InspectAPedia®   -   Search InspectApedia

Photograph of severe rust damage on a steel heating boilerHow to Find Hidden Leaks in or on Hot Water Hydronic Heating Boilers

  • POST a QUESTION or COMMENT about leaks on hot water heating systems: how to find and fix leaks and hidden leaks in boilers, piping, tanks, condensate lines, controls, radiant tubing

Hot water heating system leak diagnosis & repair:

Here we explain how to determine that a hot water heating system is in fact leaking, and second we describe how to find the location of hidden leaks in or on heating boilers, hot water heat piping, baseboards, radiators, convectors, or radiant heat floors or ceilings.

We discuss how to find leaks in radiant floor or ceiling heating systems.

How to diagnose, inspect, evaluate, repair heating boiler leaks. How to inspect & repair central hot water heating boilers - hydronic heating. Baseboard, radiator, convector heat inspection, defects, repairs.

InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers, products, or services discussed at this website.

- Daniel Friedman, Publisher/Editor/Author - See WHO ARE WE?

Tips for Finding Leaks on Hot Water Boilers or in Hot Water Heating Distribution Piping

Leak at heating baseboard connection © D Friedman at InspectApedia.com The photograph at page top shows that a heating convector recessed into the wall had been leaking into the wall structure for a long time. The leak was discovered by removing the convector cover for direct inspection.

We could also see evidence of this leak by inspecting for water stains or damage at the building sills in the basement below.

At above/left our photo shows a severe leak at an air bleed fitting on a hot water heating baseboard line that was eventually separated by freezing and frost-push.

While freezing can burst piping and cause serious leaks in buildings, a bad solder joint may be dripping into a wall, ceiling or floor for quite some time before it is detected.

Although the leakage rate in a hot water heating piping system increases when the system is hot and in use (and at higher operating pressure than when cold), much of the water leaking out of the piping evaporates.on the hot piping surface.

It is important to recognize and accurately report the significance of rust like this on any heating boiler.

Most modern heating boilers include an automatic water makeup valve that combines pressure reduction (to 12 psi cold on the boiler side of the valve) with automatically makeup water if the boiler pressure drops below that point.

Details are

at WATER FEEDER VALVES, HYDRONIC BOILER.

How Do I Know if my Heating Boiler is Leaking?

A small water leak in a hot water heating system (hydronic heat) will eventually cause pressure loss in the system, but you may never notice this problem. Leaks on hot water heating systems are likely to occur, or to leak more rapidly when the heating system is hot (at higher pressure) than when it's cool.

Leaky air vent on boiler (C) Daniel FriedmanThe pressure drop from a small heating system water leak may be occurring over a long time, months or longer, and because the leaked-water may simply dry out on the hot heating piping where it is occurring you may never see a wet spot on a floor, wall, or ceiling below the leak.

Our photo (left) shows the mineral build-up at a leaky air purge vent on a hot water heating system. Notice also those white leak stains on the boiler top itself.

How Do I Find Leaks on Hot Water Heating Systems?

To detect a small leak in a hydronic heating system we have had some success with these measures:

Leak at a boiler drain (C) Daniel Friedman

Look particularly closely where there are probably tubing connectors such as at manifolds and at the start and ends of tubing runs.

Look on floors and other building surfaces, not just at the piping itself. Our photo (left) shows the results of a dripping boiler drain.

A large water leak in a hot water heating system will usually show up quickly as a puddle, a ceiling, wall, or floor stain, or worse, as mineral clogging and damage to the boiler itself, caused by the excessive level of minerals in the constantly-added make-up water (if your area's water supply is high in mineral content).

See BOILER LEAKS CORROSION STAINS where we provide a catalog of places where leaks often occur on hot water heating systems.

This article series answers most questions about central hot water heating system troubleshooting, inspection, diagnosis, and repairs.

We describe how to inspect, troubleshoot and repair heating and air conditioning systems to inform home owners, buyers, and home inspectors of common heating system defects.

Reader Question: heating boiler expansion tank pressure drops to zero - we keep adding water.

We have the Weil-McLain boiler in floor heating system... re Expansion Tank... every 4-7 days the pressure goes down to zero (from 10 – 20 psi)...

we have a hose connected that we turn on both valves and let the water go into the tank to bring the pressure up to 10-20 psi..but still will not hold...what is the problem? and what if we do not fill with water and leave at zero? advise please. - B.A. Watford, Ontario

Reply: look for a leak in the heating system

I may not understand your question properly, and an expert onsite inspection usually reveals important additional information.

Some photos or a sketch may help me comment further - but from what I can make out you are talking about a hot water heating system and the expansion tank connected to the heating system piping and boiler.

The expansion tank's job is to absorb the initial pressure increase in the system as water heats up -- thus to avoid improper heating water spilling at the pressure/temperature relief valve. On an older steel bladderless heating system expansion tank installation, the tank eventually becomes waterlogged (air is absorbed into the heating water) and then the relief valve drips.

The "fix" is to completely drain the tank, allowing air to enter it.

When the system is turned back on and heating water is forced back into the tank, at system COLD pressures, the tank will have some water and some air inside it and the heating system pressure will be around 12 psi.

On occasion there is an air leak at the top of an expansion tank - but if that's the case you'd eventually see rust or water dripping down the tank when it becomes waterlogged. So I suspect that there is a water leak elsewhere.

I'm unclear where you are measuring pressure.

Expansion tanks don't usually have a pressure gauge attached, but as the tank and heating piping and boiler are all connected the boiler pressure gauge is approximately reflecting the system pressure.

I say approximately because the precise system pressure varies at different locations, for example it will be a bit lower at the highest point in the piping system than at the lowest point of the boiler.

Now you should not be having to add water to your heating system. Its pressure is really dropping to zero (as opposed to a gauge problem for example) then there is probably a leak somewhere that you need to find and fix.

If you have an in-floor radiant heat system the leak could be hidden below a floor slab - a condition we find by using an infra red scanner or by shutting off the water supply to the boiler and watching for a pressure drop.

I think that's the direction you need to investigate.

If you have not already read it

see BOILER LEAKS CORROSION STAINS

Also see CHEMICAL TREATMENTS, BOILER for a discussion of leak-stop products.

Other Leaks Into Boilers Can Cause Over-Pressure in the Boiler & Relief Valve Leaks

Bladderless expansion tank on gas fired heating  boiler (C) InspectApedia.com HH

Reader Question: I drained the expansion tank but the system pressure is still too high; high radiators in the house are cold & the relief valve spills

I have an bladderless expansion tank and was wondering if draining it incorrectly will not fix the problem. Here is the background of the situation.

It was noticed that a radiator one floor above the boiler (1940s oil boiler converted to natural gas) contained a lot of air in it, which was drained.

Shortly after that, it was noticed that the relief valve was dripping.

I conducted a heat test to see what pressure the boiler got to, being suspicious that the expansion tank was waterlogged. I turned off the boiler and let it cool down to ~140°F and closed the feed line and expansion tank isolation valve.

I depressurized the system at the relief valve and replaced it since it was leaking.

I then drained the expansion tank and took out about 2 gal. After that, I opened the isolation valve and then slowly opened the feed line valve, which re pressurized the system to around 15 psi.

When the system started the next morning (night time set-back), the pressure looked good and there was no dripping at the relief valve after an hour of operating, however, at two hours the pressure was at 30 psi and the relief valve was dripping.

I'm very stumped by this, because the procedure I've used seems very logical, but hope there is an issue with what I've done. We've been in this house for two previous heating season and have had no issues.

There may have been leaks in the past since the relief valve outlet was slightly corroded. Any help would be greatly appreciated. - H.H. 11/20/2013

Reply:

Let's SUPPOSE for a moment that the expansion tank is fine - that is, there are no leaks anywhere.

Let's pretend that you drained enough water out of the tank (which can be tricky). This would mean that the expansion tank is essentially empty.

Then the next day you see the tank is water logged again.

You saw "... at two hours the pressure was at 30 psi and the relief valve was dripping. "

The fact that the pressure is up to 30 makes me suspect that your system could have

- a bad automagic water feeder - feeding in too much pressure and water

- a tankless coil that leaks house-side water pressure into the boiler

If your system has a tankless coil you can check for a coil leak by TEMPORARILY shutting off water ahead of the valve. IF pressure still rises then the coil is leaking into the boiler.

If you don't have a tankless coil try this test anyway. If boiler pressure doesn't soar up to 30 when it heats up then the water feeder is probably leaking into the system.

Don't leave water shut off to a boiler or it could be ruined, dangerous, burn down, explode up or what have you if it runs out of water.

Follow-up:

The system doesn't have a tankless coil and I don't think the automatic water feeder is leaking.

I took some more observations of the system last night.

At the beginning the system was cooling down from running previously running and the boiler temperature was 110°F and pressure was 10 psi (why I think the automatic water feeder is not leaking).

I then turned raised the thermostat to fire up the boiler.

It took about 50 minutes to reach 180°F (the temperature the aquastat is set to), during which time the pressure increased. At 160°F, it was 20 psi. At 180°F, the pressure reached 30 psi and the relief valve starting leaking again.

I then turned the system off and let it cool down, which dropped the pressure too.

When the system cooled to 140°F (20 psi), I isolated the expansion tank at let things cool further. When it was 120°F, the pressure dropped to 12 psi and then I opened the expansion tank isolation valve.

I could hear water flowing through the valve and the system pressure increased back to 17 psi.

Based on these results, it seems like the expansion tank is working properly but there isn't enough air in the system to compensate for the thermal expansion (which agrees with the earlier observations that this problem began shortly after I bled a lot of air from one of the radiators).

I'm thinking I didn't drain the expansion tank properly and will try to do it again.

Do you have any suggestions or comments to what the problem might be?

I can conduct additional diagnostic tests if you'd like.

If you think the expansion tank needs to be drained again, could you provide a procedure to do it (I'm pretty sure I followed the correct one, I might have just done it when the system was too warm, but I don't see how that would have been a problem).

I've attached some pictures of the system. I now know that the lack of drain for the relief valve is very dangerous and this will be rectified once this current problem is fixed.

Reply:

The fact that you see 30 psi at just 180 °F tells us that the starting pressure in the boiler is too high.

At cold boiler you should see about 12 psi. Slightly more for a home more than two stories high. Try to be sure that you are getting ALL water out if the expansion tank. Water will reenter it but starting with a full tank of sir is usually right and sufficient.

In sum:

1. Empty the bladderless expansion tank completely.

2. With the system cold, check that the starting pressure is about 12 psi. (Keep in mind that pressure gauges on heating boilers are not lab-grade precision instruments.) If the home is taller than 2 stories see our article about setting boiler pressure to account for that difference.

3. Check that with low pressure the relief valve is not dripping.

4. Turn on the boiler and watch it go through a heating cycle. The relief valve should not spill, the temperature should be below 200F, and the pressure should be below about 28 psi.

Let's take it from there.

Reader follow-up:

Does it matter what temperature the system is at when I drain the expansion tank?

Also, I wonder if the proper way to drain my expansion tank is to use the drain valve (other end of tank in the picture I sent you) and open the union between the isolation valve and the expansion tank (it is the only fitting in the system that has Teflon tape and not pipe dope, which would imply it has been opened at a different time from the rest of the system).

As for the 10 psi pressure when cool, I was thinking the gauge could be a little off or maybe the automatic water feeder pressure was reduced because the expansion tank doesn't have any extra capacity.

The expansion tank was still waterlogged.  When attempting to drain it the first time, I must not have opened the valve enough to overcome the vapour-lock in the tank.  During the second attempt, the "glugging" sound was evident and it eventually drained. 

Now the pressure is fairly constant during operation and the peak pressure is about 25 psi. 

The cold pressure still is around 10 psi though, and was wondering if I should adjust the automatic water feeder to increase the pressure or is that pressure adequate for a one-story house?

Reply: no need to increase boiler cold pressure as long as highest radiator/baseboard is getting hot

Here's the problem - I'm just guessing because I have not see the whole expansion tank and all its fittings: You've got a container full of water with probably only one outlet - on the container bottom.

And I saw no convenient valve to drain the tank - there is a special drain valve designed for this situation, one that admits air into the tank while it is letting water out. What I saw on your system was just a union (a dis-assemblable connection) on the horizontal line near the tank - probably you've got some other lower drain point.

It's hell getting air up into the tank by that route unless you completely open the pipe and wait patiently for the tank to sloooowly drain. Or you can rig up something that pushes air into the tank intermittently to help get ALL of the water out. T

his design, unless we retrofit a better tank drain system or an air inlet higher on the tank, is so annoying that that's why we want to be sure to drain the tank fully - to get as long a life from the service job as possible. Over time the air in the tank is absorbed into water and the tank's compressible air volume shrinks - which is why ultimately the TP valve leaks.

With that chest beating done, back to your last question. As long as the highest radiator or baseboard in the home is getting hot we know the pressure is adequate. So I would not mess with the automagic pressure-reducer water feeder.

Except, to argue with myself, I'd like the cold start pressure to be slightly higher than the absolute minimum needed to allow the circulator pump to push hot water all around the heating system. That little margin, say 1-2 psi, might prevent a cold radiator under varying load or weather conditions. Usually the factory-set pressure on a water feeder/pressure reducer valve is 12 psi cold.

If you haven't seen it, this article:

WATER FEEDER VALVE, HYDRONIC BOILER

includes a neat boiler pressure setting vs building height courtesy of Carson Dunlop Associates.

And if you're feeling curious about the physics involved in the pressure increase as we heat up water,

see HOT WATER PRESSURE EXPANSION RATE

On 2020-04-10 - by (mod) -

Mr

You might try buying or borrowing an inexpensive thermal scanner to see if you can find the hot spot under the floor that would mark a leak point.

Let me know how that works.

See more thorough procedures at

RADIANT SLAB TUBING LEAKS

On 2020-04-10 by mrcackiee@hotmail.com

I have a closed (No make-up water system) radiant floor system in my barn. There are 5 loops of PEX under the floor all on one zone. It's driven by a Takagi tankless HWH.
It has worked fine for several years. Quite recently, it lost pressure and won't hold it.

The expansion tank seems fine. No fluids out of the Schrader valve, and I can pump it up with a bicycle pump.

The loops under the floor have no joints or fittings in them. I don't see any signs of liquid on any of the visible parts. There is a little corrosion on one of the manifolds, but it has been that way pretty much since the system was installed.

I thought I would try and isolate each loop and see if I could build pressure, but there is only a shut-off on the return side.

Any pressure is going to be distributed across all, so no help there. I fill the system with a small 110V pump pulling from a bucket of water / RV antifreeze mix.

I normally run the system at ~20PSI cold. I can run more pressure if that would help find the leak. Would one of the "boiler stop leak" products mentioned be suitable for this system??
Any insights would be greatly appreciated.

Greg Coleman

On 2020-03-21 - by (mod) - liquid sealer on the market that can be run through our copper system and plug small leaks

Gregory

We do not offer nor sell any product nor service.

But we're glad to try to help out with questions from our readers.

There are internal boiler/leak sealants widely sold and in a variety of formulas, though not actually an expoxy.

An example is this boiler stop leak from Hercules - available at any heating or plumbing supplier as well as at some building supply stores.

Product description:

Powdered stop-leak quickly finds and seals trouble spots on cracked steam or hot water heating boilers. Forms a tough seal that expands and contracts with boiler metal. Resists high pressure and temperature.

Once set, seal will not be dislodged by boiler cleaners. No odors. Petroleum-free. Will not clog system, valves and vents or interfere with normal boiler operation. Will not harm rubber or plastic parts.

Compatible with Hercules cryo-tek or other types of propylene glycol based anti-freeze products, chemical additives and boiler treatment compounds.

InspectAPedia.com provides building and environmental diagnostic and repair information. In order to absolutely assure our readers that we write and report without bias we do not sell any products nor services, nor do we have any business or financial relationships that could create such conflicts of interest.

On 2020-03-21 by Gregory Naumann

We live in Brookfield, Wisc and have used your company several times in the past. I believe I have a very small leak in my lower level hydronic heating system.. I cant see water on the floor but know the pressure drops a bit when working.

I heard there is a liquid sealer on the market that can be run through our copper system and plug small leaks on the inside with some type of "epoxy" seal(?), but can't locate that product. .

Have you heard of that and do you do that type of work? Please contact me by hone (262) 993-2130, or e-mail: CaptainGN@wi.rr.com. Thanks, Greg

On 2019-10-04 - by (mod) -

Yes.

Watch out: repeated dripping at the temperature/relief valve for any reason, including over-pressure, can leave deposits of minerals and debris that ultimately clog the valve and cause it to fail to open. If that happens the heating system is unsafe and could risk a BLEVE explosion (search InspectApedia.com for that phrase to read details).

As long as the valve is opening a BLEVE isn't likely, and a TPR valve on a residential boiler normally ought not open until pressure is 30 psi (or temperature is over 200F). Those conditions could be occurring at your boiler - consider that the boiler pressure/temperature gauge is not a precise instrument.

Unless your home is tall - 3 stories or more - most likely your COLD starting pressure ought to be 12 psi - and that ought to be the setting on the water feeder attached to your boiler.

You should, of course, discuss these concerns with your trained, on-site heating service technician.

On 2019-10-04 0 by Lee

Reading comments on your web site about cold water pressure in a system should be at 12 psi might be the cause of my problem. I bring the cold water pressure up to 20 psi. When it heats up it goes to about 26-27 psi and the relief valve drips water. Do you think cold water pressure at 20 psi could cause a problem ? Your web site is a GOD SEND ! Thanks

On 2018-12-17 - by (mod) -

John

I have often had success in locating a hot water heating pipe leak under a slab by borrowing or even buying a low priced thermal scanning device that can measure temperature over in the area.

Once the boiler is up to operating temperature and the circulator running, you will see a warmer area under the floor where water is leaking out of the pipe.

On 2018-12-17 by John

I have been told i have a leak in the pipes in the slab. How do i locate the leak. I see no obvious water inside or out


...

Continue reading at BOILER LEAKS CORROSION STAINS - topic home, or select a topic from the closely-related articles below, or see the complete ARTICLE INDEX.

Or see BOILER LEAKS, HOW TO LOCATE, FAQs - questions and answers posted originally on this page

Or see these

Recommended Articles

Suggested citation for this web page

BOILER LEAKS, HOW TO LOCATE at InspectApedia.com - online encyclopedia of building & environmental inspection, testing, diagnosis, repair, & problem prevention advice.


Or see this

INDEX to RELATED ARTICLES: ARTICLE INDEX to HEATING BOILERS

Or use the SEARCH BOX found below to Ask a Question or Search InspectApedia

Ask a Question or Search InspectApedia

Questions & answers or comments about leaks on hot water heating systems: how to find and fix leaks and hidden leaks in boilers, piping, tanks, condensate lines, controls, radiant tubing.

Try the search box just below, or if you prefer, post a question or comment in the Comments box below and we will respond promptly.

Search the InspectApedia website

Note: appearance of your Comment below may be delayed: if your comment contains an image, photograph, web link, or text that looks to the software as if it might be a web link, your posting will appear after it has been approved by a moderator. Apologies for the delay.

Only one image can be added per comment but you can post as many comments, and therefore images, as you like.
You will not receive a notification
when a response to your question has been posted.
Please bookmark this page to make it easy for you to check back for our response.


Comment Form is loading comments...

IF above you see "Comment Form is loading comments..." then COMMENT BOX - countable.ca / bawkbox.com IS NOT WORKING.

In any case you are welcome to send an email directly to us at InspectApedia.com at editor@inspectApedia.com

We'll reply to you directly. Please help us help you by noting, in your email, the URL of the InspectApedia page where you wanted to comment.

Citations & References

In addition to any citations in the article above, a full list is available on request.



ADVERTISEMENT