Heating Boiler Gauges
Heating boiler gauges: this article describes the combination pressure & temperature gauge found on most hydronic (hot water) heating systems. We also illustrate pressure gauges found on low pressure steam system boilers.
For both hot water heat and steam heat, the boiler gauge gives helpful temperature or pressure readings that tell us if the boiler is operating normally.
The same pressure and temperature readings at a boiler can help diagnose problems such as TP valve leaks, cold radiators, and even boiler or heating system piping leaks. We give normal heating boiler pressure and temperature numbers and we explain what variations from these data signify.
Watch out: The heating boiler gauge we show abve reads a temperature of 205 degF. If this is a conventional residential hot water heating system, this boiler is running too hot and if the relief valve is not spilling the boiler may be unsafe. I would turn this boiler off and call for repair.
InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers, products, or services discussed at this website.
- Daniel Friedman, Publisher/Editor/Author - See WHO ARE WE?
Here we describe both steam heating boiler pressure gauges and pressure readings, and hot water heating pressure and temperature gauges.
At page top and just above we show a typical hot water (hydronic) boiler pressure gauge and its location on the front of the boiler.
At left we show a common hot water heating boiler gauge location, on the front of the boiler near the boiler top.
The temperature/pressure gauge may help in checking for normal conditions before and during boiler operation.
Typical pressure for a hot water (hydronic) residential heating boiler serving a two story home would show 12 psi cold, and less than 30 psi hot.
Typical operating temperature settings on a boiler call for a Low temperature (boiler cut-in) between 120 and 160 °F.
Typical operating temperatures on a hydronic boiler call for a high temperature (boiler cuts off) of 180-200 °F.
Over 200 degrees F. we're at risk of spilling at the pressure temperature relief valve.
Typical operating temperature observed at the gauge will be below the high limit, and can be as low as nighttime room temperature in non-heating season if no tankless coil is in use.
However the boiler pressure or temperature gauge can be wrong! The gauge may be stuck and so may not always tell us what's going on.
The boiler pressure/temperature gauge above shows a pressure of about 17 psi and a temperature of 185 degF. These are normal readings for a residential hot water heating boiler that is or has been running and is still hot.
On a residential heating boiler the automatic water-feeder/pressure reducing valve that automatically provides makeup water to the heating boiler if pressure drops below 12 psi. So 12 psi is the typical "cold" pressure for residential boilers.
If your building is taller than two floors, the installer may have needed to boost the starting "cold" water pressure for your boiler to overcome the hot water distribution piping head pressure - otherwise your heating circulators may not be able to circulate hot water.
At PUMP, WATER PRESSURE BOOSTING
we explain the relationship between building height and water pressure, and we illustrate the water pressure decrease in building water supply piping with building height.
But a look at the basement water pressures in this illustration also explains the pressures that a basement located hot water heating circulator pump has to overcome.
Watch out: If we set the boiler high-limit much over 210, on many residential systems the system pressure will exceed 30 psi and we'll see water leaking from the pressure/temperature relief valve - ultimately an unsafe condition.

Typical pressure for a residential boiler serving a two story home would show 12 psi cold, and less than 30 psi hot. Over 30 psi boiler pressure will cause the pressure relief valve to open.
Typical operating temperature observed at the gauge will be below the high, and can be as low as
nighttime room temperature in non-heating season if no tankless coil is in use. The temperature/pressure gauge may help in checking for
normal conditions before and during boiler operation. However the gauge can be wrong!)
Watch out: Above our photo shows that the boiler pressure is at 15 psi - which is perfectly fine, but the boiler temperature is at 205 degF - this is abnormally high.
On a conventional residential hot water heating boiler we'd expect the temperature/pressure relief valve to open and spill hot water at this temperature as it's over 200 degF.
So either our gauge is inaccurate (perhaps its stuck), or the system is not operating normally and service is needed.
Try this first: Before calling for repair I would give this gauge a nice rap with my knuckle. If the gauge temperature or pressure needles jump to a new position, I suspect that the gauge is sticking and needs repar.
Don't confuse gauges, pressures, and temperatures found on hot water (hydronic) heating systems with those found on a residential steam heating boiler like the one whose gauge and pressure control we show below.
Because residential steam boilers, also usually "low pressure steam boilers" operate around the 0.1 to 0.5 psi range, the pressure reading you'll see on a typical steam boiler will be quite close to the zero mark.
Larger and commercial steam boilers might operate at much higher pressures.
Details about steam boiler pressures, gauges, and controls are
...
Below you will find questions and answers previously posted on this page at its page bottom reader comment box.
...
I can't find where the furnace temperature control is. The temperature is 210* I want to lower it to around 180* its an older Sentry Slant /fin model number S-120 DP ?
Any advice would be appreciated. Thank you On 2020-12-12 by Mark
by (mod) - Here is where you set your boiler temperatures
Mark:
The aquastat that controls temperatures on a typical Sentry Slant/Fin S-120, like the model we show below, is the gray box shown at upper right in the image (Yellow Arrow in my image).
Watch out: 210 deg F is too high and risks spilling at the temperature-relief valve: a condition that can make the boiler unsafe.
See AQUASTAT HI LO DIFF SETTINGS
It seems like the temperature on my Crown boiler is ok, but the PSI seems high. We only have our thermostat set to 66 degrees and the house is cold. Is there something we can do to help decrease the psi? Do we need to call a repair person? - On 2022-12-26 by Vanessa
by InspectApedia Publisher -
@Vanessa,
Your pressure gauge is sitting right at 30 psi.
1. IF you do NOT see spilling at the temperature-relief valve then that's good news - this isn't an emergency.
2. IF you took that photo when the boiler was up to full operating temperature, then that's "normal" pressure - considering that these gauges are not precise - not lab-grade instruments.
You can gently TAP on the pressure/temperature gauge - gently, as we don't want to break it - and see if the needles move.
3. Normal boiler pressures for a residential hot water heating boiler in a typical 2-story home are- 12 psi when the boiler is cold
- just under 30 psi when the boiler is at its hottest
Check the HI setting on the boiler aquastat - it should be set to 200 degF or a bit lower - often a tech will leave it at 180F.
Details are at
AQUASTAT HI LO DIFF SETTINGSWatch out: but if you DO see spilling at the temperature-pressure relief valve then the system is unsafe and should be turned off immediately; then call for repair service.
Let me know if you've got another concern like leaks at the temperature/pressure relief valve.
Good morning, I have an old Kool-Base hot water boiler that is reading 12psi cold, and no temperature at all.
Pilot like is lit, thermostat is on 85 degrees, and can not get furnace to kick on.
It is so old, I'm not even sure I can locate the ignitor?
Is it right next to the pilot light? On 2021-11-02 by Jerry H
by (mod) - diagnostic suggestions
@Jerry H,
If it's an old boiler it may use a standing pilot that is normally always lit and not an igniter.
If you can't keep the pilot light lit, the problem may be a bad thermocouple.See THERMOCOUPLE REPAIR / REPLACEMENT
If the pilot light is on and your thermostat calls for heat, then the boiler's gas valve should open and the burner ignite.
See the diagnostic steps starting at
DIAGNOSE & FIX HEATING PROBLEMS-BOILER
My "typical" 2-story residential home's hydronic boiler system (Weil McLain, 10 years old) is at a 12 psi resting state when cold (good), and as the boiler runs and the temperature goes up so does the pressure in these increments: 21 psi at 160 degrees, 23 psi at 170 degrees, 24 psi at 175 degrees.
Is that ok? This is after I replaced the expansion tank this morning. This is better than it was.
Prior to my replacing the expansion tank this morning, the psi had been increasing at a faster rate (and nearly reaching 30 psi).
E.g. 25 psi at 160 degrees, and around 28-29 psi at 170-175 degrees at which point I shut boiler off because I did not want to exceed 30 psi and blow the relief valve.
Also, importantly, I believe I have RULED OUT the possibility of a leaky combination "pressure reducing valve/backflow preventer" because in an earlier test when I turned off the water line completely that feeds the autofill/backflow (ie. zero water could be added) I STILL had that faster pressure increased I'd just mentioned.
At this point, I'm hoping I'm OK with the first incremental changes in pressure I mentioned at the beginning of this post.
Does it sound OK or normal, or should I be able to get up to 180 degrees but only be at 20-22psi? I want to know if 24psi for 174 degrees is normal.
Finally, I am not sure if my boiler would shut off at 180 degrees on its own, or some higher number. I don't know what else could cause higher-than-ideal psi in my system at the temperatures I've mentioned. Any thoughts would be hugely appreciated. On 2022-02-28
by MikeB
by Inspectapedia Com Moderator - failed expansion tank can cause abnormally high pressures
@MikeB,
As long as the pressure is under 30 psi - 28psi is typical - when the boiler is at its highest temperature (somewhere below 200 degF) your residential hydronic boiler system is working normally.
I agree that a failed expansion tank can cause abnormally high pressures and once you exceed 30 psi, the relief valve should spillPlease take a look at
AQUASTAT HI LO DIFF SETTINGSby Mike
@Inspectapedia Com Moderator,
Thanks! I will definitely read that aquastat page you recommended. I know nothing about aquastat so it will probably take me some time to research and understand it.
I will read about it and try to figure out how it might apply in my situation. I appreciate the help.
by Inspectapedia Com Moderator
@Mike
Glad to assist - keep me posted and ask for more help if needed after you read that PDF file. In the Article Index, you'll find extensive information about aquastats, what they are, how they work, etc.
No power (turned off) to the boiler but the circulating pump is 218 degrees too hot to remove safely and replace.
It has been off for 10 hours and is not cooling down. How do I get the temp down? Weil-mclain boiler Bell&Gossett circulator pump model nsf-22 On 2022-12-30 by cheryl
by InspectApedia Publisher - you've missed a switch or thermostat somewhere
@cheryl,
That sounds as if the circulator is continuing to run and I suspect that you have not turned off your boiler either.Be sure to turn off power to the whole heating system, boiler and the circulator. Then your home and the heating zone will cool down.
by Vanessa
@InspectApedia Publisher, Thank you so much for your help!!
...
What is the cost of replacing one of these gauges, the pseg guy came to check mine out and said the seal was broken, as in there was water in the gauge you couldn't read the numbers. then quoted and absurd amount, any ball park figures for the coast of parts? On 2020-11-01 by ss
by (mod) - $30-$40 for the gauge + labor: Here are the 12 steps in boiler gauge replacement
Thanks for a helpful question, SS: Typical cost of a residential heating boiler gauge;
A typical boiler gauge is about $30. to $40. U.S.
But it's helpful to understand what's needed to replace the gauge - let me outline it:
1. Drive to the site - travel time, in my truck stocked with repair and replacement costs - an overhead to the heating company
2. Talk to the customer to explain what's coming, then turn off the heating boiler and wait .... and wait ... for the boiler to cool down enough to work on it safely
3. When the boiler is cool enough to touch (water's just warm, not hot or scalding) bring in your drain hose, connect to the boiler drain, open the boiler drain, drain to an acceptable disposal point
4. Close the boiler drain, remove the drain hose.
5. With pressure off the system and boiler drained down at least to below the gauge mounting port, remove the old gauge
6. Clean up the boiler tapping, then prep the new gauge with a bit of teflon tape or equivalent, and screw it in
7 Re-fill the boiler
8. Turn heat on
9. Inspect the boiler for leaks including at the boiler drain. It's an ugly truth but too often a drain that's not touched for years, when used, spits out a dried-out stop valve washer and then can't be shut off. If the tech finds this she's got to be prepared to drain the system again and replace or repair the drain valve.
10. Purge the excess air from the system - this can take some time depending on what isolation valves were present, used, functional,
11. With boiler up to temp, inspect for leaks and
12. Confirm that every heating zone is working - don't leave the customer with an air-bound heating zone or there'll be an upset customer and a call-back for more work
It's been years so I've probably forgot something (like adding back boiler antifreeze in some systems)
But you can see that what you're paying for is not the part but the time and knowledge the service tech has to have to do the job right and not leave you with leaks or no heat in cold weather.
By the way, what cost were you quoted?
Do I need to change the gage when there is moisture on the inside of the gage glass but the gage indicates correct temp and pressure readings? Thank you. Janis On 2021-09-06 by Janis S
by (mod) - yes change the gauge
@Janis S,
Yes you should have your heating service tech change out that leaky gauge.
It's not usually an emergency, so you can schedule that for your next service call - before the oncoming heating season.
The concern is that water in the gauge tells us that there is already an internal leak in the gauge.Ongoing corrosion, or temperature change that cracks the gauge glass, or even simply accidentally whacking the leaky pressure gauge could result in its bursting;
Watch out: If that happens the result can be a boiler room or basement flood, loss of heat, and if the boiler is quite hot, even a scalding burn if someone is nearby.
I've seen leaky gauges left in place for years with nothing worse happening than that the gauge becomes un-readable. But on my boiler, rather than risk the dangers I list above, I'd have the gauge replaced.
I repete where can i buy a replacement pressure -tempurture gauge? @clint collingwood,
temperture
Where can I buy a repiacement guage? On 2020-11-28 by clint collingwood
by (mod) -
Plumbing suppliers, heating suppliers, online vendors, even Amazon.com all stock these boiler pressure and temperature gauges as it's a very common part.
Just check the pipe size, typically 1/4", of the threaded base of your boiler gauge.
...
I am stumped. Weil McLain hot water boiler is filling to 20lbs PSI cold. Three storey home.
When calling for heat the pressure goes up to 30PSI and PRV bleeds.
Expansion tank (old 4 foot long tank not bladder) seems to be taking some of the water. Any ideas? On 2020-05-07 by JH
20 psi cold is a bit high- typically we'd see 12, at a hydronic boiler. 12 psi is usually NOT enough to get hot water up 3 floors. But 15 psi is enough. So 20 is probably too high.
Sketch showing boiler psi readings vs. highest radiator in the house, courtesy Carson Dunlop Associates.
Check also the temperature: if it's going above 200F then that's the problem.
At EXPANSION TANK PRESSURE ADJUSTMENT
we discuss setting the heating boiler expansion tank pressure to accommodate tall buildings
Watch out: Also see the diagnostics and safety warnings beginning at
RELIEF VALVE LEAKS
by JH - discovered waterlogged boiler expansion tank
Think I figured it out. Expansion tank was FULL after all.
Reply by (mod) -
Way to go -
waterlogged expansion tank
Still starting at 20 psi cold is a bit high
My Weil Mclain CG boiler temp keeps rising until there is loud banging in the pipes...the temp gauge maxes out, 250f.
can't seem to get the temp to stop rising, autostat is set to 180 and the psi is around 15.
Any ideas why temp keeps rising / suggestions on what to check and how to address?
Thanks in advance! On 2020-04-17 by Jerry
by (mod) - Watch out: your boiler is unsafe, risking an explosion, turn it off
Jerry,
Watch out: That sounds very dangerous to me. At 250F if your relief valve on the boiler is not spilling you risk a BLEVE EXPLOSIONTurn off the system immediately and call for repair.
Whats the right water temperature setting for a Hydronic Boiler for a two-family house in Brooklyn New York ? And why I can't keep my boiler at 12PSI it keeps going past 30 PSI my expansion tank is new. On 2022-12-23 by Nathan
by InspectApedia (Editor) - What's the right water temperature setting for a Hydronic Boiler
@Nathan,
Your boiler temperature will be as low as room temperature when it hasn't run in some time and will heat up to somewhere under 30PSI at its hottest.If the pressure in the boiler exceeds thirty psi, the pressure temperature relief valve will open to avoid risking a boiler explosion.
You don't set the boiler pressure you set the boiler operating temperatures by adjusting the boiler's aquastat.
We explain the usual boiler temperature settings
at AQUASTAT HI LO DIFF SETTINGS
Watch out: If your boiler's starting pressure when cold is higher than 12PSI that could be your problem. In that case, when the boiler is OFF and COLD, drain water to drop the pressure to 12 psi.
Hello, I just drained out my hot water boiler, this is a three story house. I installed a new pressure reducing valve which came preset at 12 psi. I also replaced the pressure relief valve and expansion tank is also at set at 12 psi, the old one was full of water.
I filled out the the boiler and bled the air from the radiators, but my water pressure in the boiler is at 40 psi with the boiler water being cold. Am I going to have the same problem with constantly losing water? thank you- Please help! On 2022-09-12 by GEORGE.B
by InspectApedia-911 (mod) -
@GEORGE.B,
Watch out: don't even turn on the boiler before you know its cold-pressure is correct - probably 12 psi.
Either you've had street level pressure, bypassing your pressure regulator/water feeder or your pressure regulator is improperly installed or damaged.
Have you tried draining pressure from the system until it gets back to 12 psi?
Do that and if pressure stays there you're good to go.
Also don't rule out a pressure gauge that's stuck. Tap gently on the gauge to see if the needle drops.
Good day! I am writing to see if I might get some feedback if someone is available. Just got the system up and running yesterday, a 16 year old ARGO hydronic electric boiler.
The house is comfortable today, and the temperature gage has been consistent.
I have a bit of concern about the psi and the temperature seeming high according to standard said I have read about online.
And I cannot remember what the cages were reading last year. Psi is 22, temperature is 140, steady and consistent. Would anyone advise perhaps a new expansion tank? Thank you! On 2021-10-14 by Julia
by (mod) - your system is operating normally
@Julia,
An expansion tank absorbs the initial pressure increase in a hydronic heating system so as to avoid dumping the pressure/temperature relief valve.But the expansion tank has NOTHING to do with the ultimate temperature and pressure that the system will reach. Those are set by the aquastat or control over the boiler's temperature.
Your boiler pressure is about 23 psi and its temperature about 140F.
As long as you're seeing pressures that are below 30 psi (the typical PRV dump pressure) and temperatures below 200F your system is probably operating normally.
If you don't have the manual for your boiler see the Argo boiler manual downloads and contact information found at
ECR INTERNATIONAL BOILERS HVAC AGE MANUALS CONTACT
...
Benchmark 1000 boiler, my gauge pressure is zero while my temptress on same Guage is 160 F. On 2020-03-25 by Jay trinidad
by (mod) -
Jay
If you've got heat then I suspect that the gauge pressure sensor port is debris-plugged.
I have no pressure on my gauge and the boiler keeps locking out - On 2020-02-23 by Bill
by (mod) - no water pressure in boiler? Check the gauge itself
Bill:
Because sometimes the gauge itself can be debris-clogged and not register pressure, you may need to check elsewhere to find out if indeed your boiler and the heat piping are not filled with water.
Go to a high location in the building where there's an air bleeder and open the valve (carefully so as not to get scalded) to see if water comes out - if so then there is probably water in the system and the lockout may be due to a burner or safety-reset issue.
If the boiler really has no water then a low water cutoff could be shutting down the boiler to prevent damage or an unsafe condition or even a BLEVE explosion.
So if in doubt leave the system off and call for repair.
Let me know.
My hydronic heat boiler has a combination temp/press gauge installed in a sealed well.
The temperature seems to work fine, but the pressure gauge has never move off zero. How would it work in a sealed well? I'm thinking of installing a separate pressure gauge on the system that is not in a sealed well. On 2020-02-12 by Brad
by (mod) - boiler pressure gauge not working
Agree, Brad, the pressure gauge would need to be able to sense water pressure from the boiler.
But are you sure we're seeing an original installation by the manufacturer?It's not likely that the manufacturer would install a temperature/pressure gauge in a sensor well that is intended only for temperature sensors.
Attach a photo of your gauge.
Temperature on my Tridicator is 180 degrees farenheit. Is that too hot for a Weil-Mclane 150,000 BTU boiler that is 35 years old with a Honeywell R7184U Transformer ? v
by (mod) - no
180 F is a common upper limit set on heating boiler systems by service technicians.
I have a Crown boiler. The pipes in basement get hot the temperature shows temperature but the water gauge shows 0 psi.
I tried bleeding the radiators and filling with water no air or water comes out.
I replaced pressure relief valve and tried filling the boiler but no water is getting to radiators, butthe boiler is filled with water please help. Thank you. On 2021-02-24 by Jpusfinc
by (mod): sounds like your system is air-bound
@Jpusfinc, in the ARTICLE INDEX at the bottom of this page you will find several articles on
repairing an AIRBOUND HEAT SYSTEM and
others on NO HEAT - BOILER problems for hot water or hydronic heating boiler systems.
In the latter case besides resolving the Airbound question you need to look at the thermostat, thermostat wiring, circulator relay, and circulator to see if the circulator is even running.
...
Continue reading at BOILER CONTROLS & SWITCHES -home, or select a topic from the closely-related articles below, or see the complete ARTICLE INDEX.
Or see GAUGES, HYDRONIC BOILER FAQs - questions & answers posted originally at this page
Or see these
GAUGES, HYDRONIC BOILER at InspectApedia.com - online encyclopedia of building & environmental inspection, testing, diagnosis, repair, & problem prevention advice.
Or see this
Or use the SEARCH BOX found below to Ask a Question or Search InspectApedia
Search the InspectApedia website
Need to make a private comment? Email editor@inspectApedia.com. We welcome email with your website content critique, corrections, suggestions or questions. Email is monitored daily but our workload may prevent an immediate reply. For immediate results, we hope you'll first try asking your question using the search box just above.
In addition to any citations in the article above, a full list is available on request.