Inspection & tests of a condensing gas furnace:
Visual inspection of a 1996 Tempstar™ condensing gas furnace discovers signs of "reverse air flow" at the condensing furnace air intake. This condition leads home inspector Roger Hankey to expand the inspection scope to test the heating system for safety.
Page top photo: initial inspection at the top of this Tempstar™ gas furnace shows discoloration at the combustion air intake, a possible sign of improper and unsafe system operation discussed below.
InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers, products, or services discussed at this website.
- Daniel Friedman, Publisher/Editor/Author - See WHO ARE WE?
On a 20˚F day in December 2017 an initial tour of the house found a condensing gas furnace in the basement with a plastic vent pipe and no pipe on its air intake.
A plastic grid over the combustion air intake was discolored and cracked consistent with heat damage [photos above].
[Click to enlarge any image]
Also a very slight odor was found at the intake consistent with the odorant in natural gas.
Opening the front panel revealed corrosion consistent with condensate leak below the inducer but no active leak was found.
2018-01-15 The original draft of this article remains under discussion.
See the working document
at CONDENSING GAS FURNACE INSPECTION & TESTS DISCUSSION
Also see the procedures discussed at HEAT EXCHANGER LEAK TEST - Editor.
what is the normal life of natural gas furnace? - Marlin 10/30/12
Just about the warranty period - manufacturers know their equipment well; warranty periods run from 10 years to "lifetime"
Please see FURNACE HEAT EXCHANGER LIFE where we give details about residential heating furnace life expectancy.
What would cause standing pilot flame to keep going out . thermocouple was replaced hoy air furnace - Bruce 11/17/12
Bruce,
Check for these other causes of loss of the gas pilot flame
Roger Hankey is principal of Hankey and Brown Inspections, Winter Park, CO. Mr. Hankey is a past chairman of the ASHI Standards Committee and served in other ASHI chapter and national leadership roles. Mr. Hankey is a National Radon Proficiency Program certified measurement professional and a Level II infrared thermographer. Contact Roger Hankey at: 970-393-6604 - rogerhankey47@gmail.com . Website: www.HankeyandBrown.com Mr. Hankey is a frequent contributor to InspectAPedia.com.
...
Below you will find questions and answers previously posted on this page at its page bottom reader comment box.
On 2020-10-16 by (mod) - clearance between a direct-vent for a gas fired heater and an operable window.
Karottu
Thank you for the helpful photo and question about clearance between a direct-vent for a gas fired heater and an operable window.
The guidelines for clearance distance from the gas vent outlet to the closest edge of an operable window (or door) vary by country.
In the U.S., depending on the BTUh rating of the heater, you need typically 12" but as much as 36" of distance.
In Canada the specifications for gas vent to window are:
6 inches (15 cm) for appliances =/< 10,000 btuh (3 kw),
9 inches (23 cm) for appliances > 10,000 Btuh (3 kw) and =/< 50,000 btuh (15 kw),
12 inches (30 cm) for appliances > 50,000 Btuh (15 kw)
So you'll want to identify the brand and model of your specific heater and to see what the manufacturer requires.
Please see details at GAS APPLIANCE / HEATER DIRECT VENT CLEARANCES
About the distance between the gas-fueled heater direct vent exhaust opening and intake opening, your photo looks typical - instructions often specify a 12-inch separation (or more) between intake and outlet openings;
but again you'll want to see what the specific installation instructions for your specific heater require.
On 2020-10-16 by Karottu T. George
Recently installed a Carrier furnace 59TP6B040V14-10. The venting is a 2 pipe system as shown in the attached picture. The exhaust vent is about 2 feet just under a bedroom window and about 1 foot from the basement window directly below. Is this a health concern for the person in the bedroom? The vent is directly under the window (though 2 feet under).
Also, is it possible for the exhaust gases drawn into the furnace through the inlet pipe. They are both very close together..
I have a rooftop unit and have been told i have a few very small holes in the heat exchanger that can be repaired with an appropriate silicone which should hold for a season or two. True? Thanks.
Tom,
You may be lucky to find a service tech who will touch a heat exchanger with a leak. Sure, it's plausible that leaks can be sealed with an appropriate heat-proof sealant (there are high temperature silicones).
The risks that I can think of include:
- not being able to see, find, access all of the leaks to seal them safely
- improper surface cleaning, bad bond, a "sealed" leak remains leaky
- since leaks due to rust are in the form of perforations that are usually surrounded by a larger thin-rusted area of steel, there is a real risk that just touching the leak area may poke a bigger hole, making repair difficult, or that the extent of sealant doesn't cover enough area and the patch is not reliable.
Watch out: Even though your heating unit is on a rooftop (thus outdoors) a heat exchanger leak can still send dangerous flue gases, even fatal carbon monoxide into building air.
So while no one is likely to be dumb enough to bet your life on any kind of promise or guarantee, you can yourself reduce risk by making darn sure that you've got working CO detectors properly installed in proper locations in the building.
See CARBON MONOXIDE - CO and CARBON MONOXIDE WARNINGS: HOME HEATERS
(Nov 10, 2014) Anonymous said:
i have a silicone holding my heat exchanger tubes on some has come off is there a safe silicone for the air stream inside the furnace
Anon
Yes probably. I would check with the unit's manufacturer for what sealants they recommend, particularly as heat and other issues will vary among equipment and even location within the same appliance
(Nov 10, 2014) Anonymous said:
Called american standard furnace they gave me a local repair mans # he said go to the automotive store i want the factory type but that wont even go there
Reply:
I doubt that's what the American Standard furnace manufacturer had in mind. Call someone else.
(Nov 16, 2014) craig loeschke said:
there is water leaking where the secondary heat exchanger is. Would that mean my heat exchanger is bad or is there a pan that is leaking. the condensate trap is doing its job, water around the base of the secondary heat exchanger is located. hoses are clear not plugged.
The water leak from condensate could indeed destroy a heat exchanger. A more expert inspection is needed to assure your system is safe.
Susan said: what is a heat exchanger test? Won't a pressure test suggested by my landlord cause damage to y furnace?
Susan a heat exchanger test is a check for potentially carbon monoxide leaks out of a furnace into building air. There are several test approaches including the use of a tracer gas that will not risk damaging the system. I'm not sure what pressure test your tech has in mind. Discuss the system safety and the test risks with the service manager. Let us know what you're told.
(Sept 22, 2015) Steve Schassler said:
Oil burner forced hot air odor problem. In this small 1/2 duplex home severe uncombusted air smell. Severe summer summer months when furnace off. Bad also when furnace is on. During summer closed off all supply and return registers (sealed each one tightly) and oil smell has all but disappeared.
We have a new furnace but during pre-closing inspection, inspector could see burner flames via supply plenum access port due to a corrosion problem allowing combustion gases directly into supply plenum.
Could this be that supply ductwork has been contaminated prior to corrosion problem being fixed? Afraid to allow family to live in this unit. Recommendations?
Steve:
Watch out: there is a Primary life-safety issue: if your home inspector could see the burner flames through the supply air plenum then the furnace is unsafe, should not be used, and needs repair or more likely replacement. It's not just an odor problem there's a risk of setting the building afire or dosing occupants with combustion gases that can be themselves harmful or dangerous.
I can't imagine what "fix" was done to a hole in a heat exchanger. The proper repair is to replace the heat exchanger or replace the furnace. Patch jobs are likely to be un-warranted and unsafe and unreliable.
We need a more accurate diagnosis of what you're smelling - "uncombusted air" I don't know what that means.
Secondary issue: If you are smelling heating oil odors then there has been a spill or there is a leak. Those odors may be transported through the building even when the forced air system is off. Follow the oil tank from fill through tank through piping through burner to look for leak possibilities. A spill of heating oil itself in the ductwork would be odd unless some fool ran oil lines though the ducts.
See ODORS FROM HEATING SYSTEMS
and
(Mar 14, 2016) Anonymous said:
can i operate my furnace if there is a small crack
Anon:
What we MUST say for LIFE SAFETY: depending on the heat exchanger crack size, location, and other conditions such as the blower fan and duct properties, it is possible for a heat exchanger crack to kill the building occupants with fatal carbon monoxide. Also keep in mind that what's a "small crack" (at least in your view - where "small" is not defined), it can suddenly become large as heat exchanger temperatures fluctuate.
The fact is that not every small heat exchanger crack is fatally dangerous:
For example in some positions (as I said it depends on where the crack occurs), when the blower fan runs air is pushed into the heat exchanger rather than allowing dangerous flue gases out into the building's duct system. When that's the case the only time you can even measure CO at the heat exchanger is during that interval between when the burner has turned-on and before the blower fan starts.
Watch out: But as I warned, small cracks can become big fatal ones. And there may be other cracks, holes, or damage that you've not seen. So no one in their right mind would tell you , not on-site, and not by e-text, that your heating system is safe. It is not.
...
Continue reading at HEAT EXCHANGER LEAK TEST - topic home, or select a topic from the closely-related articles below, or see the complete ARTICLE INDEX.
Or see these
CONDENSING GAS FURNACE INSPECTION & TESTS at InspectApedia.com - online encyclopedia of building & environmental inspection, testing, diagnosis, repair, & problem prevention advice.
advice.Or use the SEARCH BOX found below to Ask a Question or Search InspectApedia
Try the search box just below, or if you prefer, post a question or comment in the Comments box below and we will respond promptly.
Search the InspectApedia website
If you posted comments here and no longer see what you wrote, please check for your comment in the Reader Q&A found above on this page.
In addition to any citations in the article above, a full list is available on request.