Hot water heating boiler pressure & temperature settings:
Here we explain where and how and to what numbers the pressure & temperature are set or controlled on hydronic heating boilers. We also describe where and how the pressure & temperature is controlled on residential steam boilers.
We include notes and links to detailed articles about the operation and use of controls on boilers, furnaces, and water heaters.
This article series answers most questions about all types of central heating system controls in order to aid in troubleshooting, inspection, diagnosis, and repairs.
InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers, products, or services discussed at this website.
- Daniel Friedman, Publisher/Editor/Author - See WHO ARE WE?
On a residential heating boiler the automatic water-feeder/pressure reducing valve that automatically provides makeup water to the heating boiler if pressure drops below 12 psi. So 12 psi is the typical "cold" pressure for residential boilers.
12 psi is for typical U.S. / Canadian residential heating systems normal cold temperature starting pressure. U.K. and european heating systems should be pressurized to between 1 and 1.5 bar - cold.
20 psi is typical for U.S. / Canadian residential heating systems normal hot operating temperature, up to just under 30 psi, depending on the high-limit temperature setting on the boiler limit control.
If we set the boiler high-limit much over 210, on many residential systems the system pressure will exceed 30 psi and we'll see water leaking from the pressure/temperature relief valve - ultimately an unsafe condition.
If your building is taller than two floors, the installer may have needed to boost the starting "cold" water pressure for your boiler to overcome the hot water distribution piping head pressure - otherwise your heating circulators may not be able to circulate hot water.
Watch out: the actual pressure in a hydronic heating system is tricky to pin down. System pressure is only uniform throughout the system when the circulator pump(s) are off, there is no circulation by convection, and piping is entirely and only horizontal - not a realistic situation, right?
ITT Industries (B&G et als) point out in technical publications that the pressure you read on the pressure gauge is only the system pressure at that location and at that particular operating condition (temperature and circulator on or off).[1]
The variables that determine the water pressure in the heating system include:
The PNPC is the location in the heating system piping installation where the compression tank is connected to the system. Note that this is not really a point of "no pressure" since there is always some pressure in the system. It is a point of no pressure change [or pressure difference] on either side of the tank's inlet fitting.
Watch out: ITT notes that despite the instructions from manufacturers that an expansion tank can be installed anywhere, installing the tank on the discharge side of the circulator pump is a mistake.
The action of the pump [if the tank is installed on the discharge side of the circulator] now decreases the pressure below the non operating pressure of the system everywhere except in the small section between the pump and the tank.
In systems where the non operating pressure of the system is low compared to the pump head, the large reduction in pressure when the pump comes on could cause boiling in hot water systems, draw air in through automatic vents, or even result in pump cavitation. When the pump is located in this way, it also can cause a great deal of confusion. [1]
At PUMP, WATER PRESSURE BOOSTING we explain the relationship between building height and water pressure, and we illustrate the water pressure decrease in building water supply piping with building height. But a look at the basement water pressures in this illustration also explains the pressures that a basement located hot water heating circulator pump has to overcome.
Remember that the building THERMOSTATS set the desired temperature in the occupied spaces in building, not the actual temperature in the heating boiler or furnace itself. In most heating systems, turning up the thermostat simply causes the boiler or furnace to turn on.
[Click to enlarge any image]The temperature at the boiler or furnace is controlled by local safety devices mounted right at that equipment, such as the heating boiler
AQUASTAT CONTROL shown here.
Hot water heating boiler normal pressure ranges as read on the pressure gauge, are described in this article, below.
The means by which a hot water heating boiler's pressure is set or controlled are described in this article below
at Where do I Set the Heating Boiler Operating Pressure?
For details how, to what number, and on what controls the hydronic heating boiler temperatures are set, also
see AQUASTAT CONTROL FUNCTIONS,
and LIMIT CONTROL, SINGLE.
Steam boiler temperature, pressure setting controls: For details how, to what number, and on what controls the steam boiler pressure settings and pressure readings are set see:
Furnace temperature setting controls: Warm air furnace temperatures are controlled at
the FAN LIMIT SWITCH.
See FURNACES, HEATING for a complete discussion of warm air heat.
Additional furnace controls include register and duct dampers -
Pressure and Temperature gauge on hot water or hydronic heating boilers: this gauge displays the heating boiler internal pressure and temperature.
Typical pressure for a residential boiler serving a two story home would show 12 psi cold, and less than 30 psi hot. Over 30 psi boiler pressure will cause the pressure relief valve to open.
Typical operating temperature settings on a boiler call for a Low temperature (boiler cut-in) between 120 and 160 °F.
Typical operating temperatures on a hydronic boiler call for a high temperature (boiler cuts off) of 180-200 °F.
If we set the boiler upper temperature too high over 200 degrees F. we're at risk of spilling at the pressure temperature relief valve.
If we set the boiler upper limit too low, there may be no relief valve problem but under some conditions we may reduce the operating efficiency of the boiler and heating system, thus increasing heating costs.
See AQUASTAT CONTROL FUNCTIONS for details.
Typical operating temperature observed at the gauge will be below the high, and can be as low as nighttime room temperature in non-heating season if no tankless coil is in use.
The temperature/pressure gauge may help in checking for normal conditions before and during boiler operation.
However the gauge can be wrong!
This gauge shows a typical in-boiler pressure of under 20 psi, and a temperature of about 190 °F. (The boiler had just cut off on a heating cycle.)
For more diagnostic aid on finding the cause and executing the cure of abnormal heating boiler pressures see
The operating pressure of a heating boiler (hot water or hydronic heat) is read at the pressure and temperature gauge (see above) and controlled by
The building THERMOSTATS do not normally directly control the temperature or pressure in the heating boiler. The thermostat sets the desired temperature in the building, but to the heating boiler it is working as a simple "on" - "off" switch, turning the boiler "on" until the thermostat is satisfied (the building is warm enough), then turning the boiler "off".
Temperature gauge on steam heating boilers:
Because a steam boiler makes heat by producing steam - by boiling water, at sea level, the temperature at the boiler will be boiling or 212 °F or close to that figure. Details are
Residential steam heating systems are almost always designed to operate at very low pressures, perhaps around 0.2 to a maximum of 0.5 psi - that' s 1/2 of one psi. Click to enlarge and you can see the actual pressure settings on the steam boiler control shown at left. High rise building and some commercial steam heat systems operate at higher pressures.
Details are at STEAM BOILER PRESSURE - home.
If your residential steam boiler is operating at higher pressures that may be an indication that a service technician or owner was having trouble getting heat distributed through the building. Rather than finding and fixing the problem, someone is trying to "force" the steam around the system.
Also take a look at the dial setting on
your STEAM BOILER PRESSURE CONTROL SWITCH
Moved to
WATER PRESSURE GAUGE INSTALLATION
...
Below you will find questions and answers previously posted on this page at its page bottom reader comment box.
On 2021-02-11 by (mod) - no steam heat on the third floor of a house
@John,
The two most-likely causes are
- imroperly-sized, type, or clogged steam vents on radiators
- a blockage in condensate return from the third floor
Let us know what \your heating service tech says as that will help other readers.
On 2021-02-11 by John
I have a three story home, with a steam boiler system, and the heat doesn’t travel to the third floor. Why is that?
On 2020-11-28 by (mod) - charting boiler supply & return temperature vs. pressure over time
Jon
Nice instrumentation. An interesting graph. Thank you. I've annotated and edited your original chart slightly for clarity. The Bosch chart above is of course a smooth and logarithmic scale and represents theory rather than your "real world" actual measurement.
In general we would expect the boiler pressure to fall, as it does, mapping a decline in temperature in the boiler, affected slightly by the operation of the circulator pump.
I can't say if the failure of the pressure line to exactly map the shape of your temperature lines is an artifact of where you're measuring each of these or if there's an effect of thermal mass in the boiler.
Bosch has published a helpful article on this that I cite below, and from which the liquid, steam, and boiling curve vs. temperture (C°) shown above is excerpted. Bosch notes: "The diagram shows the pressure-temperature curves with the boiling curve. Please also observe the notices on reading logarithmic graphs."
Bosch, BASIC PRINCIPLES of WATER VAPOUR - retrieved anew 2021/04/20 original source: https://www.boiler-planning.com/tools/basic-principles-of-water-vapour/
I'd like to work further on your interesting question about the relationship between hydronic heating system pressure and temperature, for which some added details would be helpful:
- what is the left side scale ranging from 0.0 to 0.8?
- What would be the scales for pressure and for temperature respectively on your chart?
How and exactly where are you measuring pressure and temperature? What devices, at what locations in the system.
On a typical residential hydronic heating boiler the operating pressures in the system range from about 12 psi cold to just under 30 psi hot - principally thanks to the pressure increase associated with the thermal expansion of water as it's heated.
On a heating boiler,
Over 30 psi the temperature/pressure relief valve should open and spill hot water
Over 200F (more or less) the temperature / pressure relief valve should open and spill hot water.
There may be a slight difference in pressures in a hydronic system when the circulator is running, depending on where you measure water prressure, such as at the circulator pump outlet end vs. its inlet end, or at the boiler outlet vs. boiler return.
And there will be pressure variations across the building at various elevations or heights, again depending on how pressure is measured and exactly where.
Possibly of interest
THERMAL EXPANSION of HOT WATER
THERMAL EXPANSION of MATERIALS
On 2020-11-28 by Jon
I have just added a pressure gauge in addition to supply and return pipe surface temperature gauges. Can you explain the strange relationship I see between pressure and heat in my system? The high is ~16psi for pressure and the high for supply/return is ~140F. About an hour after the boiler shuts off - the pressure decrease drops off in a somewhat non-linear fashion.
On 2020-09-28 - by (mod) -
Frank
Aquastat is a generic term for water temperature sensor control that includes controls used on water heaters and also on hydonic heating systems - i.e. boilers or forced hot water heat.
We discuss just about every aquastat type starting at
AQUASTAT CONTROLS
On 2020-09-28 by Frank
Is an aquastat just for domestic hot water? Of for forced hot water heat?
On 2020-09-28 - by (mod) -
Frank
Aquastat is a generic term for water temperature sensor control that includes controls used on water heaters and also on hydonic heating systems - i.e. boilers or forced hot water heat.
We discuss just about every aquastat type starting at
AQUASTAT CONTROLS
On 2020-09-28 by Frank
Is an aquastat just for domestic hot water? Of for forced hot water heat?
On 2018-11-29 by James
The cold water pressure of our boiler heating system is zero. But the hot water pressure is 50 PSI and hot water temperature is 220 F. We just changed a new PRV and Expansion Tank. But the problem persists.
Thanks for help
On 2018-10-15 - by (mod) -
Normal hot water heating system boiler oressure when cold is about 12 psi.
Call for repair
On 2018-10-14 by Sabina
Pressure gauge Is at 0 , what is it means?
IMAGE LOST by older version of Clark Van Oyen’s useful Comments code - now fixed. Please re-post the image if you can. Sorry. Mod.
On 2018-05-19 - by (mod) -
Mel
Watch out: a mistake can make the heating system unsafe to use.
A heating service tech would start by eliminating the thermostat from the situation by disconnecting its wires at the heating system primary controller.
If, after that step, jumping the two T T terminals together (that's what happens when the thermostat calls for heat) turns on the heater, then we know the problem is in the thermostat wiring between the thermostat and the heater, or the problem is with the thermostat and its connections.
On 2018-05-19 by Mel
Have changed old thermostat with new and still won't turn furnace on or off or regulate temperature leaving me to turn furnace on and off at furnace main wall switch what do I have to replace on furnace?
On 2018-01-17 - by (mod) -
Bill
The volume of water needed in a heating boiler depends on
- the type of heating boiler & system (steam vs. hot water)
- the physical dimensions of the boiler
- for hot water or hydronic heat, the total volume of all of the piping and radiators in the system
So there is not one "right answer"
A steam boiler is filled to a boiler water level line marked on or near the boiler sight glass
A hot water heating boiler is filled to eliminate ALL air from the system including boiler, pipes, radiators, baseboards.
On 2018-01-17 by Bill d
How much water does an empty. Boil we take or full do fill it back up and have another prob with water to faucet s is to hot
On 2017-12-03 - by (mod) -
Most heating boilers have an automatic water feed valve that will feed water into the boiler at 12 PSI when the system is cold. Your system has such a valve it's not working and you need your Plumber Heating service person to repair or replace it.
On 2017-12-02 by bt
I had a leak in the oil heating system and was fixed (pipe burst last Winter because cold temp.). We didn't use the oil heating system for about a year. Now there is no pressure (PSI) at all. The temperature reaches 180F-200F. I allowed water in the tank above the system by opening a valve to compensate for water lost when the pipe was leaking. Didn’t solve the problem. What can I do to fix the PSI issue? I was told it should reach between 15-20. Now it’s at zero. As a result, there is no heat in the house. Should I turn the oil heater on for a while, let us say 10 minutes or more?
On 2016-12-24 by Anonymous
I have barely any hot water pressure what do I do to get better pressure
...
Continue reading at PRESSURE & TEMPERATURE SETTING, CONTROL FAQs or select a topic from the closely-related articles below, or see the complete ARTICLE INDEX.
Or see these
PRESSURE & TEMPERATURE SETTINGS, CONTROLS at InspectApedia.com - online encyclopedia of building & environmental inspection, testing, diagnosis, repair, & problem prevention advice.
Or see this
Or use the SEARCH BOX found below to Ask a Question or Search InspectApedia
Questions & answers or comments about heating system operating pressures, temperatures, and controls for hot water and hot air heating systems and for warm air furnace systems
Try the search box just below, or if you prefer, post a question or comment in the Comments box below and we will respond promptly.
Search the InspectApedia website
Note: appearance of your Comment below may be delayed: if your comment contains an image, photograph, web link, or text that looks to the software as if it might be a web link, your posting will appear after it has been approved by a moderator. Apologies for the delay.
Only one image can be added per comment but you can post as many comments, and therefore images, as you like.
You will not receive a notification when a response to your question has been posted.
Please bookmark this page to make it easy for you to check back for our response.
Our Comment Box is provided by Countable Web Productions countable.ca
In addition to any citations in the article above, a full list is available on request.