Bottom tee and chimney and lower brace for the exhaust vent of a Cinderella incinerating toilet  - (C) Daniel Friedman at InspectApedia.comCinderella Incinerating Toilet Installation Details - CHIMNEY INSTALL Part 1

Here we provide photos and notes giving details of a successful installation of the Cinderella Incinerating Toilet.

This is article #5 of seven articles in this series.

The full list of seven is included in the Recommended Articles list at the end of this page.

This article series describes the brands, properties, installation, and maintenance of incinerating toilets - a waterless system for onsite waste disposal where a septic system cannot be installed.

InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers, products, or services discussed at this website.

- Daniel Friedman, Publisher/Editor/Author - See WHO ARE WE?





ADVERTISEMENT





Cinderella Incinerating Toilet Installation Details

Cinderella incinerating toilet installation manual: Model: Cinderella Comfort, electric - cited & discussed at InspectApedia.com

Above: the cover of the instruction manual for the Cinderella Comfort incinerating toilet.

The manufacturer provides excellent instruction manuals for the installation of each Cinderella incinerating toilet model. Be sure to obtain and read and follow those instructions.

Failure to do so could mean that your installation doesn't work properly or worse, that the installation is unsafe. Always start by reading the instructions.

[Click to enlarge any image]

In this article series we provide detailed photos and notes that expand on the manufacturer's instructions to show how we implemented them in a specific case.

These added "how to" details explain and illustrate exact details of every step in the installation of an incinerating toilet.

We include a few tricks of the trade that solve special problems such as how to mount a flat vent cover on a curved log exterior wall, and how to set up chimney sections to measure the correct lengths to which you should cut the material.

We also include details on adding additional chimney/vent bracing at the roof edge to solve what in our OPINION was a very wobbly and potentially problematic exterior vent installation.

Please visit CINDERELLA INCINERATING TOILET INSTALLATION - home for a complete list of all the steps included in the installation of a Cinderella incinerating toilet.

For ease of page loading and reading we have divided the entire incinerating toilet installation procedure into a series of web pages listed there.

If you prefer to have all of this information together in a single printable document simply download CINDERELLA TOILET INSTALLATION INSTRUCTIONS - ALL [PDF]

Article Contents

...

Install the Vertical Chimney Vent for the Cinderella Incinerating Toilet

The chimney vent material supplied by Cinderella uses standard 4-inch polypropylene soil and waste pipe produced by Uphonor, labeled as

UPHONOR Soil & Waste PP-MD 110x3 4 SN8 BD NPG PS102, Part No. 6414904015345 (bar coded). Our piping was date stamped as having been manufactured in 2018.

4-inch plastic pipe supplied with the Cinderella incinerating toilet installation kit  - (C) Daniel Friedman at InspectApedia.com

These pipe sections are assembled by simply pushing them together (if you're smart, aided with a bit of dish soap). Sections are sealed by a gasket that resides in a groove in the pipe hub.

Hub gasket for 4-inch plastic pipe used as chimney for a Cinderella incinerating toilet  - (C) Daniel Friedman at InspectApedia.com

Noticing that our pipe sections supplied by Cinderella must have been stored outdoors and exposed to the weather as the hubs were contaminated with dirt.

Out of concern that the pipe joints may not seal reliably, we removed each gasket and cleaned the gasket and the hub groove with a warm water and soap.

Cleaning the dirty gasket and hub to get a reliable pipe seal when assembling the vent for a Cinderella incinerating toilet  - (C) Daniel Friedman at InspectApedia.com

The cleaned hub and gasket are shown below.

Cleaned up plastic pipe hub ready for assembly and use in the Cinderella toilet chimney system  - (C) Daniel Friedman at InspectApedia.com

...

Cut a Close Nipple to Join the 45 degree Elbow to the Vertical Chimney

Below is one of two 45 degree angle double hubs needed for us to construct the chimney jog around the roof overhang.

To use this double-female elbow you'll need to cut off the hub from your angled and your final vertical pipe segments.

45 degree elbow used to extend the Cinderella incinerating toilet exhaust vent out past the roof edge  - (C) Daniel Friedman at InspectApedia.com

Above: one of our two 45 degree angled elbows needed to build the outdoor jog in the Cinderella exhaust vent as must pass the roof overhang.

Measuring to cut a close nipple of 4-inch plastic to add the 45 degree angle elbow to a Cinderella toilet vent  - (C) Daniel Friedman at InspectApedia.com

Because the elbow is provided with a female hub on both ends we needed to cut a short length of vent pipe to join the elbow to the upturned hub of the vertical exhaust vent pipe extending up from the bottom tee outside the building wall.

Here we cut and test fitted our 4" pipe length that permits joining two female pipe hubs. Note in the photo below that if we want 4" of additional space we make the pipe length longer than that to allow for the length of pipe that slips into each of the two hubs.

In our photo we hadn't yet used our rasp file to clean off the second pipe end edges.

Preparing a close nipple of 4-inch plastic to add the 45 degree angle elbow to a Cinderella toilet vent  - (C) Daniel Friedman at InspectApedia.com

Below our cleaned up pipe "nipple" cut to joint the first 45 degree angle elbow to the hub at the top of our vertical chimney section.

Close nipple now ready for use to assemble the 45 degree elbow to the straight section of Cinderella toilet vent - (C) Daniel Friedman at InspectApedia.com

Below: I've put some dish soap solution on the edges of our 4" nipple to make it easier to slip it into the pipe hubs.

Soap on the close nipple helps assemble plastic chimney parts for the Cinderella toilet  - (C) Daniel Friedman at InspectApedia.com

Below is the lower end of our first vertical chimney pipe section inserted into the upper opening of the pipe tee provided in Cinderella's installation kit.

The bottom of the tee will receive a removable cover that is taken off to permit future chimney vent cleanouts.

Bottom tee and chimney and lower brace for the exhaust vent of a Cinderella incinerating toilet  - (C) Daniel Friedman at InspectApedia.com

Below: here is the first vertical chimney vent section installed, hub-up, into the exhaust tee.

The bottom cover that seals that tee has a small hole for drainage, should moisture get inside of the exhaust vent. You'll want to be able to remove that cover for periodic chimney inspection and cleaning.

Cinderella incinerating toilet exhaust vent lower section installation complete  - (C) Daniel Friedman at InspectApedia.com

Below: this photo shows that our 4-inch nipple has been inserted into the 45 degree elbow and I'm about to insert the other end of the nipple into the upturned hub of the vertical chimney section.

Installing the lower 45 degree elbow to extend our incinerating toilet vent out past the roof edge  - (C) Daniel Friedman at InspectApedia.com

Below: the elbow has been connected to the upturned hub of the vertical chimney exhaust pipe and the second of several support clamps has been snugged to the building wall.

Lower incinerating toilet exhaust vent (chimney) ready to install angled extension to clear the roof edge / eaves / soffit  - (C) Daniel Friedman at InspectApedia.com

...

Build the Angled Chimney Extension Around the Roof Edge

Now we are ready to insert, measure, and cut the angled length of chimney-vent to get our remaining chimney installation clear of the roof overhang.

Below: we have installed the angled run of chimney pipe and are ready to measure the cut point below that uppermost hub.

We'll cut the angled pipe to a length that gives us the desired distance from the roof edge to our final vertical chimney section.

Pythagorean theorem allows us to calculate the length of any side of a right triangle  - (C) Daniel Friedman at InspectApedia.com

To calculate the necessary length of our diagonal pipe length we can use the simple formula for a right triangle shown below.

Remember to include in your length the amount by which the pipe will extend into the interior of the 45-degree angle hubs.

Or, by making the required measurements with the pipe already inserted into the lower 45 degree elbow in the photo above, when we measure (or calculate) the length C that is needed, we need only include the extra length of pipe that extends into the upper 45 degree elbow hub since the lower elbow already has the pipe inserted.

Just mark the upper pipe length cut location (green line in our photo).

Pythagorean theorem allows us to calculate the length of any side of a right triangle - cited & discussed at InspectApedia.com

Knowing any two lengths of a right triangle's sides A, B, and C you can calculate the length of the remaining side using the Pythagorean theorem: C2 = A2 + B2

If you've forgotten how to calculate a square and square root of a number you can use a calculator or an online calculating website.

Cinderella exhaust vent chimney during installation  - (C) Daniel Friedman at InspectApedia.com

Above: We chose to space our chimney around the soffit's fascia at plenty of distance to avoid damage from snow sliding off of the roof and to give room for the supporting chimney bracket.

Measure the total length of the angled or sloped section of the Cinderella chimney to be sure it is within limits  - (C) Daniel Friedman at InspectApedia.com

Above: we test-assembled the angled pipe run on the ground and checked our measurements of both the total assembly length (photo above) and the straight cut pipe length with its upper hub already removed (photo below).

Note that these are the measurements we needed for the particular roof and soffit overhang dimensions shown in this article. The dimensions you'll need will almost certainly differ.

Easiest, with no calculations at all, is to simply test-assemble the pipe as we showed above on this page, then mark the cut line on the pipe as a point level with the lower edge of the roof.

Watch out: Cinderella warns about two angle options for this sloped section of chimney pipe

  • If the angled section is using 30 degree elbows and slope, the total length of the angled section must not be longer than 5 ft. (1.5m)
  • If the angled section is using 45 degree elbows (illustrated here), the total length of the angled section must not be more than 3 ft. 4 in. (1.0m)

Below, the straight length between hubs in our installation was 15 1/2" and the total straight length of this angled section was about 18" - well within the Cinderella's limits.

Measure the total length of the angled or sloped section of the Cinderella chimney to be sure it is within limits  - (C) Daniel Friedman at InspectApedia.com

Below: our two 45 degree angle pipe hubs and straight length of chimney vent pipe between them brings the opening of the upper hub level with the lower edge of our roof, and at the distance we wanted our chimney to be spaced out horizontally from the fascia board.

In this installation the distance of the lower vertical chimney pipe from the building was set by the horizontal vent pipe that comes through the building wall and the tee attached to its end.

That put our lower vertical pipe at about the middle of the two-foot wide soffit or roof overhang.

Cinderella vent angle extension complete, ready to add final vertical chimney length  - (C) Daniel Friedman at InspectApedia.com

For the upper section of our chimney to jog around and clear the soffit and then continue vertically we measured and cut the length of the angled pipe run as described above.

 


Please continue reading the next article in this series on installing a Cinderella incinerating toilet - the link is just below.

© 2023 InspectApedia.com

...

Continue reading  at CINDERELLA INCINERATING TOILET INSTALLATION - CHIMNEY INSTALL Part 2 or select a topic from the closely-related articles below, or see the complete ARTICLE INDEX.

Or see these

Recommended Articles

Suggested citation for this web page

CINDERELLA INCINERATING TOILET INSTALLATION - CHIMNEY INSTALL Part 1 - at InspectApedia.com - online encyclopedia of building & environmental inspection, testing, diagnosis, repair, & problem prevention advice.

Or see this

INDEX to RELATED ARTICLES: ARTICLE INDEX to TOILET INFORMATION

Or use the SEARCH BOX found below to Ask a Question or Search InspectApedia

Ask a Question or Search InspectApedia

Share this article:

Questions, answers, FAQs, and reader comments about incinerating toilets.

Search the InspectApedia website

Need to make a private comment? Email editor@inspectApedia.com. We welcome email with your website content critique, corrections, suggestions or questions. Email is monitored daily but our workload may prevent an immediate reply. For immediate results, we hope you'll first try asking your question using the search box just above.

Citations & References

In addition to any citations in the article above, a full list is available on request.



ADVERTISEMENT