate drain line. Our photo of a pair of outside compressor units (below right) shows what looks like a neat installation, but the mounting of the refrigerant piping against the building wall and absence of slack is just asking for a refrigerant leak in these systems.

Refrigerant line fastener (C) Daniel Friedman Refrigerant line slack (C) Daniel Friedman

According to McQuay International, a large producer of refrigeration equipment,

Refrigerant lines need to be securely installed to minimize vibration that causes noise and damages piping. Reciprocating compressors, in particular, cause vibration. Steel braided flexible refrigerant lines (a must for spring isolated reciprocating compressors) minimize this vibration. ...

Refrigerant lines that rub against solid objects wear holes through copper and create a leak. For this reason, when refrigerant lines pass through walls, the line should pass through sleeved openings in such a manner that the lines do not touch. There are several commercially available pipe clamping systems that allow pipes to be held rigid without causing damage to them. Most include some form of rubber grommet around the pipe, which is then secured within a bracket. Many building codes specify minimum support spacing. Piping should also be protected from mechanical damage. Where piping is exposed to possible damage, the lines should be routed out of the way or be protected in some form of chase.

Burying refrigerant lines should be avoided.

Refrigerant Line Insulation & Nail Protection Requirements

Use Nail and Screw Plates to Protect Refrigerant Tubing

Refrigerant piping routing (C) D FriedmanWhere refrigerant piping (or condensate drains) are routed through building walls, floors, or ceilings, if the holes drilled through framing members place the tubing too close to an interior or exterior wall surface, there is a risk that a drywall nail or screw, or an exterior siding nail will puncture the refrigerant lines.

We protect against this hazard by nailing standard nail plates across the face of each stud, joist, or rafter where this risk is present.

Our refrigerant line photo (left) shows liberal use of these nail plates on the interior face of wall studs where the routing of refrigerant lines was close to the interior wall surface.

Because the builder had not yet completed the exterior siding (just the OSB sheathing was in place), we also had to watch out for use of long siding nails that might puncture one of these lines.

Outside the building in areas where this was a concern, because the sheathing was already in place, we simply marked "no-nail" areas on the OSB.

Protect Refrigerant Lines & Their Insulation Outdoors

Manufacturers also recommend wrapping the insulated refrigerant lines exposed to outdoor weather, using an appropriate weatherproof tape.

Effects of Missing, Damaged, Crimped Refrigerant Line Insulation

Refrigerant line insulation (C) Daniel FriedmanMissing or damaged refrigerant line insulation insulation on the refrigerant lines, particularly on the larger suction line, will cause condensation and drips from the lines in humid areas.

We have seen very costly building damage where lines were not properly insulated indoors: condensate drips wet gypsum board walls, leading to a costly mold remediation project. Missing refrigerant line insulation also probably increases system operating cost.

According to McQuay International, a large producer of refrigeration equipment,

Suction lines are cold – 40°F (4.4°C) SST – and cause condensation, even in conditioned spaces. In addition, any heat that enters the refrigerant adds to the superheat and reduces system efficiency. For these reasons, suction lines should be insulated with a vapor proof insulation. This is a requirement of many building codes. Rubratex is the most common form of refrigerant line insulation.

Liquid lines generally are insulated. They are warm to hot (110°F (43.3°C) for air-cooled). If liquid lines pass through a space that is warmer than the refrigerant (i.e. the roof of a building at roof level), or if they could be considered hot enough to pose a safety risk, then insulation should be added.

Discharge lines are generally uninsulated. They may be very hot, in excess of 150°F (66°C), so insulation may be warranted as a safety consideration, or if the heat loss from the discharge gas line would be considered objectionable to the space.

Hot gas bypass lines should be insulated, especially if the runs are long or if the piping is exposed to cold temperatures.

Crimped Refrigerant Line or Tubing Insulation

Air conditioner manufacturers include installation instructions with each unit. It's worth taking the time to read all of those details as the manufacturer has the same desire for a successful and trouble-free installation as the home or business owner or the HVAC installer. Among these instruction details you'll read how the manufacturer wants the refrigeration lines installed, including the following:

When installing insulation over the refrigerant tubing, do not over-tighten the foam insulation (typically held in place with plastic ties or tape). Crimping the insulation along its refrigerant tubing pathway creates points of less and possibly inadequate insulation.

Missing or inadequate refrigerant piping insulation means a system that operates at a lower efficiency and it risks condensate drips into problem areas such as wall or ceiling cavities - a mold risk.

Air Conditioner Refrigerant Line Diameters & Lengths vs. Distance Between Compressor/Condenser and Air Handler/Evaporator Coil

Question: How Far Apart Can I Separate the Air Conditioner Compressor/Condenser from the Air Handler/Evaporator Unit?

I live in a townhouse and have a split air conditioner system. The compressor is currently on the roof, but it may need to be relocated to ground level. The other unit is in the attic. How far away from the house can the compressor be (maximum, not minimum). I do not want to put the unit on my terrace, which is next to the house, because it would diminish our ability to use the terrace due to noise, etc. Could the unit be located approximately 37 feet away from the house without affecting it's function? This would place it at the back of the garden, either behind a fence or obscured by a shrub. - Anon.

Answer: Almost any A/C equipment separation distance can be made to work, but the installer will need to take a look at refrigerant piping diameter guides

Moving an air conditioner compressor to a distance of about 40 feet from a building wont' prevent it from working, but the installer might need to adjust the diameter of the refrigerant lines to be sure that the equipment is working at 100% of its capacity.

A more careful answer to your question is not so much that there is a specific distance limit between the A/C compressor and A/C evaporator coil so much as a need to get the size (diameter) of refrigerant lines and amount of refrigerant charge correct - that is, if we exceed some distance, probably like 100', we may need to increase the refrigerant piping diameter as well as the refrigerant charge for the system to work properly.

There is a more subtle technical concern with refrigerant velocity in the line. If the velocity is too low, refrigerant oil may not be properly distributed in the system. In addition to total length of refrigerant piping, the number of elbows, bends, fittings, also affect flow and have to be taken into account.

Each A/C manufacturer offers their installer technicians equipment installation instructions that include how to size refrigerant piping properly. The instructions may include complex calculations, or simply a chart of separation distances between the outside compressor/condenser unit and the inside air handler/evaporator unit.

If there is not a "table" of distances and pipe diameters for a specific air conditioning system, then the manufacturer will expect the installer whose layout is different from the usual distances to make some measurements on the system and to adjust it accordingly.

Diameter of Refrigerant Piping & Tubing

In a nutshell, the size in diameter of the refrigerant suction and supply piping needs to be determined by the installer based on the distances involved, the equipment tonnage, changes in elevation between compressor and evaporator coil, the number and type of fittings in the refrigerant piping system, ambient operating temperature ranges, and other cooling equipment specifications given by the manufacturer.

If the installer places the equipment far enough apart that s/he should have used a larger (or smaller) diameter piping system, the A/C system will still work, but its cooling capacity may be reduced.

A cooling line that is too big in diameter OR too small in diameter can cause the equipment not to work properly or efficiently.

Copper Tubing ID versus OD: internal diameter versus outside diameter

It's easy to get confused about pipe sizes or diameters when discussing flexible copper tubing. Refrigeration technicians often refer to flexible copper refrigerant tubing by its outside diameter or "OD" while plumbers usually refer to any piping by its inside diameter or "ID".

A 1/4" OD (outside diameter) flexible copper refrigerant line actually has about a 1/8" ID (inside diameter). So when you are measuring or ordering piping, make sure you and your supplier are talking about the same size by using "OD" or "ID" in your measurements.

Storage of Refrigerant Piping or Tubing

Unused refrigerant piping or tubing should be stored with its ends capped to keep dirt and moisture out of the piping.

Refrigerant Piping or Tubing Connections

Most HVAC systems that we have inspected and all that we have installed or repaired used soldered or brazed connections for copper refrigerant piping on both suction and high pressure lines. Some manufacturers, codes, and procedures also allow flare fittings - something we have used on some LP gas lines but in our opinion flare fittings are more leak prone than soldered connections. (We do not use compression fittings on refrigeration and air conditioning systems.)

Soldering or Brazing Copper Refrigerant Tubing or Capillary Tube Connections

Swaging copper tubing procedure (C) D FriedmanIn the opinion of some HVAC instructors, half of the leaks found in refrigerant piping are traced to defective soldered or flared connections so it's important to make these connections as close to perfect as you can during system installation or repair. [1]

Sections of flexible copper tubing to be soldered or brazed together are connected using a procedure called swaging.

A swaging tool (see our sketch at left) is inserted into the end of the copper tubing through a lfare block. The swaging tool is carefully hammered until it has expanded the copper tubing internal diameter (ID) sufficiently to permit it to slip over the connecting copper tubing section.

Guide to Soldering Materials & Temperatures for Refrigerant Piping & Tubing

This article describes three different temperature ranges for soldering copper piping or tubing along with some general copper pipe or tubing soldering advice.

General Soldering Advice for Copper Piping or Tubing

  • Clean oxidation off of the copper tubing inside and outside before soldering, using emery cloth or wire brushes. Meticulous cleaning is necessary to get reliable solder connections and leakproof joints.
  • Use anti-corrosion soldering paste. This prevents oxidation of the copper surface when you heat the tubing or piping in the course of soldering the materials together.
  • Don't use more heat than necessary to make a soldering connection. Too much heat boils away the flux and oxidizes the copper. If you see this happening you'll have to stop, cool the copper tubing or piping, and start over at the cleaning step.

Temperature Ranges of Copper Soldering

  • 300 degF copper soldering: uses a 50:50 solder that requires little heat. The solder flows like water - it's easy. (50:50 lead solder is no longer used in plumbing applications out of concern for lead in water supplies).
  • 500 degF copper soldering: using 95:5 solder to get more heat to get the solder to flow.
  • 1150 degF copper soldering: silver solder, use on big refrigeration systems, use when there are wide temperature variations (to withstand the expansion/contraction); can cause flaking inside the copper line, so in refrigeration applications, good practice fils the lines with nitrogen and flush them with nitrogen too while soldering; silver soldering is also used when there are variations between the two metals joined, e.g. steel to copper. The joint has to be red hot. Watch out to avoid using this process too close to 95-5 solder joints or they will melt.

Capillary tube soldering advice (C) D Friedman

The copper tubing ends to be connected are cleaned, sanded, treated with soldering or brazing flux, and soldered or brazed.

When a capillary tube is to be soldered take are not to place soldering flux too far into the joint or the solder may flow over and close the end of the capillary tube. (see our sketch).

Advice for Making Flare Fitting Connections with Copper Tubing or Piping

Flare fitting (C) D Friedman

  • When you cut copper piping or tubing using a saw (rare) or a copper pipe or tubing cutter (the usual practice) the cutting wheel may leave a lip of copper on the inside of the copper pipe or tubing.

    For soldering or flaring copper piping, you will want to remove this lip (to be sure that the full diameter of the pipe is available to avoid a flow restriction, and when making a flare fitting in particular, be sure also to remove burrs in the copper pipe or tubing end before attempting to create the flare end of the tubing using your flaring tool. Plumbing and HVAC supplies sell special reaming tools used for this purpose. Don't over-do the reaming or you may create an over-thinned tapered edge of your flare that will crack during expansion, but be sure that all burrs are removed.
  • Put the flare nut onto the tubing before making the flare - you'll only make this mistake once.
  • For 1/4" OD tubing, the end of the tube extends about 1/8" above the flaring block at the start of the flaring procedure.
  • The flare that you create should fit snugly inside of the nut, extending to fully cover the tapered seat inside the nut, and it should exactly cover the face of the flare fitting.
  • Also see "Identifying Sources of Leaks at Brass Flare Fittings ..." found at Gas Leak Detection where we illustrate examples of causes of leaks in flare fitting connections

More Details about Refrigerant Piping Sizing and Run Length: refrigerant pressure drop and temperature loss

For example, measuring the refrigerant gas line pressure drop (or temperature change) on the suction line (return to the compressor) will show (typically) that a 4 degree temperature loss through the refrigerant line will result in an 8 percent loss in cooling capacity of the system.

Or on the discharge line (output from the compressor) will show (typically) that a 4 degree temperature loss through the refrigerant line will result in a 2 percent percent loss in cooling capacity of the system.

So it's not that the air conditioner won't work at all if the compressor/condenser is located at an unusual distance from the air handler/evaporator coil, it's more that it may lose some capacity and have to work harder - meaning higher electrical bills and in extreme cases, shorter equipment life.

Some air conditioner manufacturers such as McQuay provide a refrigeration piping guide that gives complete, detailed guidance and charts on refrigerant line sizing (diameter) as a function of length of run.

Technical Note on Refrigerant Piping: HVAC economizer detail using refrigerant line brazing or soldering together of the Low Pressure & High Pressure lines for deliberate heat exchange

In some refrigeration system designs, a low-temperature (heat laden) vapor line (suction line) is soldered alongside the high-temperature, high-pressure liquid refrigerant line. This conjoining of the two refrigerant lines is likely to be done where the vapor line is entering the compressor/condenser unit.

The purpose of this line-to-line soldering is to act as a heat exchanger, to reduce the temperature of the liquid refrigerant that is going to enter the metering device (TEV or cap tube), gaining some benefit to system operation - we want a lower refrigerant temperature at the point where the liquid refrigerant is about to be metered or released into the cooling coil (evaporator coil in the air handler).

A second benefit of this heat exchange is that in the larger suction line entering the compressor, the refrigerant enters at a higher temperature, easing the compressor's job of compressing and raising the refrigerant temperature on the condenser side, so that the refrigerant is (by being hotter) better able to transfer heat to ambient air in the environment around the condensing coil.

Other forms of air conditioner and heat pump economizers and economizer tricks of the trade are discussed at AIR CONDITIONING HEAT PUMP SAVINGS

Frequently Asked Questions (FAQs) about HVAC system refrigerant piping or tubing routing, connections, materials, charging

Question: can I use standard 3/4" diameter copper piping instead of flexible 3/4" copper tubing for the refrigerant suction line?

Type M Copper (C) D FriedmanI am running the piping for my central air unit. I will have a qualified HVAC technician make the connections.

I have no problem bending the smaller 3/8 tubing. However, I am having a difficult time installing the ¾ line without crimping the pipe.

My question is can I use standard ¾ inch cooper piping instead of the ¾ in tubing? I’m good at plumbing.

I could then neatly run the pipe to within a foot of the condenser and coil and have the technician complete the install. Thanks for your help and the great website. Steve

Reply: Yes but ...

Certainly I've seen [DJF] commercial HVAC installations where larger diameter soldered-joint copper piping was used for refrigeration liquid or gas movement - there is no conceptual problem with that approach but

  • more solder joints rather than flexible tubing bends increases the risk of a leaky joint, so choice of high quality copper (type M?) and joint soldering or brazing workmanship and proper soldering materials will be important
  • as with any new air conditioner or heat pump installation, the amount of refrigerant charge may need to be adjusted to accommodate the volume within the refrigerant piping system.

Bending copper tubing - tips for

Incidentally, among my plumbing tools I keep a set of tightly coiled springs of appropriate inner-diameter to slip over flexible copper tubing that needs to be bent without crimping or kinking. These springs, sold at HVAC suppliers, slip over the tubing in the area where you want to make the bend, and the steel of the spring holds the copper tubing keeping it round so that you can make a bend without any crimps.

Also you may have noticed that even smaller diameter flexible copper tubing can become increasingly difficult to bend and re-bend in the same area of tubing. That's because as you bend the tubing the heat of the bending process alone is sufficient to anneal the copper, making it harder. So we try to get the bends nice and neat and right the first time.

Question:

Need to know what kind of fitting is used on a Carrier Air conditioner that attaches freon line to condensing unit - VInce

Reply:

Vince the two common piping attachment on refrigeration lines are soldered/brazed copper tubing at which a female connecting end is prepared using a swaging tool, and in some communities, carefully-prepared flare fittings. Details are in the article above.

Question: Are exposed copper refrigerant lines ok outdoors?

Is it safe to have all copper refrigerant lines installed on the outside of the house? Thank you, Caren

Reply: Yes but refrigerant piping should ben insulated, supported, and where outside, wrapped

A competent onsite inspection by an expert usually finds additional clues that help understand whether or not there are problems with your air conditioning system or its installation details. If you see signs of amateur workmanship on one part of the system it's appropriate to raise a question about other installation details that may not have been noticed, and thus to take a closer look.

That said, it is perfectly normal for copper air conditioner or heat pump piping to continue outside the house in order to connect to and from the compressor/condenser unit.

However air conditioner manufacturers and other expert sources include installation instructions that specify that the refrigerant lines should be insulated, supported, and wrapped with a weatherproof protective tape. Also be sure that the opening in the building wall where the refrigerant lines emerge has been properly sealed against leaks and insect pests.

Questions & Answers regarding this article

-->

Ask a Question or Search InspectAPedia

HTML Comment Box is loading comments...

Recommend / Share this Article            

...

Technical Reviewers & References

  • InspectAPedia.com® - Daniel Friedman - Publisher & Editor.
  • InspectAPedia Bookstore lists recommended books, organized by topic & available for purchase. Most of our articles also include a list of recommended books for the specific article topic as well as other references, and information sources.
  • Critique, contributions wanted: Contact Us to suggest corrections or additions to articles at this website, and if you wish, to receive online listing and credit as a contributor. Particular thanks are due to the many experts and also consumers who read and critique technical articles at InspectAPedia.com.
  • Additional technical contributors & reference sources for this article are listed below.

Use links just below or at the left of each page to navigate this document or to view other topics at this website. Green links show where you are in our document or website.

REFRIGERANTS
  GAUGE, REFRIGERATION PRESSURE TEST
  REFRIGERANT CHARGING PROCEDURE
  REFRIGERANT DRIERS & FILTERS
  REFRIGERANT LEAK DETECTION
  REFRIGERANT LEAK REPAIR
  REFRIGERANT METERING DEVICES TEVs
  REFRIGERANT METERING CAPILLARY TUBES
  REFRIGERANT PIPING & DISTANCES
  REFRIGERANT PRESSURE READINGS

  • Carson, Dunlop & Associates Ltd., 120 Carlton Street Suite 407, Toronto ON M5A 4K2. (416) 964-9415 1-800-268-7070 info@carsondunlop.com. Thanks to Alan Carson and Bob Dunlop, for permission to use illustrations from their publication, The Illustrated Home which illustrates construction details and building components. Carson Dunlop provides home inspection education including the ASHI-adopted Home Inspection Training Program (home study course), publications such as the Home Reference Book, report writing materials including the Horizon report writer, and home inspection services. Alan Carson is a past president of ASHI, the American Society of Home Inspectors.
  • Thanks to reader Anon. for discussing the allowable distance between air conditioner compressor and a building or from the air handler - July 2010
  • ASHRAE Handbook Refrigeration, Chapter 2, 2006. © American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc., www.ashrae.org
  • Refrigerant Piping Design Guide, McQuay Corporation, Americans HQ: 13600 Industrial Park Blvd., Minneapolis, Minnesota 55441, 800-432-1342 (Toll Free) 763-553-5330 (Direct), 763-553-5177 (Fax). Web search 07/15/2010 original source: http://www.mcquay.com/mcquaybiz/literature/lit_systems/AppGuide/AG_31-011_120407.pdf - quoting:
    McQuay International delivers engineered, flexible solutions for commercial, industrial and institutional HVAC requirements with reliable products, knowledgeable applications expertise and responsive support. As part of Daikin Industries, a Fortune 1000 company, McQuay is the second largest air conditioning, heating, ventilating and refrigeration company in the world. 
  • [1] "Air Conditioning & Refrigeration I & II", BOCES Education, Warren Hilliard (instructor), Poughkeepsie, New York, May - July 1982, [classroom notes from air conditioning and refrigeration maintenance and repair course attended by the website author]

Books & Articles on Building & Environmental Inspection, Testing, Diagnosis, & Repair

  • Our recommended books about building & mechanical systems design, inspection, problem diagnosis, and repair, and about indoor environment and IAQ testing, diagnosis, and cleanup are at the InspectAPedia Bookstore. Also see our Book Reviews - InspectAPedia.
  • Complete List of Air Conditioning & Heat Pump Design, Inspection, Repair Books at the InspectAPedia Bookstore.
  • Home Reference Book - Carson Dunlop The Home Reference Book - the Encyclopedia of Homes, Carson Dunlop & Associates, Toronto, Ontario, 2010, $69.00 U.S., is available from Carson Dunlop. The Home Reference Book is a bound volume of more than 450 illustrated pages that assist home inspectors and home owners in the inspection and detection of problems on buildings. The text is intended as a reference guide to help building owners operate and maintain their home effectively. InspectAPedia.com ® author/editor Daniel Friedman is a contributing author. Field inspection worksheets are included at the back of the volume.
  • Modern Refrigeration and Air Conditioning, A. D. Althouse, C.H. Turnquist, A. Bracciano, Goodheart-Willcox Co., 1982
  • Principles of Refrigeration, R. Warren Marsh, C. Thomas Olivo, Delmar Publishers, 1979
  • "Air Conditioning & Refrigeration I & II", BOCES Education, Warren Hilliard (instructor), Poughkeepsie, New York, May - July 1982, [classroom notes from air conditioning and refrigeration maintenance and repair course attended by the website author]
  • Refrigeration and Air Conditioning Technology, 5th Ed., William C. Whitman, William M. Johnson, John Tomczyk, Cengage Learning, 2005, ISBN 1401837654, 9781401837655 1324 pages
  • Carson Dunlop, Associates, Toronto, have provided us with (and we recommend) Carson Dunlop Weldon & Associates' Technical Reference Guide to manufacturer's model and serial number information for heating and cooling equipment ($69.00 U.S.).
  • Air Conditioning Inspection, Diagnosis, Repair, Efficiency all the basics for home owners, inspectors, new repairmen
  • NewAir Conditioning SEER - New DOE Air Conditioner and Heat Pump Efficiency Standard
  • Asbestos HVAC Ducts and Flues field identification photos and guide
  • Fiberglass: Indoor Air Quality Investigations: Fiberglass in Indoor Air, HVAC ducts, and Building Insulation
  • ...

  • Home About Us Accuracy Contact Us Content Use Policy Printing Tips Privacy Website Description © 2012 Copyright InspectAPedia.com