Water Pump Won't Run, Diagnostic FAQs
Well water pump won't start or won't run, diagnostic FAQs:
This article provides answers to frequently-asked questions about water pumps or well pumps that will not start or will not run.
If the well pump or control switch makes no noise at all, just hums or clicks, and when the water pump simply does not run these diagnostic questions may help track down and repair the trouble.
This article series gives diagnosis & repair advice for well or water pumps, controls, tanks, water pressure, water flow, water quantity.
InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers, products, or services discussed at this website.
- Daniel Friedman, Publisher/Editor/Author - See WHO ARE WE?
These questions and answers were posted originally
at WATER PUMP WON'T START - be sure to check out the ten diagnostic and repair steps that we give in that article.
Also see our index to all questions and answers about well or water pumps that won't start or won't run, at WATER PUMP WON'T START FAQs
...
Gone from home for a few days, turned pump on at fuse box, the pump ran 2 minutes then shut off. Now it will not come back on - Dave
Reply: Sequence of steps to check if the well pump is not turning on.
Dave: re "gone from home for a few days turned pump on at fuse box ran 2 minutes then shut off will not come on"
See WATER PRESSURE PROBLEM DIAGNOSIS TABLE for a comprehensive list of things to check when you've lost water pressure, including well pump troubles. By your message alone, and just guessing, as so little information is provided, I'd check things in this order:
Watch out: for electrocution hazards when checking electrical wiring and devices. If you lack training and equipment have those checks made by a professional.
Watch out: often when a pump is turned OFF for a few days we discover a pre-existing problem that had been covered-up, namely a bad foot valve or check valve that allows water to slowly leak out of the pressure tank and back into the well.
As long as the pump power is turned on, when the leak causes pressure to drop below the cut-in point the pump cycles on and re pressurizes the water system and so the pump never loses prime.
But when power to the well pump is left off long enough, a slow leak can lose all of the water above ground (back into the well) and you lose prime.
So that's where I'd start looking.
When I start my pump, it builds pressure to about 30psi and then shuts off and will not cut on again and I have to restart it and ends up same results. I've tried 3 different pressure switches.
My pressure tank has the correct air pressure in it. There's a lot of condensation on my pressure tank that I have never noticed before. Any suggestions on what to do On 2022-03-12 by Brian
by Inspectapedia Com Moderator - First check for the right air pressure but wrong air volume
@Brian,
I don't think this is a pressure tank problem - though if condensation reaches near the top of the tank, indeed it's water-logged ( a condition that can cause pump short-cycling).
Your tank might have the right "pressure" of air but not the right air volume.You want the tank air pre-charge to be 2 psi below the CUT-IN pressure when the pump has been turned off and all water pressure has been drained from the system.
Rather when the pump turns off before reaching the cut-off pressure I suspect the well is running out of water and the pump is being shut off by a pump protection switch OR the pump itself is overheating or failing.
...
...
We have had a lot of rain in the area and our pump quits working and we cannot get any water to the house. Is this normal?
I am not well versed on water pumps.
Is there a safety feature on newer pumps (about 2-3 years old) for when the water table is high, the pump will not work? On 2017-05-09 by Steve
by (mod)
Steve,
No it's not normal for rainfall to cause your well pump to stop working.
WATCH OUT: there may be wet electrical wiring or wet controls that could shock or kill someone. Ask your electrician to check the pump control circuit.
It would be odd to turn a pump on or off depending on the water levels in soil outside the well being high; a well pump protection switch does the opposite: protecting the pump when water level in the well is too LOW.
See WATER PUMP PROTECTION SWITCHOur pump won't run after a nightd of heavy rain
We've had 3.25" of rain over night and I'm waking up to no running water in the cabin! On 2020-02-06 by Kim King
by (mod) -
is it possible that a pump control or above ground pump has been wet or flooded or shorted out?
...
I have a pedrollo water pump with a smart head attached. It was installed about 1 year ago and was working great , but now it delays in switching on when the tap is turned on. What could be the problem? On 2021-06-29 by Dirkson
Explanation by inspectapedia.com.moderator (mod)
@Dirkson,
I would check first for a silt or debris-clogged water pressure sensor port. That is a very common cause of a pressure switch being slow to respond to a drop in water pressure below the CUT-IN pressure setting.Since silt and debris can clog both the pressure sensing tube that conducts water to the pressure switch as well as clogging the pressure sensor on the pump itself, if cleaning the tube doesn't get the switch to respond to a drop in water pressure I'd replace the switch.
Watch out: a pressure switch that doesn't properly sense water pressure can be unsafe: it may fail to turn the pump OFF at the CUT-OFF pressure - bursting a water tank and injuring anyone nearby.
On our well water pump system the gage is reading is over 100psi.
I bled the tank and it went back to 60psi and then and the pump came on the pressure went back to 100ps which cut the relay off, But no water is getting to the water heater - (Feb 21, 2015) calvin
Watch out: If the pressure really is that high the situation is dangerous as you can blow out the water tank or piping, causing injury or even death.
If the water pressure is really over about 70 psi then the pump control is not responding to water pressure and so is not turning off the pump.
That happens if the tubing that conducts water to the pressure switch is clogged or if the pressure sensor on the pressure switch is clogged or broken.
Clean or replace the tube and replace the pressure switch.
See details at
A separate possibility is that the water pressure isn't as high as the gauge reads, which can happen if the water pressure gauge itself is debris clogged and or faulty.
Check the actual system, pressure independently by following the instructions
I've adjusted cut on and off pressures, etc. My problem is that when the pressure drops through the cut in point, the switch "tries" to trip. The contacts close briefly, pump just starts to turn, then everything stops and pressure falls. I can start it with the manual switch and it will run fine . Pressure tank is brand new, and adjusted to about two pounds below cut in pressure. Any ideas?
Pressure control switch isn’t turning on the pump - when using the manual cut in switch the pump isn’t turning on either, however, if you manually use a screwdriver and push the contacts down you can get the pump to engage. hold the contacts down and you can get the tank up to pressure, however as soon you run out of pressure you have to go down with your screwdrivers and get the pressure back up
Hmmmm whats going on? (Oct 18, 2011) Kerry
Reply: check for a debris clogged pump pressure switch or sensor port or tubing
Jim,
I realize there could be another problem, such as with the pump itself, but I'd start by replacing the pressure switch. Also replace or clean out the switch mounting tube so we're sure it's properly sensing water pressure.Kerry:
it's possible that the pressure sensing port on the bottom of your pressure control switch is clogged and not properly sensing water pressure. If the switch thinks that you are above the cut-off pressure it won't turn on the pump. Another possibility is that the switch contacts are burned.
I'd try replacing the switch and making sure the little tube on which it mounts is also unblocked by rust or debris.
...
My water in my house stops working. If I go down to the tank and give it a little shake, my water starts working again for a short period of time. Could this be air pressure or maybe a switch? (June 15, 2016) Matt
Reply:
Sounds like a loose connection or switch component. Next time try tapping on the pressure control switch. Debris can clog its sensor. If so replace the switch. Keep me posted, Matt.
The problem with my booster pump is different from what you have described above...what I am experiencing is that the pump is late to 'kick in' and also late to cut off. I had tried to adjust pressure switch cut in and cut off nuts but the issue still persists (coincidentally my pump is fitted with Square D FSG 2 Pressure switch).
What you think could be the issue? Is it my tank bladder or the pressure switch? On 2011-08-27 by Izhar
by (mod) - Probable cause: sediment-clogged pressure switch or switch tubing
Izhar,
When a water pump is not responding properly to the pressure in the system I suspect that the pressure control switch is defective OR (and this is very common) if there is rust, iron, sediment, crud in the water supply, the switch may no longer be sensing pressure in the plumbing system.A blockage of the pressure switch mounting tube or the very small water orifice (hidden from your view) in the bottom of the pressure control switch sensing diaphraghm can cause the switch to delay starting in response to a drop in water pressure.
Other mechanical problems within the pressure control switch itself could be at fault too.
I'd replace the switch and the mounting tube.
...
...
Hello there! Our well water pumps works for two mobile houses. We had a really bad storm in which the power kept going off. Short story, we no longer had water.
Had a man come out and look at it. Well he said our pump went out.
Spent over $1550 and put a new pump, supposedly new pressure switch, new breakers, and new pipe.
Our water would work for 5 minutes at a time, then after 10 minutes would run again.
Then come to find out our pressure tank's bladder busted. So another $902 later we got a new pressure tank.
Our water worked good for a day. Now we have no water again. My husband checked the pump and it has 220 volts going to the pump but the pump won't turn on.
Checked pressure tank and its fine. My husband thinks our new pump burned out. Could it be something else maybe?
Is there anything we can do besides paying another arm and leg for another pump? Its been over a month with either little water or no water at all. I am over it! Please help - On 2021-06-10 by Alyssa
by (mod) -
@Alyssa,
Thanks for the question though, saying "thanks" when you have no water ....well that stinks.I agree with your husband that if power is being switched on to the pump and it's not running, then EITHER the wiring is broken or open between switch and pump OR the pump has burned-out.
A trained electrician might use a Volt-Ohm meter to measure the current draw and to check the wiring for a short circuit or an open wire.
Also ask Hubby to take a look at the diagnostic steps at
WATER PUMP WON'T START where there are more suggestions, starting withmaking sure that the pressure switch contacts are closing to turn on the pump
Repair tips: unless there is pressure in the system ABOVE the PUMP CUT-IN setting on the pressure control, the pump ought to run regardless of the pressure tank condition.
So first we rule out the pump: check the pressure control CUT IN setting against the tank's air pre-charge. How?Check the pressure in the system now that the pump is OFF.
If your installer put in a new pressure switch and did not fool with its settings, the CUT IN pressure is either 20 psi or 30 psi.
So if your system pressure is below 20 psi (easily done with pump off, just run some water) then
IF the pump isn't turning onAND IF there is power to the pump (on the pump side of the pressure switch that ought to be closed, calling for water)
THEN the problem is the wiring, or pump itself, or there is a broken-open water line
We just had a lightning storm blow thru and now my well quit. I can push in the reset button and pump comes on but after a few seconds it trips again.
Reply:
Look for a damaged pump wiring, lightning damage to the pump, pump control, even a leak in well casing or piping.
Start with following the pump controls and wiring. I suspect lightning damage to the pump motor.
Diagnostic question: When you say the pump comes on: is it actually running and delivering water, then turning off?
And when the pump turns off, is a circuit breaker tripped ?
Water pump did not come on after electrical outage. What might be wrong? (June 6, 2015) Ted
Reply:
Check all of the circuit breakers/ fuses for loss of power; also a lightning strike can damage well pump, well piping wiring, or the well itself.
...
My 2 line jet pump hums but doesnt turn over. I've replaced the start capacitor. But still nothing.
I am able to kick start the motor by turning the shaft with a screw driver. The motor doesn't get hot and sounds beautiful when running. What else could my problem be?
Thanks in advance for any input. On 2020-03-16 by BenG -
Explanation by (mod) - what to check when the pump won't start unless you spin it
Ben
Trying a new starting capacitor is a reasonable effort but if you used the right value starting capacitor, the cap is properly wired and is itself un-damaged,and if you've checked out other "pump won't run" causes given
We're left guessing a loose or bad internal wiring connection in the start circuit or perhaps low supply voltage
Our pump always needed a slight push to start the motor The switch was on when rwe an out of electricity and i forgot to switch it off.
After an hour when the lights came, back on we found thadt the water pump was stuck and wouldn't start.
And after half an hour smoke started coming out of wires of the pump. There was a little blasting sound too. what do i do now? (June 27, 2014) Asad
Reply:
Asad,
It sounds as if the pump as well as possibly some wiring burned up and so both need replacement. Also check for proper fusing.
The earlier problem of having to give the pump motor a little spin to get it going tells me that the pump probably had a bad starting capacitor.
So when power was off, then back on and you left the pump trying to start, it probably sat there humming and overheating without starting until the motor burned up.
...
Our well pump motor only hums when plugged in. (July 17, 2014) John
Pump not starting unless you spin fan by hand - (Aug 13, 2014) raykan
Reply:
John, look for a seized pump motor or bearing or impeller or a bad motor start capacitor
Raykan: your pump probably needs a start capacitor replacement
Watch out: when an electric motor hums but doesn't run leave power to it OFF - otherwise you risk an electrical fire or a pump motor that burns up beyond repair.
The repair may be as simple as a new starting capacitor, run capacitor, or lubrication of the pump shaft.
See CAPACITORS for HARD STARTING MOTORS
If that doesn't work see the electric motor diagnosis and repair steps for humming or buzzing electric motors
at ELECTRIC MOTOR WON'T START / RUN
My well pump needs a slight push to start the pump.
Switch was on when ran out of electricity and i forgot to switch it off. After an hour when the light came, since switch was on so pump stuck and did'nt start.
And after half an hour smoke started coming out of wires of the pump... there was a little blasting sound too. what do i do now? (June 27, 2014) Asad said:
Reply:
Asad,
Sounds as if the pump as well as possibly some wiring burned up and need replacement. Also check for proper fusing.
Then ask your electrician to check the well pump motor for a failed start or run capacitor.
...
Pump won't start on battery power
Hi I have a small water pump that I use for a saltwater aquarium.
I live in a country that power comes and goes, so we use automatic invertors and run off batteries when there's no power
Trouble is the pump has trouble starting on batteries - just click and rattles and takes about 15 minutes to start. I've checked the voltage at the plug - 120 same as with power from the company.
I've tried other pumps, and other outlets - same result. The only difference I can see is that the invertor is quasi-sine (or modified sine)... would this make a difference? Are pumps sensitive to this? On 2017-03-28 by Tim
by (mod)
Tim,
I too have read about the difference in power curve properties between backup battery systems (square wave) and grid power systems (sine wave) but I don't think we have to focus on that difference to solve this problem.
You'll want to either buy a self-contained battery-backup aquarium pump (the less expensive solution) or to buy a true battery backup system - also referred to as "double conversion" power backup systems.The DC battery is charged from line voltage (until a power outage) but the power the unit produces from the DC battery is converted back to normal or standard AC power.
These will cost 3-5 times a battery-backup acquarium pump but could be needed to handle either longer power outages or larger pumps.
Indeed many battery backups don't provide the same current draw (amps) that a motor might use briefly at start-up; but I'd expect that if you try out a larger battery-backup system that will solve the problem.
One thing that always gives me courage in attacking a question like this is that I figure someone has already had the problem and has come up with a solution. I looked around and found that several companies sell battery-backp pumps specifically for aquariums, since obviously we don't want a power outage to kill the fish or whoever else is living in the aquarium.
Some battery backup aquarium pump vendors include
APC Smart-UPS aquarium backup systems
Azoo whose pump will run for 10 or more hours if there is a power failure
...
The water pressure has been dropping low then comes back for a few weeks now last night lost water all together.
I try to prime the pump; it will kick on and suck water and pressure goes up but once I put hose back on the pressure drops to 0 .
I did pour water over pump to cool because it was very hot.
Now when I try to prime the pump it smells like wire burning and smokes white smoke could the smoke because the water I poured on it . And the reason pressure drops back to 0 when I put hose back on. On 2017-02-26 by nancy
Recommendations by (mod)
Sounds as if your pump has been running dry, overheating, and is in danger of being damaged; if it's not delivering water, leave it off.
Watch out: while your pump motor was overheating, a sign of failing bearings or low voltage or other damage, pouring water over it may have caused an internal short that burned up the pump motor.
Watch out: In my OPINION it's unsafe to continue to try to run this motor. Leave power off to avoid an electrical fire or shock.
The underlying problem could be that there's low or no water in your well.
It'a time to get a trained service tech on site. DF
Well pump hot to touch. Low water pressure. Turned pump off but now it won't come back on, just hums. On 2017-02-12 by Peter
by (mod) - signs of a pump wiring error or damage
Sounds to me like a wiring problem, perhaps damaged wire or a bad connector. Less likley but possible: a failing pump motor that's drawing high current or a pump with a failed start capacitor.
...
My water well will work for about 20 minutes, then it shuts down. I can re-start it by depressing the disconnect switch. What is my problem ? (July 1, 2015) John Stauffer
Reply:
Most likely the well flow rate is very poor and your are pumping water out faster than the well recovers. If your pump is protected by a pump protection switch it may be shutting the pump off when the control detects that the pump is not getting water.
We explain that safety device at WATER PUMP PROTECTION SWITCH
If there's a possibility that your pump is indeed pumping the well nearly dry, you can confirm that problem by
a WATER QUANTITY TEST: WELL FLOW TEST
A second possibility is an overheating well pump motor.
If that were the case it would not re-start immediately on stopping, as time would be needed for it to cool down.
At ELECTRIC MOTOR OVERLOAD RESET we explain that the underlying cause can be low voltage to the pump or a failing pump bearing or similar issue.
Dear Dan, I have an irrigation network in my home garden using sprinklers that connected and supplied from my home water supply network (bathrooms,showers water faucets and so on.) which supplied from upper roof tank by a pump (booster).
The water is supplied to this upper roof tank by another pump located at the entrance of my home (at ground floor).
When the irrigation system stop, no water come down from the upper tank because both two pumps are shut down and need to be reset manually from their electronic pressure controller. I don't know why?
What can I do to solve this problem? (July 11, 2015) Anonymous
Reply:
Anon
It sounds to me as if you ran the water out of the rooftop tank and ran the supply pumps dry until they shut off on thermal reset.
...
...
Continue reading at WATER PUMP WON'T START - topic home - for ten things to check or select a topic from the closely-related articles below, or see the complete ARTICLE INDEX.
Or see these
WATER PUMP WON'T START FAQs at InspectApedia.com - online encyclopedia of building & environmental inspection, testing, diagnosis, repair, & problem prevention advice.
Or see this
Or use the SEARCH BOX found below to Ask a Question or Search InspectApedia
Search the InspectApedia website
Need to make a private comment? Email editor@inspectApedia.com. We welcome email with your website content critique, corrections, suggestions or questions. Email is monitored daily but our workload may prevent an immediate reply. For immediate results, we hope you'll first try asking your question using the search box just above.
In addition to any citations in the article above, a full list is available on request.