Building Inspection, Diagnosis & Repair Info

Steam vent on a radiator (C) Daniel FriedmanSteam Vent Types & Selection

  • POST a QUESTION or COMMENT about steam vent selection and installation; guides to steam vent models, features, choices, applications, manufacturers, sources

Steam vent types:

Two-pipe steam heat vents vs one-pipe steam heat vents: this article describes the different types of vents used on two pipe and one pipe steam heating systems and explains why a 2 pipe steam heat system will generally require different vents at different locations from a 1 pipe system.

InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers, products, or services discussed at this website.

- Daniel Friedman, Publisher/Editor/Author - See WHO ARE WE?





ADVERTISEMENT





Steam Vent Types, Applications, Choices & Selections

Adjustable steam vent helps regulate heat output (C) Daniel Friedman

Here is the top of an adjustable steam vent showinbg an adjustment slot and vent rate markings on the edge of the device. You can see "2 SLOW".

By turning the top with a flat bladed screwdriver you are adjusting between fast and slow: you can regulate how quickly this steam radiator gets hot.

Steam radiator vents are found principally on one pipe steam heat radiators.

Here we discuss the requirements, installation, and troubleshooting of steam vents on radiators as well as other steam vents found on steam piping and at other locations in steam heating systems for both one pipe and two pipe steam systems

Watch out: If the radiator continually makes noises (whistling or wheezing) at the steam vent, there is a problem that needs to be fixed: a bad steam vent, steam piping problem, steam pressure set too high, or boiler oversized for the heating distribution system.

Watch out: Be sure your steam heating system and its controls are properly adjusted - excessive steam pressure can be dangerous.

[Click to enlarge any image]

Which Type of Steam Vent Should I Install?

Basically steam heating system heat up radiators by sending steam up riser pipes into the radiators. Vents at different locations depending on the steam heating system type (1-pipe vs. 2 pipe) let air out of the steam pipes and/or radiators so that steam can enter those heating devices.

1-pipe steam heat radiator control & vent (C) InspectApedia.com & Carson Dunlop Associates

In a one pipe system just one pipe feeds each steam heat radiator, as in the photo we show above, courtesy of Carson Dunlop Associates. As steam enters the radiator, air escapes at a radiator-mounted steam vent.

If your heating system is a 1-pipe steam heat system

see ONE PIPE STEAM HEAT VENTING - summarized just below

In a two pipe steam heat system two pipes are found connected at each steam heat radiator. Steam enters the radiator through one pipe and air and condensate exit at the other through a special steam trap or control as illustrated below.

Thermostatic traps on two pipe steam heat radiators (C) Carson Dunlop Associates at InspectApedia.com

Carson Dunlop Associates is a home inspection, report writing tool & education company in Toronto. (C) Illustrations used with permission.

If your heating system is a 2-pipe steam heat system

see STEAM VENTS, 2-PIPE SYSTEMS - described further below

We also provide a separate

STEAM VENT TABLE, CROSS REFERENCE & SOURCES

Air Vents on 1-Pipe Steam Radiators

Steam radiator (C) Daniel Friedman

Above our photo illustrates a 1 pipe steam system with a typical radiator vent.

Details about 1 pipe steam heat radiator venting are

at RADIATOR STEAM VENTS, 1-PIPE SYSTEMS. Just below on this page is a brief summary:

Vent-Rite No. 11 Steam Vent - Vent-Rite Valve Corp. & InspectApedia.com

Shown above: a Vent-Rite # 11 steam vent intended for 1 pipe steam systems.

  • Float-type steam vents:

    an water+alcohol filled float inside the steam vent heats, rises, and closes the vent as the radiator heats. The float also rises to prevent water from spitting out of the vent should condensate rise inside the radiator or vent.

    On FLOAT-TYPE STEAM VENTS (as well as most others) rust or sediment can clog the float vent opening and interfere with its proper operation. Excessive steam pressure can also prevent the vent from operating properly.

    The Vent-Rite #1 (or #11) shown above is designed for 1-pipe steam systems and mounts on the radiator. The company describes their #1 vent as providing ... quick, uniform distribution of heat to all radiation ...

    This requires balancing the radiation by controlled venting.
    Vent-Rite #1 Non-Vacuum vents are adjustable and all vents are designed for positive action and straight-line venting. They function automatically to vent the air. If, through an unusual condition the vent is filed with water, the vent port automatically closes.

    The Vent-Rite #1 Air Elimination Valve VentRite No 1 for Steam Radiators ... has been designed to eliminate air in any one pipe steam radiator system as quickly as possible to assure rapid ad efficient heating.

    It will open and close all pressures up to 3 PSI Do not use at system pressure above 10 PsI This air valve is easily installed its [sic] standard 1/8" male connection makes it interchangeable with practically any other valve. It is fully adjustable, enabling the user to balance a system with a minimum of effort.

    Use for free standing radiators,
    one pipe steam radiator system. (Adjustable angle vent).
  • Adjustable steam vents

    operate similarly to the float-type steam vents described above, but add the feature

    of ADJUSTABLE AIR VENTS allow varying the air vent opening size so that the air venting rate can be better matched to the radiator size. (Larger steam radiators need a larger air vent opening.)

    Examples of adjustable steam vents include: Hoffman Model 1A (Part No. 401422) adjustable air valve with 6 settings (1-slow to 6-fast venting); VariValve® Quick-Vent. Those vents are designed for traditional steam radiators. If your steam heat is by a steam convector unit, different steam vents are required, such as the Hoffman Specialty Model 1B (Part No. 401425).
  • Adjustable-Thermostatically-operated steam vents

    ADJUSTABLE THERMOSTATICALLY OPERATED include an adjustable room temperature thermostat that allows the occupant to set the desired room temperature.

    Setting this thermostatically operated steam vent control actually adjusts the rate at which the vent permits air to escape from the individual radiator, similar to the adjustable steam vents described above, but in this case once the thermostat is set, the automatically regulating steam vent is responding to the room temperature setting.

...

Vents for 2-Pipe Steam Radiator Systems

Steam radiator with Hoffman valve steam trap (C) Daniel Friedman at InspectApedia.com

A two pipe steam system carries steam up and condensate back in different pipes, using a thermostatic trap at the end of each radiator to discharge both air and water from the radiator.

Our photo shows a 2-pipe steam heat radiator; one pipe feeds steam at the top right end of the radiator, controlled by a thermostatically operated inlet valve, while at the left side of the radiator at its bottom condensate returns to the boiler through a Hoffman steam trap.

Simple texts like Weil McLain's study course simply state

Do not use air vents on two pipe steam heat systems" Instead yo use float and thermostatic (F&T) traps at the end of the system main. These are fast-acting traps that allow both air and condensate out of the system main.

The Vent-Rite #35,75, or 77 are intended for main vents (two pipe systems and located on the mains); The Vent-Rite #31 & 33 are used on steam risers and on steam convectors. Contact the company for help or to download their product guide.

The Honeywell Braukmann V110F, for example, is used on both hot water and two-pipe steam systems to provide individual radiator heat control (by thermostatic operation).

Some two pipe steam systems also include a vacuum breaker in the mains.

That device allows air into the system when the system cools down after the boiler has shut off.

Curved two pipe steam radiator with steam trap at Ellis Island NY (C) Daniel Friedman at InspectApedia.com

Above is an unusual curved two pipe steam radiator at which both connections are at the radiator's bottom, inlet at the right, outlet at the left.

A thermoststatic control valve at the radiator's right end (white knob) controls the steam input into the radiator - closeup below:

Thermostatic inlet valve controlling a steam heat radiator at Ellis Island NY (C) Daniel Friedman at InspectApedia.com

A Hoffman steam trap a 2-pipe steam radiator's outlet end (photo below) allows condensate to return to the steam boiler.

Hoffman steam trap (C) Daniel Friedman

Details about steam traps are

at STEAM TRAPS

Are There Air Vents for 2-Pipe Steam Heating Systems?

In a two pipe system air escapes via the Hoffman steam trap (photograph above) or similar device at the radiator base (on the condensate return side of the radiator), as well as from vents along the main piping (photo below).

While you won't see steam vents on two-pipe steam heat radiators, there may indeed be different models of air vents on the main steam pipe risers in the 2-pipe steam heating system in your building.

Simple texts like Weil McLain's study course simply state

Do not use air vents on two pipe steam heat systems" Instead you use float and thermostatic (F&T) traps at the end of the system main. These are fast-acting traps that allow both air and condensate out of the system main.

Steam vent on steam piping (C) Daniel Friedman

Other Main Vents, Hoffman Steam Traps & Vacuum Breakers Used on 2-Pipe Steam Heating Systems

Vent-Rite Steam Vents for 2-Pipe Systems

Vent-Rite No. 35 Steam Vent - Vent-Rite Valve Corp. & InspectApedia.com

  • Vent-Rite Valve Corporation: 1875 Dewey Ave. Benton Harbor, MI 49022 TEL: (269) 925-8818 FAX: (269) 925-7888. Vent-rite advises: For venting basement mains use the Vent-Rite 35, 75, or 77 air valve or an equivalent from another manufacturer.
  • The Vent-Rite #31 & 33 are used on steam risers and on steam convectors.
  • The Vent-Rite #35 (shown at left), Vent-Rite No. 75, or Vent-Rite steam vent No. 77 are intended for main vents (two pipe systems and located on the mains). The Vent-Rite No. 35 shown in our photo is distributed on EBay by Barnes & Jones, Inc.

You will probably also find a Hoffman trap at the two pipe steam radiator outlet (below left) and one or more main steam line vents (photo below right).

Some two pipe steam systems also include a vacuum breaker in the main as well. That device allows air into the system when the system cools down after the boiler has shut off.

Basically, to work at all, steam systems have to let air in and out of the piping system. Air enters when the system cools (the burner is off) and air is forced out by rising steam when the system heats (burner is on and making steam).

Rising steam works with air vents to allow steam into and air out of radiators during the heating phase. During the cooling phase air enters the system at vacuum breaking vents, air vents, and possibly at valve stems and other locations.

Honeywell Braukmann automatic valves on steam systems?

Honeywell Braukmann EA122A heating vent (C) InspectApedia

The Braukmann automatic valve you cite as present on your system is a Honeywell product, though I don't know which product you found installed.

The Honeywell Braukmann EA122A1002 Automatic Air Vent shown above (if that's what you've got) is intended to vent air from high pressure mains and equipment in hot or cold water systems - this is a hydronic systems valve not a steam vent.

However we might find a hydronic (hot water heat) system air vent installed on a steam system in which a lower floor in the building is being heated by hot water from the boiler rather than by steam.

The company does produce thermostatic radiator valves that might be found on a steam or hot water heating system and also a Honeywell V2042HSL10 steam radiator valve used on one pipe steam systems and shown just below.

One pipe steam radiator valve Honeywell V2043HSL (C) InspectApedia & Honeywell

If yours is a two pipe steam system I would not expect you to find this valve installed.

If you can give me a photo or identifying markings I will explain further; most likely it's there to purge air from the steam main. Quoting:

Continuing: Mike, I suspect that the old vent you removed was a mistake from the get go; it might have worked, somewhat, as it's a versatile valve, but that's not what the literature says works properly.

The Braukmann auto valve is a Honeywell product; if you can give me a photo or identifying markings on your Honeywell Braukmann I will explain further; most likely it's there to vent the steam main.

Or if you are talking about a radiator valve, the Honeywell Braukmann V110F, for example, is used on both hot water and two-pipe steam systems to provide individual radiator heat control (by thermostatic operation).

Contact

  • Vent-Rite Valve Corporation: 1875 Dewey Ave. Benton Harbor, MI 49022 TEL: (269) 925-8818
  • Emerson Swan, Inc., 300 Pond Street, Randolph, MA 02368, Tel: (781) 986-2000 Fax: (781) 986-2028, info@emersonswan.com - Emerson Swan is a nationally recognized, stocking manufacturer’s representative organization serving the northeastern United States and the Greater Toronto Area.

For steam vent troubleshooting also see STEAM VENTS where we discuss other steam vent problems such as cold radiators, banging pipes, noisy radiators, steam vents that spitting water, clogging steam vents, and steam vent replacement.

...

Summary of Types of Steam Vents on 1 & 2 Pipe Steam Systems

The Table of Non-Vacuum Vents & Their Applications & Substitution Part Numbers

and the

Steam Vent Cross Reference / Substitution Chart are now

at STEAM VENT TABLE & CROSS REFERENCES

 

...




ADVERTISEMENT





Reader Comments, Questions & Answers About The Article Above

Below you will find questions and answers previously posted on this page at its page bottom reader comment box.

Reader Q&A - also see RECOMMENDED ARTICLES & FAQs

On 2020-02-27 by Anonymous - What is the difference between Hoffman No. 40 or No. 41 steam vent?

What is the diference between 40 or 41 valve

On 2020-02-28 - by (mod) - Mounting location difference between the Hoffman No. 40 and Hoffman No. 41 Steam Vents?

Hoffman No. 41 steam vent cited & discussed at InspectApedia.comAnon:

Both the No. 40 and No. 41 are steam vents found on the steam distribution system such as radiators and convectors. The main difference is in how each vent is mounted and thus where it is intended for use.

  • The Hoffman No. 41 is a steam vent that mounts vertically and is normally used on convector steam heaters.
  • The Hoffman No. 40 is a steam vent that mounts with a right-angle fitting normally found on the side of steam radiators.

Hoffman No. 41 Steam Vent details

Hoffman Model 41 Part No. 401455, 1/8" Straight Steam Convector Air Valve (Non-vacuum)

Telescopic siphon tube with angle cut assures drainage

1/8" NPT straight shank

Maximum operating pressure 6 psig (0.4 bar)

Drop away pressure - maximum pressure against which the vent can open

Maximum pressure 10 psig (0.7 bar)

Shown above is the Hoffman NO. 41 steam vent

Hoffman No. 40 Steam Vent Details

Hoffman No 40 steam vent cited & discussed at InspectApedia.com

Hoffman Steam Air Vent 40, 1/8" Angle Steam Radiator Air Valve 401440

Air Valve (non-vacuum)

Float-type vent

Single non-adjustable port

1/8" NPT angle connection

Maximum operating pressure 6 psig (0.4 bar)
This vent is shown just above

Also see this Hoffman Steam Vent Selection Guide from p. 133 of the Hoffman Specialty General Catalog HS-900G available from Hoffman or at this website https://inspectapedia.com/heat/Hoffman-Specialty-Catalog-HS-900G.pdf

[Click to enlarge any image]

Hoffman steam vent selection guide at InspectApedia.com

Also see the companion Hoffman Specialty Service Parts Catalog and contact information for Hoffman given in the article above on this page.

On 2020-02-02 by Mary - How do I adjust a Dole steam vent?

Almost all my radiators have Dole adjustable steam vents like the one you have pictured below the headline "Steam Vent Types, Applications etc." This winter my bedroom radiator has decided not to work.

How do I adjust the steam vent? I've never had a problem with my radiators before so I want to make certain I do this correctly.

On 2020-02-02 - by (mod) - Dole type steam vent operation & adjustment

Mary the Dole type steam vent in our photo has a slot on the vent top that permits use of a thin coin or a wide-bladed screwdriver to turn the top adjustment to a setting between "1 = slow" and "10 = fast" - setting to a higher number will vent air faster and the steam radiator should heat more-rapidly.

However if your steam vent isn't venting at all it may need to be replaced.

Watch out: I do not recommend even trying to replace the steam vent unless

1. the steam radiator control knob can be closed - and has been set to its closed (clockwise) position

or

2. the building's steam heat is OFF and will be left off long enough to unscrew the old and screw in the new steam vent

and

3. you have a replacement steam vent at hand, ready to install

My concern is that if the building steam is "up" and you remove the vent entirely you can get scalded by steam blowing out of the steam vent mounting opening.

On 2017-11-24 by Trn - here is a report on flow tests done for steam vents

For everybody who wants to figure out settings across brands of vents, look for an online PDF by Gerry Gill and Steve Pajek.

They did flow rate tests and they have a chart that tells you exactly what each setting does in cubic feet per minute so you can compare with a different manufacturer.

On 2017-11-25 by (mod) - flow rate in CFM of air or air/steam mix being vented from specific steam vents

Thanks TRN, for taking the time to add the suggestion about steam venting data provided by Gill and Pajek.

Readers will want to note that the flow rate in CFM of air or air/steam mix being vented from specific steam vents at individual radiators in their homes will vary from both theory and from the factory numbers for specific models of steam vents for a number of reasons such as the exact pressure in their particular team system, piping restrictions, formation of scale in the steam vent, etc.

In the field the truth of these variables in actual installed steam system sufficiently nettlesome that most installers use simple rules of thumb or simply buy and install steam vents with which they're familiar, perhaps changing out to a larger or smaller steam vent or an adjustable steam vent when they get complaints about individual rooms or radiators that are too hot, too cold, or too slow to warm up.

If whole areas of a building are heating too quickly or too slowly, the steam technician will be looking first not at individual steam radiator vents but at vents on the vertical main steam risers.

Still Gill and Pajek's 2005 study, commented-on by Dan Holohan (Mr. Steam), can be helpful if you are having trouble balancing the heat output from a steam system (across different steam radiators or in different rooms or areas in a building).

You can find their paper currently at Dan Holohan's website:at heatinghelp.com/assets/documents/Balancing-Steam-Systems-Using-a-Vent-Capacity-Chart-1.pdf

On 2016-10-26 by Wayne - what's the best replacement Steam Vent?

I need to replace an 85 year old Hoffman No 16 vent valve on my home steam main (one of 4). The No 16 was for a vacuum system but my system is no longer operated as a vacuum system. A simple 1 pipe low pressure system. I have tried a Dole No 13 and it spouts water when the heat comes up in the AM. What is the best, American made replacement?

On 2015-11-25 by ed levy - what replacement steam vent should I buy?

hi there. quick question. i manage a 15 unit apartment building, 5 story. oil burner. approximately 4 small radiators per apartment. single pipe system ( i believe). my super is installing "maid-o-mist" â…›" #4 vents on the radiators. there are 7 risers (on the top floor). what type vent and size vent should be installed there?
thanks
edmond

Moderator reply: choose the steam vent based on the radiator size, vent capacity, and need for adjustability

Above on this page we outline types of steam vents that depend on your need, and we give links to sources of the most popular steam vent brands and models and free PDF downloads. Each manufacturer will also have steam vent model recommendation charts, in those PDFs that you can match to your system and radiators.

But really the easiest way to choose a replacement steam vent is to buy the same type and model that was installed originally. I think that the original steam system installer has already done the analysis to choose the best vent in size or capacity.

The reason you might change from that original steam vent would be the need for added function such as thermostatic control - where you're getting too much heat in some areas and not enough in others.

On 2015-11-19 by Ed - Hoffman No.30 boiler return trap with no water in sight glass.

Have a Hoffman no.30 boiler return trap with no water in sight glass.

On 2015-11-19 by (mod) - trouble with no water in boiler

Ed

The problem could be the sight glass itself, but

Watch out: to avoid destroying the boiler I would SHUT THE BOILER OFF IMMEDIATELY

then you will want to investigate further. Failure of return of condensate to the steam boiler is usually a condensate return line or condensate trap clog issue.

See also SIGHT GLASS, STEAM BOILER

and LOW WATER CUTOFF VALVE, BOILER - to protect your boiler if in fact it doesn't have enough water to prevent an explosion or damage

On 2014-12-02 by Anbu Mahesh - is a vent mandatory on steam equipment?

In a steam condenser, vent is mandatory or not?

If vent is not provided, what will be problems occured during operation.

On 2014-12-02 by (mod) -

Anbu

If your radiators are unvented, particularly in a 1 pipe steam system designed to use steam vents, the result of no vents will be:

No heat

But as you'll read in this article series, some two pipe steam system radiators use other controls and won't have a steam vent.

 


...

Continue reading at STEAM VENTS, 1-PIPE SYSTEMS where we describe just about every type of automatic steam vent used on residential and most commercial systems. or select a topic from the closely-related articles below, or see the complete ARTICLE INDEX.

Or see these

Recommended Articles

Suggested citation for this web page

STEAM VENT TYPES, SELECTION at InspectApedia.com - online encyclopedia of building & environmental inspection, testing, diagnosis, repair, & problem prevention advice.

Or see this

INDEX to RELATED ARTICLES: ARTICLE INDEX to STEAM BOILERS

Or use the SEARCH BOX found below to Ask a Question or Search InspectApedia

Ask a Question or Search InspectApedia

Share this article:

Search the InspectApedia website

Need to make a private comment? Email editor@inspectApedia.com. We welcome email with your website content critique, corrections, suggestions or questions. Email is monitored daily but our workload may prevent an immediate reply. For immediate results, we hope you'll first try asking your question using the search box just above.

Citations & References

In addition to any citations in the article above, a full list is available on request.



ADVERTISEMENT