InspectAPedia®   -   Search InspectApedia

Oil fired hot water heating boiler (C) Daniel FriedmanGas or Oil Burners Must Be Above Garage Floor
Code requires you to elevate an ignition source & protect from impact

This article describes the requirement that sources of ignition in a garage, such as a heating boiler, furnace, or water heater shall be elevated at least 18" above the floor to reduce the chances of an explosion caused by igniting gas fumes that might originate from a vehicle in the garage or similar sources.

Photo: this oil burner is installed in a utility alcove that opens into a New York garage. There is no door on the utility space but its floor is 4" above the garage floor.

That was not sufficient elevation of the oil burner above the garage floor, so the installer used stacked concrete blocks to raise the oil burner itself more than 18" above the level of the garage floor.

InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers, products, or services discussed at this website.

- Daniel Friedman, Publisher/Editor/Author - See WHO ARE WE?

Building Codes Require Installer to Elevate Ignition Source & Protect from Impact

Elevate appliance in garage & protect from impact, adapted from 2009 IRC as per WA, cited in detail at InspectApedia.com (C) Daniel Friedman at InspectApedia.com

Oil and gas-fired heating equipment and other sources of ignition must be elevated above the garage floor sufficient to avoid a common source of ignition.

The concern is that leaks or fumes from a vehicle in the garage or possibly even fuel (unsafely-) stored in a garage can explode if ignited by any source of ignition in that space.

This elevation, usually achieved by putting the heater up on concrete blocks, is required by some building codes that specify that the water heater must be elevated above floor level, for example for water heaters or heating boilers or furnaces installed in a garage.

[Click to enlarge any image]

Note that many new water heaters are FVIR rated or "Flammable Vapor Ignition Resistant".

IRC Mechanical Code Section 69. APPLIANCES INSTALLED IN GARAGES.

Section M1307 IRC 2009 - furnace (or boiler or water heater etc) in a garage

M1307.3 Elevation of ignition source.

Appliances having an ignition source shall be elevated such that the source of ignition is not less than 18 inches (457 mm) above the floor in garages.

For the purpose of this section, rooms or spaces that are not part of the living space of a dwelling unit and that communicate with a private garage through openings shall be considered to be part of the garage.

M1307.3.1 Protection from impact.

Appliances shall not be installed in a location subject to vehicle damage except where protected by approved barriers.

Requirement to Elevate Oil & Gas Appliances No Less than 18" Above the Garage Floor

Original source of the text and illustration above:

In-Garage Stairs to Basement = An Explosion Waiting to Happen

Basement stair with open side, no rail (C) Daniel Friedman

Above in a variation of basement walk-out stairs we illustrate an unsafe entry stair passing from a residential garage into the home's basement.

Watch out:  As heating equipment is most often found in the home's basement, imagine the explosion that may occur (one did, despite our emphatic warnings, in Fishkill NY) if a vehicle leaks gasoline and gasoline fumes into the garage.

Gasoline fumes, heavier than air, fall down the stairwell, into the basement (or crawl space) where, at the next spark or flame, there is risk of an explosion

A "fire door" in the stairwell bottom is not enough security for this installation. In fact, as you can see, the (not fire-rated) door has been left ajar.

See also BASEMENT WALKOUTS & COVERS

See details about the requirement for self-closing doors and fire-rated doors

at GARAGE DOOR & DOOR OPENER SAFETY

...




ADVERTISEMENT





Reader Comments, Questions & Answers About The Article Above

Below you will find questions and answers previously posted on this page at its page bottom reader comment box.

Reader Q&A - also see RECOMMENDED ARTICLES & FAQs

On 2017-07-19 by (mod) re: clothes dryer location vs gas furnace clearance distances

Heather:

The two worries, I suspect, nagging at your maintenance guys were

1. lint and dust from the clothes dryer may clog the combustion air inlet of your gas fired heating furnace, causing unsafe conditions and risking fatal carbon monoxide poisoning.

2. They might miss a chance to sell you a lint filter that you not only don't need, but that depending on the type and installation might itself be a serious fire hazard.

If your clothes dryer is properly and safely vented to the building exterior, the release of lint around the dryer itself ought to be minimal and not a safety hazard.

Start with a practical examination: is there dust visible in, on, or around your gas fired heating equipment? Is that dust dryer lint? If so, then a combination of housecleaning and an inspection of the dryer for dust and lint leaks is in order regardless of the dryer's exact placement.

Two feet more or less distance change from a clothes dryer that's leaking lint would not make one iota of difference in safety.

So where is the issue with clothes dryer distance to the gas furnace?

The answer is working space or fire clearances from combustibles that will be specified in the gas furnace installation manual for your specific heater. If the dryer is installed too close to the heater it violates the manufacturer's instructions, may prevent proper heater maintenance, and might be unsafe.

Using an American Standard Gas Furnace installation manual as an example, since you don't name your furnace brand and model, the word "clearance" appears 50 times in the document, showing that the manufacturer indeed has a worry about safe clearance distances for the heater.

Watch out: as you say two gas appliances are in your garage on the floor, there is also an explosion risk, as we explain above on this page.

Also see CLOTHES DRYER FIRE HAZARD WARNINGS

On 2017-07-19 by Heather: clothes dryer location vs gas furnace clearance distances

My maintenance guys said that my gas-heated clothes dryer and gas furnace are unsafe. They're both in the garage, and the clothes dryer just blows its exhaust onto the floor near my gas furnace.

Are they right? Why should I care? - Heather [paraprasing] 2017/07/19


...

Continue reading at PROTECTION BOLLARDS for MECHANICAL EQUIPMENT, or select a topic from the closely-related articles below, or see the complete ARTICLE INDEX.

Or see these

Recommended Articles

Suggested citation for this web page

ELEVATE OIL or GAS BURNER 18" ABOVE GARAGE FLOOR at InspectApedia.com - online encyclopedia of building & environmental inspection, testing, diagnosis, repair, & problem prevention advice.


Or see this

INDEX to RELATED ARTICLES: ARTICLE INDEX to HEATING FURNACES

Or use the SEARCH BOX found below to Ask a Question or Search InspectApedia

Or see this

INDEX to RELATED ARTICLES: ARTICLE INDEX to GAS APPLIANCES, PIPING, CONTROLS

Or use the SEARCH BOX found below to Ask a Question or Search InspectApedia

Ask a Question or Search InspectApedia

Try the search box just below, or if you prefer, post a question or comment in the Comments box below and we will respond promptly.

Search the InspectApedia website

Note: appearance of your Comment below may be delayed: if your comment contains an image, photograph, web link, or text that looks to the software as if it might be a web link, your posting will appear after it has been approved by a moderator. Apologies for the delay.

Only one image can be added per comment but you can post as many comments, and therefore images, as you like.
You will not receive a notification
when a response to your question has been posted.
Please bookmark this page to make it easy for you to check back for our response.
Our Comment Box is provided by Countable Web Productions countable.ca

Comment Form is loading comments...

Citations & References

In addition to any citations in the article above, a full list is available on request.



ADVERTISEMENT