Building Inspection, Diagnosis & Repair Info

WellMate  fiberglass water pressure tank (C) D Friedman J HafnerWater Pump Short Cycling Diagnostic FAQs

  • POST a QUESTION or COMMENT about diagnosing problems water pumps, well pumps, pressure tanks that show up as pump cycling on & off too often or too rapidly

Water pump short cycling diagnostic FAQs:

This article provides answers to frequently-asked questions about how to diagnose short-cycling problems with a water pump or well pump.

If the well pump runs too often or cycles on and off rapidly these diagnostic questions should help troubleshoot the problem.

InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers, products, or services discussed at this website.

- Daniel Friedman, Publisher/Editor/Author - See WHO ARE WE?





ADVERTISEMENT





Q & A about well pumps or water pressure pumps that run too often (short cycling)

These questions and answers about troubleshooting and fixing a well or water pump that keeps turning on and off rapidly were posted originally

at SHORT CYCLING WATER PUMP - home - be sure to read the procedures and repairs discussed there.

Article Index

...

Definition & Examples of Well Pump Short Cycling

What pump on-off frequency or interval is considered "short cycling"?

I really appreciate your comments but am having a slight problem with terminology. Is the “cycle” of a well pump measured by the time from when it turns off to when it turns back on or the time from when it turns on until the time it turns on again? I have a bladder tank set at 40 psi/65 psi.

When I run three outside hoses it takes roughly a minute from when the pump shuts off at 65 until it turns on again at 40. It then takes about 4 minutes from when it turns on at 40 until it shuts off at 65, i.e., a total of five minutes between turn on’s. So is my cycle only one minute or is it 5 minutes?

And in either case, does that sound like I’m likely burning out or shortening the life of my pump? Thanks much.

A follow up question to my previous one. In general, at what frequency of turn on to turn on ((i.e., from when it clicks on at 40, pumps up to 65, drops back down to 40 and clicks on again) do you start to worry about burning out your well pump motor or your switch?

Every 2 minutes? 5 minutes? Etc. Thanks so much. On 2020-08-31 by Greg

by (mod) - Opinion: 30 seconds or less is "short cycling" of a typical residential water pump

Greg

At 30 seconds or less intervals between pump on cycles I consider that short cycling that should be addressed and

Watch out: if your pump is short cycling very rapidly, say every few seconds or less, repair is more-urgent lest the pump or the pressure control switch are damaged.

How fast is "rapid cycling" or pump short cycling?

I have a small pressure tank and expect that the pump will have to turn on and off, but when is it cycling too fast?

How many seconds should it run before kicking off and then restarting? On 2017-03-26 by Anonymous

Recommendations by (mod)

How fast is "rapid cycling" or pump short cycling? good question.

IT depends on tank size, and more, on the water outflow or usage rate, and also the pump's pumping rate capacity in gpm for the whole system including total vertical lift, piping restrictions & distances.

If a pump, tank, piping, well are in perfect condition and the pump is cycling on and off for a moderate water flow usage rate such as someone running a bathroom sink faucet, then if the pump is turning on and off more often than every 30 seconds I'd want a larger pressure tank.

The pump manufacturers, are, however the final authority on this so you'll want to check with the company who makes your tank.

Certainly if a pump under any circumstances is turning on and off every few seconds or less, something's seriously wrong and the pump or its controls are likely to be damaged or to have a short life.

For pressure boosting pumps that do not use any pressure tank (the control that turns the pump on and off is built into the pump), the pump turns on as soon as a plumbing fixture is opened to run water and runs all the time water is being run.

Watch out: with tankless booster pumps: any small leak such as a running toilet or pinhole leak in a pipe may cause the pressure booster pump to cycle on and off more frequently than the manufacturer intends - risking damage to the pump.

Pump cycles every two minutes: is that "short cycling"?

So I had a pressure tank installed on my well today because the system of short cycling bad. I would turn the water on and it would go up to 50 PSI and drop down to 30 PSI and repeat every few seconds. The tank I installed is a 20 Gal.

Now when I run the water the pressure goes up to 50 in about 2 minutes, and then the pressure is down to 30 PSI in about the same time. Is this a normal rate?

or is there still a problem? I was under the impression this tank was suppose to keep that from happening. (Sept 14, 2012) M1helmethead

Reply: that's normal

M1

You are describing what sounds normal for a small sized water pressure tank.

To get a water draw-down time that is longer there are two approaches - choose depending on your equpment's capability:

1. install a larger capacity water pressure tank - 20 gallons is not much drawdown, but you won't want to do this having just installed a new tank

2. adjust the pressure control switch to widen the gap between cut-in and cut-out pressures. Just be sure not to set the cut-out to a pressure higher than your pump can maintain. For example, if you set the cut-in DOWN to 20 or 25 psi and keep the cut-out at 50 you'll get a longer draw-down cycle.

The draw down time for a properly-charged water pressure tank (with proper air pre-charge) depends on tank size, water pressure, and the flow rate out of the tank.

 

Water pump is cycling on and off,every 2-3 sec. when a tap is opened

My water pump is cycling on and off,every 2-3 sec. when a tap is opened. I have replaced the switch with a 20-40 psi switch and checked that the pressure tank ( bladder type ) has 18 psi in it.. any ideas would be helpfull. Tks 10 Aug 2015 Dave

Reply:

Dave:

Watch the pressure switch. It's possible that water is not entering the tank or that your tank is waterlogged and includes a pressure gauge that's stuck, giving a false reading.

Gently rock the tank (don't break any connections) and you can usually tell if it's empty (it'll be light), and similarly, if no water is entering the tank its pressure and temperature and weight wont' change.

If you are dead certain the pressure tank accepts water and is being pumped up I cannot imagine why you'd have sort cycling every 2-3 seconds. I'd be looking for an obstruction that lets water into the tank such as a bladder stuck on itself or a nearly closed or blocked valve.

Our complete diagnostic list of all known causes, diagnostic steps, and repair procedures for well pump short cycling is

at WATER PUMP SHORT CYCLING DIAGNOSIS TABLE

If you are not sure what "water pump short cycling" means or how it is recognized, see

SHORT CYCLING WATER PUMP.

Intermittent water pump cycling which is discussed at

INTERMITTENT WATER PUMP CYCLING When No Water is Running means that the water pump comes on for no apparent reason.

Loss of water pressure means that the pressure with which water enters a plumbing fixture has become too slow, or is sometimes too slow or weak in water flow rate, or water flow may stop entirely.

See WATER PRESSURE LOSS DIAGNOSIS & REPAIR

...

Well Pump Rapid Cycling as Cut-Off Pressure is Reached

Pressure Switch Cycles On and Off Rapidly at End of Pump-On Cycle

Pump pressure switch switches on and off rapidly when high pressure is turning pump off On 2018-05-23 by Rob

by (mod) - problem of rapid water pump on-off cycling right at the CUT OUT pressure

Often I find that the problem of rapid water pump on-off cycling right at the CUT OUT pressure is traced to

- Most Often: a debris-clogged check valve between pump and well pipe bottom - pump stops, high pressure water squirts back into the well, pump re-starts. You can diagnose this by watching the water pressure gauge at pump cutout.

Try turning the pump OFF just as it's reaching the CUT OUT pressure, then watch the pressure gauge.

If it falls, and if no water is being used in the building (turn that valve off for this test) then there's a leak between pump and well pipe end.

- On occasion: a failing pressure switch: burned contacts,

- Often: debris-clogging at the switch pressure sensor port or in the tube bringing water pressure to the switch,

- Commonly: water leaks in the system, such as a bad check valve or foot valve, that shows up more severely at the higher pressure near the pump CUT OFF setting

- an obstruction anywhere between the pump and the pressure tank

- or a cut off pressure that is close to just what the pump can produce

- On occasion: improperly-located pressure control switch - too far from the pressure tank - if this is the case the problem may have always been there or it may show up on an older system in which for any reason the pump output capacity has changed

Details about these problems are

at WATER PUMP PRESSURE CONTROL SWITCH CHATTER 

Also review WATER PUMP SHORT CYCLING CAUSES

or if you prefer causes and cures in a more concise table see

WATER PUMP SHORT CYCLING DIAGNOSIS TABLE

If the pump turns on immediately when you open a tap your water pressure tank is water-logged - has lost its air charge, see WATER TANK AIR, HOW TO ADD

If the pump runs occasionally for no reason there's water running somewhere or there there's a leak - see WATER PUMP INTERMITTENT CYCLING

 

Well Pump Sometimes Cycles on and Off repeatedly at the end of a pump-on cycle, then stops.

By water pump seems to cycle properly while we're running water.

The proplem is "Some Times!!" at the end of the cycle as the pump cuts off it immediately restarts for a second or a couple seconds cuts off repeats then will cut off normally --- the water pressure is at the high point on the gauge when it gets to the lower cut on pressure it will cut on again,

but at the end of the run cycle it will the "chatter" or cut off as it should -- real problem is sometime the contacts are together (but don't conduct enough to start the run cycle then I have no pump and no water On 2012-07-18 by Anonymous

by (mod) - causes of a sudden repeat pump cycle right at the cut off point

Anon:

Two things (there are surely others) that cause a sudden repeat pump cycle right at the cut off point are

- burned pressure control contacts or a failing switch

- dirt or debris blocking the pressure sensor port at the switch base

From what you describe, I would replace the switch and make sure to also clean or replace the tubing or pipe nipple that conducts water pressure to the switch mounting base (that contains the pressure sensing port)

Jim:

It sounds to me as if there is a bad check valve in the pump or in the well, perhaps combined with a waterlogged pressure tank.

Jennifer: I'm not so sure of this one, partly we need to know how the well and water piping are routed; Usually a well pump feeds the building and simultaneously the pressure tank; If that's your case and you get no water at the house the problem is obviously before that point - a well piping leak, clog, valve problem.

If your water pressure tank is piped "in series" between the incoming water and water piping to the house such that water has to enter the tank before heading on to the house (an unusual setup) then you could have a stuck tank bladder that prevents water from entering the tank.

 

...

Short Cycling Pump due to Stuck Water Tank Bladder

Water Pump short cyles even with a brand new bladder type water tank

Just installed a new deep well water pump and new precharged bladder tank but pump is short cycling or kicking on and of again every few seconds. Can hear the pump turning the water used to prime it and both lines running to jet in well were profiled before hooking up the pump to lines . I am stumped as to what is causing this do you have any suggestions On 2019-02-14 by Gloria

by (mod) - check for and fix stuck water tank bladder

Possibly the tank bladder is stuck against the tank inlet and ban be freed by a brief higher pressure as long as you stay below the tsnks safe upper pressure limit.

 

Pump cycles on and off multiple times before reaching the CUT-OFF pressure

Water pump kicks on for about 5 seconds and cuts off with pressure switch contacts still closed . It takes about 5 times on and off to build pressure up to 50 psi and open contacts? On 2016-12-30 by Brian

Diagnostic suggestion by (mod)

Brian:

Start by checking for a clogged filter or a valve that's clogged or nearly closed between the water pump and the pressure tank or building.

 

...

Artesian Well Floods Water Tank?

Could an artesian well be putting water into the pressure tank even with the pump OFF?

My well supply water tank is 33 gallon 30/50, tank PSI at 28. The more I read the more I am getting confused.

Pressure drops to the cycle on after running faucets 2 minutes. When it is filling it takes 40 seconds to fill again. When water isn't used the pressure gauge is steady. So no leaks

The plumber stated older style bladder pressure tank switch, drained and pressure check was all good. However, as he was draining it he emptied 5 buckets of water and the tank was still draining.

Question is - is it possible that the artesian well with its constant flow of water could have been putting water into the tank even though the well pump power was switched off?

I believe that light switch is how to shut off the power to the well pump - right? On 2019-01-19 by bvorobel@yahoo.com

Solution by (mod) -

BV

Thanks for an interesting question.

Certainly if you turn off power to the pump - as you indicated and as we see in the photo - then a flowing artesian well condition could continue to send water up to the pressure tank and building plumbing.

Some wells can temporarily function as a flowing artesian well (read about those by searching this site for ARTESIAN WELL) .

But "emptying 5 bucket of water" from a pressure tank isn't a decisive fact.

First: your water pressure tank is one that uses an internal bladder.

So there is NO reason that the tank should EVER need emptying. The bladder keeps water and air separated. Air doesn't get absorbed into water and air isn't lost from the tank unless the tank or its air valve or the internal bladder (one of those) is damaged or leaky.

The fact that your plumber was trying to empty an internal bladder pressure tank suggests inexperience or error.

If someone is trying to empty a tank like yours (which I said is not necessary nor useful) the air pressure in the water tank would make the tank continue to "empty" until pressure on the gauge and tank and system dropped to zero.

Your initial description of how your water system is operating does not sound odd to me except that the tank fills pretty quickly. That can be normal IF your submersible well pump is a powerful one and the well has great flow rate.

The tank air pre-charge of 28 psi is correct for a 30 psi CUT IN pressure control switch.

So in sum your system was probably working normally to start with.

Finally, you can rule out an "artesian well" as supplying water to your tank simply by turning off the valve (not shown , so I don't know if one is installed) between the supplying water line from the well and the tank itself.

but DO NOT do that if the pump is turned on as that could cause damage.

Turn off power to the pump

Close the valve

Drain the tank (for no reason as it's not necessary except for your own edification)

Notice that ultimately pressure measured at the tank drain or elsewhere in your home falls to zero and water stops leaving the tank.

At that point, IF you measured air pressure at the air pressure gauge on the tank top (under that little black cap on the right side of the tank top in your photo) you should see 28 psi of air pressure - that's the tank pre-charge pressure.

Close the tank drain.

Confirm the tank air pre-charge

Turn the pump on.

Done

Thanks so much for your information. You are the only one who made sense by writing in more layman terms.

Thanks so much for your information. You are the only one who made sense by writing in more layman terms.

I believe the large dial on the piping is a shut-off valve so you can stop the well water from coming into the house from the well.

The plumber couldn't shut that down so I am assuming the artesian well water flow was still entering even though he turned the submersible well pump power off.

The well pump is 1/2 hp and the well is only about 100 feet deep when they hit the spring.

The outside water gate ("faucet") at the top of the well pipe (14 Inches above ground) flows continuously (ALWAYS) with an air space of about 3 inches into another pipe that flows underground to a creek

. I am assuming that would be enough water pressure to continue into the house on its own volition without power. That is why when the plumber was attempting to drain the basement water storage tank water just kept running out of it. Thanks again. I think I will leave well enough alone. I was concerned about the 40 sec it took to fill the tank as being too short of a time.

And that tapping the outside of the tank didn't offer two different sounds like one part (top) being a hollow sound as far as I can tell.

Sometimes it seems like it an then again it doesn't. When it fills I can hear the movement of a balloon type sound or some type of movement. https://inspectapedia.com/water/Artesian_Flow_Disch_MI_050s.jpg On 2019-01-19 by bvorobel@yahoo.com

by (mod) -

BV

In your photo the green handled valve appears to be a shutoff between well piping and the pressure tank and switch.

It's common for an old, seldom-used water valve to fail to work when needed. It can be replaced by a plumber.

Your description of conditions at the well sound like a flowing artesian well.

You will want to read details at ARTESIAN WELLS, WELL SPOOLS inspectapedia.com/water/Artesian_Well_Spools.php

Your concern about a short 40-second tank fill time was reasonable- in that ***IF*** also the draw-down time in water volume and time before the pump turned on was also vey short - that would be "short cycling" of the well pump, described at

WELL PUMP SHORT CYCLING inspectapedia.com/water/Short_Cycling_Pump.php

where we give causes and cures.

BUT your case, driven by a (at least sometimes) powerful voluntary water flow out of a flowing artesian well is a different situation. The water tank re-fills so quickly because your well is sending water up to the tank at an unusually fast rate.

The movement and "balloon" expanding sound you hear may be the rubber bladder inside your water pressure tank as it expands and contracts.

Above (for other readers) is the illustration you were attempting to attach

...

Proper Tank Air Charge to Avoid Short Cycling

What's the proper pump air pre-charge pressure to avoid short cycling?

Our water pump runs short cycle recharge tank when drained water what should the pressure be and when filled what is its pressure to be for 40-60 ? (Nov 29, 2012) Jerry

Explanation by (mod): how and what air pressure to set in the water tank

With an empty tank and pump off the air precharge should be set to 2 psi below the cut-in pressure.

But

Watch out: it's not just pressure measured under any circumstances.

Properly your water tank must be empty when you set the air pre-charge pressure. - Daniel

...

Well or Piping Leaks vs Short Pump Cycling?

We hear hissing air leak sounds coming from the well and have no water

I can hear what sounds like a small air leak down in my shallow well and the pump will not run.I am wondering if I could have a bad foot value? We have just replaced the air tank,pressure switch and gauge.my well is only about 8 feet deep and has had a good supply of water for approximately 50 years.

please respond asap as I have been without water for 2 weeks and am very homesick. I'm on a fixed income and trying to figure all this out myself,with only help from a sister. (Feb 17, 2014) sue

Reply:

Sue,

I'm of course not sure what you're hearing but:

First: leaks anywhere in the water system can cause the pump to turn on and off even when nobody is using water. With a pressure tank that does NOT use an internal bladder (to protect against loss of its air charge) that can lead to loss of water tank air and then to pump short cycling.

Next: a hissing noise sounds like a leak somewhere.

Assuming you've got a one-line jet pump (which would work for a well just 8 feet deep) and the pump is above ground, with a simple foot valve at the bottom of your well pipe in the well,

THEN if you hear hissing I suspect that the pump is running but a leak at a pipe fitting connection or at a hole in well piping could be allowing air INTO the well piping;

Air in the line will cause air cavitation inside the pump body and the pump will run but not pick up water.

WATCH OUT: do not leave the pump running with no water - it can damage the pump.

As you just replaced the pressure tank I wonder: has your pump always been above ground? If so you can ignore my remarks below about snifter valves.

Start by using a good flashlight to look into the well casing: with the pump running you expect to see a single pipe in the well casing and from the above we expect to hear air entering the well pipe; but there might be something else going on.

Less likely, but you could be hearing air escaping from a bad snifter valve though I'd expect a snifter valve ONLY on a deep well with a submersible pump - search InspectApedia for "snifter valves" to read about that topic.

...

High Water Pressure Surging

Sudden water pressure surge to high pressure 80 psi and blew out a water pipe! Can't get pressure below 60 psi.

My water pressure suddenly went to 80 psi. It blew a water line. I’ve adjusted the pressure switch to 60-70 but cannot get it to drop below 60 psi. Is this due to a bad pressure switch? Thanks!(Apr 26, 2014) Dave Jones

Reply: repair procedure

If your pressure tank never goes below 60 psi do this:

  1. Turn off power to the pump
  2. Run water until no more water comes out of the tap
  3. Check the water tank air pressure with an independent pressure gauge (your tank gauge could be stuck)
  4. If the water tank air pressure is NOT 2 psi below your pump switch CUT-IN then release tank air to drop pressure to that point.
  5. Set your pressure switch to a wider spacing such as CUT-IN at 40 psi and CUT-OUT at 60 psi or if you insisit on 70 psi then set the CUT-IN to 40 or 50 psi.
  6. Adjust the empty water tank air pressure to 2 psi below the new CUT-IN pressure.
  7. Turn the pump back on
  8. Check the pump operation and tank pressures again

Diagnose our water pressure problems in Peru: pressure shoots up higher than permitted; how do I fix it?

I have a problem with the pressure in my water system and it is making a lot of pipes leak.

When the Pump starts the pressure shoots up to 5 bar and is designed to run at 1 bar. Can you tell me how to reduce the pressure. it is a fairly new system
Help please - (Nov 14, 2014) John Bickerton in Peru.

Reply:

Juan

Your pressure control switch may be improperly set, the pump may be over-sized, or you may need to install a pressure regulator on the house piping or at the pump outlet.

...

Short Cycling Pump due to Bad Motor Capacitor?

Short cycling well pump traced to bad start capacitor

My deep well submersible pump was short cycling, 4-5 seconds every minute or so. I changed the pressure switch but the problem continued. further troubleshooting revealed very high amp draw from the pump while it was trying to turn on.

The reason for this was the pump control start capacitor had burned out. The pump requires a "boost" of electrical energy to get started and run.

When the capacitor goes bad, the pump is unable to start and run, causing a high amp draw and short cycling. Replacing the start control box fixed the problem. Hope this helps. 7/23/14 M.H.

Reply:

M.H.

Thanks for the comment.

Usually short cycling is caused by a waterlogged pressure tank.

But some pump motors use a start capacitor that can fail - just as you cite.

Or a pump motor may be old, worn, and have trouble starting - needing a stronger, booster start capacitor.

See CAPACITORS for HARD STARTING MOTORS 

But because a waterlogged pressure tank can cause short cycling that can in turn damage pump controls or starting capacitor, or the pump motor itself, I'd double check that the pressure tank is not itself waterlogged.

Diagnose hot well pump motor, no water

Nick's water pump (C) InspectApedia.com GE pumps

I have a water pump that I don't use often. Today when I turned the water on I did not have any.

I check the pump and the motor felt warm to the touch. I disconnected the power supply and turned the shaft. I plugged it back up and it eventually started back pumping. It stopped again and I replaced the pressure switch.

It worked fine for several hours but now I have not water and the pump is not cutting on again. What could be the cause of this? (Oct 31, 2014) Anonymous

Reply:

Anon
Sounds as if the motor is seizing; you might try checking for lubrication requirements or for an impeller that is debris clogged.

IF the pump is removed and disconnected from power and the motor won't turn freely, replace it.

...

Water Pump Short Cycling on Water-to-air Heat Pump System

With new pressure switch the pump still cycles every few seconds

Our InspectApedia reader asked us:

I have a water to air heat pump supplied by a 1hp jet pump. After inspection, the contacts on the pressure switch appeared burned.

Replaced the switch, however, upon replacement, the pump began cycling every few seconds while the AC unit was running.

Usually the pump runs continuously providing water to the system until the AC unit turns off. Afraid of burning up my pump if this continues.

Possibly a bad bladder tank (it's a small one like that used in an irrigation system)? Sept 17, 2014) DPaul1701

Reply: diagnose the cause of short cycling water pump on a water-to-air heat pump

Indeed,Paul, if a water pump is short cycling that can burn up the switch contacts as well as damage the pump itself.

But the short cycling is the symptom of an underlying problem.

Short cyclilng, when the pump turns on and off every few seconds tells me that you have no working pressure tank with an air charge.

IF your water to air heat pump system is a closed loop system then the problem is with the controls and pump installation.

IF your water to air heat pump system is an "open loop" water to air heat system, then there should be a water pressure tank that includes an air pre-charge. Since you mention "possibly a bad bladder tank" I suspect that's what you've got.

That air charge in the tank acts like a giant spring to push water out and into the building when a tap is opened. Without it, because water itself is not very compressible, the moment you turn on the tap the pump will begin to run and as long as the pump can pump water faster than you're using it, the pump will cycle on and off rapidly.

Your case might be a ruptured tank bladder or something else. So check that little pressure tank - if it's water-logged it will need to be replaced.

At the Continue Reading section on this page you'll see more detailed pressure tank diagnostic articles. - Daniel F

For your heat pump diagnostics see these two pages

HEAT PUMPS - home

DIAGNOSTIC GUIDE A/C or HEAT PUMP - diagnose air conditioner or heat pump not working

...

Short Cycling vs Finding Cause of Tank Air Leak

Short cycling farm well pump - couldn't find an air leak

Our farm well pump is short cycling when the water is run.

A constant pulse or surge.

It is supposed to cut in at 30 psi and cut out at 50 psi. However, the system shows 110 psi at the gauge. Turn the water on and it quickly drops to 80 psi where the pump cuts in and pegs the gauge, pulses between the peg and 100 psi until you shut off the water. Then it short cycles and settles at 110 psi. Although gauge shows 110 psi, water pressure appears normal..not 110 psi. I'm stumped.

Water pressure gauge shows 110 but I know pressure is not that high.

Also, the short cycling is a pulse or surge with constant clicking of the relay.

Reply:

Monte,

Watch out: That very high pressure is likely to exceed what your water pressure tank can safely handle. The risk is an exploded water tank or burst pipe that injures or kills anyone nearby and of course also there's a risk of pipe leaks.

Set the CUT-OUT pressure down to 70 psi or below.

The rest of your problem sounds like classic short cycling due to a water-logged tank and probably a debris clogged pressure gauge.

Try the diagnostic list at WATER PUMP SHORT CYCLING DIAGNOSIS TABLE

Monte replies: We also found that the pump starting capacitor seems to be corroded and leaking dielectric.

Moderator reply:

That s ounds like the pump needs repairs to start and run normally. Other readers have reported pump short cycling and having trouble starting when the starting capacitor for the pump motor is bad.

Monte Myers follow-up: damaged pressure gauge repair; tank lost air charge but don't know why

Dan,
The gauge face was bent causing the dial to spin on its' shaft. It wasn't clogged. I installed a new gauge. The tank had lost its' air. I added air and the short cycling stopped. However,I couldn't find any cause for the air loss.

Moderator reply:

Thanks for the update Monte.

Air may be lost from a pressure tank by absorption into the water passing through if the tank is *not* one that uses an internal bladder to keep water and air charge separate. Air can also leak out through a pinhole leak in a tank or from a leaky air fill valve.

...

Short Cycling Water Pump but Water Tank is OK

Pump short cycles but pressure tank does not seem water-logged

I have a Well Rite WR60 tank in my house system that was completely overhauled 4 years ago.
I'm experiencing short cycles and an extreme drop in pressure just as the pump is about to kick in at 40 psi.

First I replaced the 40 - 60 switch and no luck.

Then I checked the tank air pressure when drained and it was high - close to 50 psi.

Reset the air pressure to 38 psi and thing ran OK for about a week and then back to the short cycling and surging at cut in.

I've reset the air pressure several times but it never seems to last more than 4/5 days.

One thing that confuses me is that when I relieve the excess pressure there is no water coming out.
For what it's worth the tank is still under 5 year warranty but - probably pro rated ? 12/11/2014 Ron

Answer by mod: bad pressure control switch or water not entering water tank

Ron

Have you checked for a pressure switch that is not sensing water pressure due to clogging due not to the switch(which you replaced) but due to a clog in the small diameter tubing on which either the switch mounts or that conducts pressure to the switch sensing port?

Also have you confirmed that when the pump runs water is actually entering the water pressure tank? If not that could explain pump short cycling even though the water tank is "empty".

IF we find high air pressure in the tank after it's drained:

There could be a small leak in a tank bladder - in odd cases water leaks out of the bladder into the air space enough to keep pressure there abnormally high. If you think the tank is "empty" of water but it still feels heavy it may contain water.

I know we expect water to squirt out of the air valve when a tank is fully waterlogged, but it is possible for some water to be in the tank bottom but air still at the tank top (the water should be in the bladder not outside it in most designs).

I think of this as described by a few other readers as "pinhole leak in water tank bladder results in abnormally high air pressure creeping up in the pressure tank"

See PINHOLE LEAKS in WATER TANK BLADDER

...

Well Pump On-Cycle Too Short

How to get a longer pump-on cycle - problems traced to damaged pumps

Thanks for all the help guys!! The first water pump was tested and had a mechanical malfunction.

The second one had a bad injector.

The power to the well house was always turned off unless a test was being ran. Furthermore I was rewarded with a full refund on first pump and the second pump I was rewarded with exchange.

After this I decided to do a shallow well attempt instead of deep well.

I now have 1 pipe to the house (discharge tee placement) and a pipe from the pump( Injector On assembly) to well. After this I took off the additional pipes and have foot valve and cycle stop valve with control box installed,(3 way) 30\50 pressure switch, (on pump instead of hose line to switch) and the bladder tank at 28.5 psi.

After using the blue glue I made a final check of the 2 pipes and all connections and made my electric connections secure. I primed the pump and did a operation test. i did get to 10 psi on first attempt. After 82 gallons of priming water I can now say i FIXED IT and working GREAT :-) :-)!

Now I do have a question. Can I do a longer cycle? Example: 30 psi cut in/on and 55 psi cut out/off?

Now with all my issues fixed I would like to look out for "short cycling". I wanna say thank you to everyone for the help and a special thanks to DanJoeFriedMan for sticking in there with me! Hope to hear from you soon! 5 Aug 2015 Josh ( Mountain Well Water) FIXED!!

Reply: how to get a longer pump on-cycle

Nice going, Josh and thanks for the follow-up.

You can get a longer pump on-cycle by

- installing a larger pressure tank

- spreading the cut-in and cut out pressures as you describe. Just don't set the cut-out higher than the pump can achieve, and when setting the cut-in down lower check that your building water pressure remains adequate on the upper floors.

30/55 is within the range of most pumps. You could even go to 20/50 or 20/55 if pressure is adequate at the low end.

Installing low flow rate plumbing fixtures will also slow your water usage rate and give the pump and well a bit of a break.

Joshua (Well Water) said: Discharge tee on pump was set too low and pressure switch sensor line was clogged.

So I Got the water running. The Discharge Tee on top of the pump had to turned down to set flow.

Also Pressure switch had sediments in line. Now as i got the water back on i had some faucet issues in kitchen and bathroom. I took the kitchen hose off and cleaned out the head of the handheld.

As for the bathroom. The toilet had some trash in it so i bought a new Korky Quiet Fill to replace. for the shower/tub. I Have a old 70s set up it has a new retractable shower head and new tub faucet but the water cut on is a round stem u could say. So Now the hot works great but the cold doesn't it runs but slow.

Clogged line? Air lock? FOR THE GRAND FINALE! As I was trying to fix this issue the water stopped!! The pump wont cut on!

All Pressue is at 0 in home. Did the step by step check and will still not come on. Could a new pump go bad this quick? burnt up? Thanks for the help in the last post and thanks for all in this one who helps

(mod) said:

Thanks for the update Joshua.

It's no surprise that faucet strainers or toilet fill valves and shower heads would have been clogged, and usually an easy clean-up fix.

When hot pressure is good but cold flow rate is poor we can but guess that there is a clog at a pipe elbow or valve. It's not air lock as water pressure would force air through the lines and out at the nearest plumbing fixture.

Subseqent loss of all water pressure suggests further debris clogging. If your water source is silty even a new pressure swtich could become clogged rather quickly.

Josh ( Mountain Well Water) said: why is the well pump getting hot?

First of all I wanna say thanks for all the help. I redid a complete well pump with piping, pressure switch, pressure gauge, discharge tee with pressure indicator (Water tube from pump to tee). Replaced my 1970s shower/tub valve with a new one and all new fixtures.

After installation I did a pressure check for all faults and to check gauges for correct psi levels cut on and off with the 38 psi tank pressure and a 40/60 cut off. This was correct and works great. This morning I woke up and it was again fine.

Then I put on a load of laundry and after water cycled I was makin a bath for my children. the water pressure was giving out! I quickly ran to see the gauge in the basement near bladder tank and it was falling to 0.

The pump was VERY HOT at the pump house and it was doing the same but didn't go to 0 but stayed up about 0 due to the water pump pressure. I have several cut off valves thru the house One at pump house on line to the house. next is the one at the bladder tank.

next is at tee that goes to basement bedroom and rest of house. for the next one is at the water heater. lastly I have two on the cold and hot right under the bathroom which I installed just yesterday for further access and easier cut off for that room.

So in a nutshell i have all room with water I can cut off. I checked all of these to make sure no leak, or block was the problem.

So my question now is how come by pump is getting hot?

the pump house itself is about the size of a good size shed (Sorry don't have exact measurements) and the old pump didn't never just get hot. Now I did remove the pipe foam when installing this new pump. So the pipes are exposed but I do belive thats only for winter??? So what do i do? more air flow?

aim fan on pump? My well house has good installation in the wall I have a battery powered LED light and radio mounted in wall so its not to shabby and as for the rest is just ground and the well. So whats my options? New pump due to overheating? For adequate air flow? or ? thanks again!

(mod) said: Watch out: SHUT OFF THE PUMP

SHUT OFF THE PUMP if you have not already done so, so as to avoid burning it up.

If the well has lost prime the pump can run dry, hot, and may be damaged, thence losing the ability to pump water. I'm assuming this is a 1-line or 2-line jet pump.

I can't quite guess if the problem is the well running out of water (poor flow rate) or a piping leak, bad foot valve, loss of prime. I'd start by checking the pump to see if the pump housing is full of water or empty.

I'd also check the voltage being delivered to the pump (low voltage can cause trouble for some motors)

The fact that you've had previous debris problems could indicate

- low water in the well, poor flow rate, or a damaged, leaky well casing

- clogs at controls and switches

Josh said:

Thanks for all the help guys. Pump housing is full. Voltage is good. checked the new well seal and no leaks there or on pipe. discharge tee has what looks like leak but may be sweat from heat. its 90 where I am now and the building is probably about 100+.

the pump and water heater is turned off until i get i narrow it down more.

so with water in housing and voltage good where does that leave me? As before all the components from pump to well is new. Can i upload pics or videos? It might help.

(mod) said:

An electrician would at this point check the current draw of the pump for a clue about a motor problem causing high current causing overheating.

Josh said:

To begin with I wanna say this becoming a nuisance!! The old pump burned up, now my new pump died!

I got a new 1/2 hp this time. After the install it gave 20 psi to the house. so I checked the all the lines again under the well seal. Making sure to replace a already new but 3 month old foot valve. Making sure all connections was correct and leak proof.

After this put it all back together and did a re test. Now it's below 20 and the pressure is jumping The pressure switch isnt jumping but almost like not enough to get to pressure switch.

After cutting it off u can hear the water going back and forth. So Im back to no to VERY little pressure/water help? I did a measure depth test also. My well is 40 Ft with 33 foot of water leaving 7 foot from seal to top of water.

(mod) said: STOP just replacing pumps.

Certainly it's worse than a nuisance.

STOP just replacing pumps. It sounds as if there is either a control problem or the well is running out of water. You cannot allow a pump to keep running dry or it will be destroyed.

There are several approaches to protecting a pump from burn-up: a tailpiece in the well that recirculates water through the system for submersible pumps, or a pump protection switch that operates at the pump above ground.

A 33 foot static head in the well is about 150 gallons of water that can be pumped. After that quantity you are running on the flow-rate of water into the well. You may need to do a well flow test.

See

inspectapedia.com/plumbing/Pump_Protection_Switches.php

and see

inspectapedia.com/water/Well_Flow_Test.php

Josh( Mountain Well Water) FIXED! - Found that Water Pump was Bad

Thanks for all the help guys! The first pump was tested and had a mechanical malfunction.

The second one had a bad injector. The power to the well house was always turned off unless a test was being ran. Furthermore I was rewarded with a full refund on first pump and the second pump I was rewarded with exchange.

After this I decided to do a shallow well attempt instead of deep well.

I now have 1 pipe to the house (discharge tee placement) and a pipe from the pump( Injector On assembly) to well. After this I took off the additional pipes and have foot valve and cycle stop valve with control box installed,(3 way) 30\50 pressure switch, (on pump instead of hose line to switch) and the bladder tank at 28.5 psi.

After using the blue glue I made a final check of the 2 pipes and all connections and made my electric connections secure. I primed the pump and did a operation test. i did get to 10 psi on first attempt. After 82 gallons of priming water I can now say i FIXED IT and working GREAT :-) :-)!

Now I do have a question. Can I do a longer cycle? Example: 30 psi cut in/on and 55 psi cut out/off?? Now with all my issues fixed I would like to look out for "short cycling". I wanna say thank you to everyone for the help and a special thanks to DanJoeFriedMan for sticking in there with me! Hope to hear from you soon!

(mod)

Nice going, Josh and thanks for the follow-up.

You can get a longer pump on-cycle by

- installing a larger pressure tank

- spreading the cut-in and cut out pressures as you describe. Just don't set the cut-out higher than the pump can achieve, and when setting the cut-in down lower check that your building water pressure remains adequate on the upper floors.

30/55 is within the range of most pumps. You could even go to 20/50 or 20/55 if pressure is adequate at the low end.

...





ADVERTISEMENT





...

Continue reading at SHORT CYCLING WATER PUMP - topic home, the home page for this water pump topic, or select a topic from the closely-related articles below, or see the complete ARTICLE INDEX.

Or see these

Recommended Articles

Suggested citation for this web page

WATER PUMP SHORT CYCLING FAQs at InspectApedia.com - online encyclopedia of building & environmental inspection, testing, diagnosis, repair, & problem prevention advice.

Or see this

INDEX to RELATED ARTICLES: ARTICLE INDEX to WATER SUPPLY, PUMPS TANKS WELLS

Or use the SEARCH BOX found below to Ask a Question or Search InspectApedia

Ask a Question or Search InspectApedia

Share this article:

Search the InspectApedia website

Need to make a private comment? Email editor@inspectApedia.com. We welcome email with your website content critique, corrections, suggestions or questions. Email is monitored daily but our workload may prevent an immediate reply. For immediate results, we hope you'll first try asking your question using the search box just above.

Citations & References

In addition to any citations in the article above, a full list is available on request.



ADVERTISEMENT