Building Inspection, Diagnosis & Repair Info

Vent condensate freeze (C) Daniel FriedmanCondensing Boilers & Furnace Condensate Drains

  • POST a QUESTION or COMMENT about high efficiency heating boilers & condensing boilers: inspection, diagnosis, maintenance, & repair advice

High efficiency & condensing heating boiler condensate drainage piping & disposal guide:

Plumbing & heating codes & suggestions for disposal of condensate produced by high efficiency gas-fueled condensing boilers & furnaces.

This article series discusses the installation, operation & maintenance as well as defect inspections for high efficiency oil and gas fired heating boilers & furnaces, condensing boilers, and similar energy-saving equipment.

InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers, products, or services discussed at this website.

- Daniel Friedman, Publisher/Editor/Author - See WHO ARE WE?

Condensate Drain Specifications for High Efficiency & Condensing Gas Heating Equipment

High efficiency heater problems (C) Daniel Friedman

Reader Question: proper piping materials for condensate from condensing furnaces or boilers

2017/01/11 Greig

Can a brass fitting be used to connect a condensing boiler flue condensate or will this corrode?

This question and answer were posted originally

at CHIMNEY WET TIME & CORROSION

Reply: use corrosion-resistant piping for condensate disposal

Condensate from condensing boilers is quite corrosive, a view shared by experts (Xinqiao 2006). That's why plastic is a good drain material. Stainless steel might be acceptable in some situations. I'd be careful about using brass, iron, copper, galvanized pipe.

While the manufacturer of the boiler would be the an authority on what is acceptable piping material for condensate disposal, model building codes say this, using ICC model building codes adopted by Virginia in the U.S. as an example:

ICC SECTION 314 - CONDENSATE DISPOSAL

[M] 314.1 Fuel-burning appliances.

Liquid combustion byproducts of condensing appliances shall be collected and discharged to an approved plumbing fixture or disposal area in accordance with the manufacturer’s installation instructions.

Condensate piping shall be of approved corrosion-resistant material and shall not be smaller than the drain connection on the appliance.

Such piping shall maintain a minimum horizontal slope in the direction of discharge of not less than 1/8 unit vertical in 12 units horizontal (1-percent slope).

[M] 314.2.1 Condensate disposal. Condensate from all cooling coils and evaporators shall be conveyed from the drain pan outlet to an approved place of disposal.

Condensate shall not discharge into a street, alley or other areas so as to cause a nuisance.

[M] 314.2.2 Drain pipe materials and sizes.

Components of the condensate disposal system shall be cast iron, galvanized steel, copper, cross-linked polyethylene, polybutylene, polyethylene, ABS, CPVC, or PVC pipe or tubing. All components shall be selected for the pressure and temperature rating of the installation.

Condensate waste and drain line size shall not be less than 3/4-inch (19 mm) internal diameter and shall not decrease in size from the drain pan connection to the place of condensate disposal.

Where the drain pipes from more than one unit are manifolded together for condensate drainage, the pipe or tubing shall be sized in accordance with an approved method.

All horizontal sections of drain piping shall be installed in uniform alignment at a uniform slope.

Research on corrosion in condensing boiler condensate systems

...




ADVERTISEMENT





Reader Comments, Questions & Answers About The Article Above

Below you will find questions and answers previously posted on this page at its page bottom reader comment box.

Reader Q&A - also see RECOMMENDED ARTICLES & FAQs

Why does moisture sometimes come from the combustion air intake line on furnace

Leaks at a condensing gas boiler or furnace - where is the leak source? (C) InspectApedia.com TimSo, I’m unable to get an answer from anyone on this.

Why does moisture sometimes come from the combustion air intake line on furnace & cause rust & corrosion.

It could be improper pitch, not enough return air, exterior terminations are to close to home...but nobody has a definitive answer. Any thoughts? 2020/03/31 Tim said -

This Q&A were posted originally

at HEATING SYSTEMS

2020/03/31 common sources of condensate leak in high efficiency or condensing gas heating equipment

Tim

You ask why, in a condensing or high efficiency gas furnace, we see condensate dripping back into the heater.

[Annotations on photo are by InspectApedia.com - Ed.]

You cite condensate at the combustion air intake - which IMO is a bit unusual except for heaters that use a concentric air-intake + exhaust-outlet system.

Can you confirm how your heater gets its intake air and how its exahust is vented? Can you post a photo of the air inlet and exhaust outlet from outside the building (one photo per comment).

Please also post more detailed photos of the point where you think the leak is occurring.

You also pose the most-common explanations: improper pitch somewhere in the exhaust vent system, and improper exhaust vent termination (blocked, too close to ground, wind-impaired).

You also mention inadequate return air which is a clever and subtle potential explanation of exhaust vent problems: if there is inadequate return air it is possible that a vacuum is created near

*either* the combustion air intake (creating for gas fired appliances a high risk of unsafe carbon monoxide production)

*and/or* a vacuum near the exhaust vent that on gravity-vented or naturally-vented appliances draws exhaust gases out into the space around the heater

*or* for high-efficiency gas appliances, a nearby negative air pressure might draw condensate (and a small amount of exhaust gas) out of a small diameter drain opening or air intake or poorl-sealed flue joint where it could drip into the gas heater.

On a high efficiency gas appliance condensate may be disposed-of by draining back into a condensate drain for disposal into the building's DWV system. Condensate may also drip out of the exhaust termination but in freezing climates I've found this to be unsafe as ice build-up can block the exhaust.

See details at

DIRECT VENT INSTALLATION, SNAFUS & SPECS

and

CONDENSING BOILER/FURNACE CONDENSATE DRAIN

also

CLEARANCE REQUIREMENTS for Direct Vented Gas Appliances

SLOPE REQUIREMENTS

On gas heaters that I've inspected and that had rust stains inside of the cabinet the most-common leak was at a gasket or joint on the exhaust line that was allowing condensate to escape into the unit instead of draining into the condensate drain that some units carry.

Following all of that speculation and review where are we?

We need a thorough, complete, detailed visual inspection of your specific gas heater by an experienced technician. In my experience a careful inspection (rarely some testing is needed) can find visual evidence of the leak source (by deposits if not actual condensate) by some common sense: water flows down-hill. Find the stains, look up and around to find the source.

I'd like to see more-detailed photos of the leak stains in your heater and of the components above and near that location.

 

Black mold in the Condensate Pump

High Effficiency Condensing furnace 11 years old. In this last year, a black mold has been entering the Condensate Pump to the point of smothering it.

Replaced the pump and discharge line this Dec 16, 2019. Pump ran clear and in the last week, Algae again blackening the discharge line and is evident in pump reservoir. Pump discharges into laundry pump drain. On 2020-01-14 by Rick

Reply by (mod) -

Sounds like some kind of slime mold. It would be useful to track backwards to try to find the source. I suspect that you're going to want to clean and sanitize the system.

OK to dispose of gas furnace condensate on the lawn?

Can I dispose of condensate from a gas fired furnace to the lawn area? On 2019-07-24 by Chuck Goin

Reply by (mod) -

That should be ok - be sure water drains away from the building not into it. And I'd watch to be sure that acidic condensate isn't harming any plants or the grass.

If that becomes a problem you'll want to let it drain to a harmless cource such as a drywell.

...

Continue reading at CONDENSING BOILERS/FURNACES or select a topic from the closely-related articles below, or see the complete ARTICLE INDEX.

Or see these

Recommended Articles

Suggested citation for this web page

CONDENSING BOILER/FURNACE CONDENSATE DRAIN at InspectApedia.com - online encyclopedia of building & environmental inspection, testing, diagnosis, repair, & problem prevention advice.

Or see this

INDEX to RELATED ARTICLES: ARTICLE INDEX to HEATING BOILERS

Or use the SEARCH BOX found below to Ask a Question or Search InspectApedia

Ask a Question or Search InspectApedia


Questions & answers or comments about high efficiency heating boilers & condensing boilers: inspection, diagnosis, maintenance, & repair advice

Try the search box just below, or if you prefer, post a question or comment in the Comments box below and we will respond promptly.

Search the InspectApedia website

Note: appearance of your Comment below may be delayed: if your comment contains an image, photograph, web link, or text that looks to the software as if it might be a web link, your posting will appear after it has been approved by a moderator. Apologies for the delay.

Only one image can be added per comment but you can post as many comments, and therefore images, as you like.
You will not receive a notification
when a response to your question has been posted.
Please bookmark this page to make it easy for you to check back for our response.


Comment Form is loading comments...

IF above you see "Comment Form is loading comments..." then COMMENT BOX - countable.ca / bawkbox.com IS NOT WORKING.

In any case you are welcome to send an email directly to us at InspectApedia.com at editor@inspectApedia.com

We'll reply to you directly. Please help us help you by noting, in your email, the URL of the InspectApedia page where you wanted to comment.

Citations & Reviewers

In addition to any citations in the article above, a full list is available on request.

  • "Top Ten High Efficiency Gas Furnaces Based on Repair Frequency", in "#1 rated A/C & Heating System in the industry today? ", Merchantcircle.com, retrieved 4/3/12, source: http://www.merchantcircle.com/answers/q/91715/In-your-opinion--what- -would-you-say-is-the--1-rated-A-C---Heating-System-in-the-industry-today-
  • Carrier Model BW9 Gas-Fired Condensing Boiler - Gas Fired Direct Vent Condensing Boiler - Example Installation & Operating Manual
  • In addition to citations & references found in this article, see the research citations given at the end of the related articles found at our suggested

    CONTINUE READING or RECOMMENDED ARTICLES.


ADVERTISEMENT