Building Inspection, Diagnosis & Repair Info

Congoleum sheet flooring, Australia (C) InspectApedia.com 1970s Congoleum Nairn Sheet Flooring & Floor Tile

Congoleum flooring identification:

This article provides a guide to identifying traditional or early Congoleum rugs and other sheet flooring products, Congoleum-Nairn asphalt-asbestos, vinyl asbestos floor tiles, linoleum, and sheet flooring (resilient flooring).

Some of these Congoleum floor covering materials contain asbestos in asbestos fiber or asbestos powder-filler form.

InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers, products, or services discussed at this website.

- Daniel Friedman, Publisher/Editor/Author - See WHO ARE WE?





ADVERTISEMENT





Asbestos in Some 1970s Congoleum-Nairn Vinyl-Asbestos Floor Tiles & Congoleum Linoleum Sheet Flooring

Congoleum sheet flooring, Australia (C) InspectApedia.com Asbestos was found in at some Congoleum flooring products including: Congoleum-Nairn Flor-Ever Vinyl, Fashionflor Cushioned Vinyl flooring, Gold Seal Vinyl Inlaid flooring, Gold Seal Vinyl Nairon Standard flooring.

Asbestos is safe and legal to remain in homes or public buildings as long as the asbestos materials are in good condition and the asbestos can not be released into the air.

SEQUIN PATTERN [image] Congoleum resilient flooring is shown above.

[Click to enlarge any image]

Congoleum Sheet Flooring, 1970's Asbestos Content

Question:

I am doing renovation on a 1978 house. While busting up tile in about 150 sqft it was revealed that there was linoleum sheet flooring underneath.

I could [not] read all the back of it but did see "Pacemaker" and saw it was a Congoleum product. I saw that product on a list of asbestos-related flooring, but the damage was done. Not all the flooring came up but a good amount did with the tile jack.

Any thoughts? - Anonymous by private email 2018/09/09

Reply: 1970's Congoleum sheet flooring may contain asbestos - as well as Congoleum flooring up to 1984.

You're right, Anon, that Congoleum Pacemaker flooring contained asbestos - Congoleum Pacemaker is among the product names listed

at CONGOLEUM FLOOR PRODUCTS CONTAINING ASBESTOS.

However at least one reader reported having tested later Congoleum Pacemaker and finding it contained no asbestos.

"Pacemaker II" from Congoleum contained no Asbestos in it. The trademark for the stamp was issued in 1982.

Details are at CONGOLEUM-NAIRN FLOOR TILES & LINOLEUM FAQs

Typical sources and the mesothelioma websites and lawyers typically assert that Congoleum's sheet flooring products between 1958 and 1968 contained asbestos. Other websites put the end date for asbestos in flooring as 1979. Still other law firms cite 1980 as Congoleum's last year producing asbestos-containing flooring.

Most of those web pages and authors are, by our research and by our own lab reports, mistaken:

Asbestos has been confirmed in Congoleum sheet flooring by lab tests reported by some of our readers for Congoleum flooring installed as recently as the early 1980s. Note that that is a bit past 1980.

Now it's possible that "new old stock" asbestos-backed floor tiles or sheet flooring that were manufactured before 1969 (or those later years I cited) were installed at later dates but that assumption may not be sufficient to rule the asbestos-question in or out.

It is common for both asphalt-impregnated felt-backed flooring products and the light or near-white waxy paper-like backing on sheet flooring from the 1970's and early 1980's to contain asbestos.

See 1980 CONGOLEUM NO-WAX SHEET FLOORING - With Asbestos-Content - for an example.

Therefore I agree that for a 1970's Congoleum floor material that has not been tested to confirm the presence or absence of asbestos, it would be prudent to treat the floor as PACM - Presumed Asbestos Containing Material.

You will want to do the obvious: damp wipe, HEPA vacuum up dust, and don't make more of a dusty mess when removing the remainder.

Below I will give two asbestos floor removal article links that you should review before doing more work on the floor in your home.

If you want to have a sample tested, which you certainly should do if you're facing a large cleanup or removal expense now,

see ASBESTOS TESTING LAB LIST and please let us know the result as that will assist other readers.

If there are instances in which the Pacemaker stamp or other markings are clear I'd like to see photos of those as well as of the actual pattern on the floor surface and of course of the current state of the floor. That might let us comment further.

Don't panic: doing so invites getting gouged by a cleanup company.

ADVICE: For buildings with floor tiles that could be assumed to have been installed in North America before 1986 it would be prudent to treat the flooring as "PACM" or "Presumed Asbestos Containing Material".

The presence of known asbestos-containing flooring does not mean we should panic nor that we should undertake an expensive and dangerous asbestos removal project.

Asbestos is safe and legal to remain in homes or public buildings as long as the asbestos materials are in good condition and the asbestos can not be released into the air.

Generally the safest approach is to leave asbestos-containing sheet or tile flooring alone and to cover it with a coating or with another layer of flooring.

On any of our asbestos-related InspectApedia pages, at CONTINUE READING you will find a complete ARTICLE INDEX to ASBESTOS HAZARDS

See also in that index these articles:

ASBESTOS FLOORING HAZARD REDUCTION

ASBESTOS FLOORING REMOVAL GUIDE

ASBESTOS REMOVAL, WETTING GUIDE

Question: how do we reduce the risk of asbestos dust exposure after this 1975 Congoleum Floor has already been removed?

1975 Congoleum floor presumed to contain asbestos (C) InspectApedia.com Danielle \

We just purchased built in 75 and started renovating a home that tested positive for asbestos in the popcorn ceiling which we’ve had professionally removed.

We now discovered this flooring when getting ready to put in tile, and unfortunately didn’t the think to research it until we ripped it up. I’m terrified that after all our efforts with the ceiling being properly handled, now we’ve just spread of exposed ourselves to asbestos anyway through this flooring.

Perhaps someone has knowledge about this exact flooring.

1975 Congoleum floor presumed to contain asbestos (C) InspectApedia.com Danielle

It appears to be Congoleum brand.

What can we do to make sure the house is safe from asbestos before we move my daughter with chronic health issues in? - Anonymous by private email 2020/10/28

Moderator reply: have representative dust samples tested for asbestos

1975 Congoleum floor presumed to contain asbestos (C) InspectApedia.com Danielle

Thanks you for a helpful question Anon.

At this point with the flooring gone how can we manage the risk of possible asbestos exposure:
As there is no flooring to test, and as we've described in this Congoleum flooring asbestos article series, you'd presume that the floor contains asbestos.

So what can we do now to avoid the secondary health hazards of either asbestos dust exposure or of anxiety and worry about asbestos dust in the home?

What's left is to collect representative samples of settled dust from the occupied spaces of the home and have those screened for any meaningful levels of asbestos or other harmful particles.

See DUST SAMPLING PROCEDURE for a strategy for collecting building dust samples, when, where, how many samples to collect.

This process uses simple clear adhesive tape and freezer-type ziplok bags to collect dust samples that represent building conditions.

You'll want to look for horizontal surfaces close to the area where the flooring was removed and that have not been cleaned or dusted since that activity. Often we find these atop a refrigerator or over door or window trim.

Then see

ASBESTOS TESTING LAB LIST

for a list of certified labs who can analyze your samples.

IF the lab report says that your house dust (normally mostly fabric fibres and skin cells) contains significant levels of asbestos,

THEN you'd want to have more expert, thorough cleaning in the home, such as using damp wiping and HEPA vacuuming of surfaces and additional cleaning of fabrics and other soft goods.

Recommended reading:

OTHER PEOPLE's MONEY - what happens if you try too hard to reduce your risks to zero by getting outside consultants' advice.

1970's Congoleum Flooring: Pacemaker under demolition

1978 Congoleum Pacemaker sheet flooring (C) InspectApeda.com Hans

Question: any thoughts about this linoleum sheet flooring

I am doing renovation on a 1978 house. While busting up tile in about 150sqft it was revealed that there was linoleum sheet flooring underneath.

I could read all the back of it but did see "Pacemaker" and saw it was a Congoleum product.

I saw that product on a list of asbestos-related flooring, but the damage was done. Not all the flooring came up but a good amount did with the tile jack.

Any thoughts?

Thanks, Anonymous by private email, 2018/09/09

Moderator Reply:

Don't do anything expensive before we know if this is an asbestos-containing flooring - or else have a sample tested.

Hiring an asbestos cleanup company is still expensive. But so is making a dusty mess of asbestos debris that later needs still more-extensive cleanup.

See ASBESTOS TESTING LAB LIST

Congoleum Pacemaker identifying stamp on the back of the sheet flooring.

1978 Congoleum Pacemaker sheet flooring (C) InspectApeda.com Hans

Watch out: often the white backer on older resilient flooring or sheet flooring like that shown above contains asbestos.

Reader follow-up:

Not even sure it'd be worth it at this point. I guess I need to get the flooring tested, too. I hate this.

Moderator reply:

Or instead of testing, if it's all DIY, you could simply assume the floor contains asbestos and handle it accordingly.

Congoleum Sheet Flooring Backer Text - Australia 1970's - Asbestos?

Congoleum sheet flooring, Australia (C) InspectApedia.com

This Congoleum sheet flooring and the photographs of text on the flooring backer were observed in an Australian home. The design pattern looks like some older sheet flooring whose backer contained asbestos. But we're not sure where nor just when this particular floor covering was produced.

The pattern shown above does not appear in the current (2016) Congoleum sheet flooring catalogs scanned online at the company's website.

However the reference to Seam Sealer SU 106 suggests that this might be a more-recent Congoleum flooring product. If so it would not be expected to contain asbestos. Thanks to readers L and G.R. 2016/03/31

Congoleum sheet flooring, Australia (C) InspectApedia.com

Above: text indicating that seams of this flooring product should be sealed with Congoleum SU106 seam sealer. Congoleum's SU106 seam sealer is a current product (2016). This product is applied on top of the seam of Congoleum sheet flooring that has already been joined below using QuikStik adhesive tape.

(You'll need to protect the sealed Congoleum floor seam from foot traffic for at least 16 hours.) This same seam sealing product can be used to repair small areas of damaged or torn flooring.

Below: close-up photo of text on the "back" of Congoleum sheet flooring.

Congoleum sheet flooring, Australia (C) InspectApedia.com

Modern, contemporary Airstep Congoleum sheet flooring seams are sealed with a Congoleum seam sealer kit and are used with Congoleum and IVC Flexitec vinyl floor coverings.

The company provides an adhesive sealer for sheet flooring and a "QuikStik tape used for loose-laid flooring seams and to adhere the perimeter of sheet flooring to the subfloor.

Sheet flooring can also be stapled down to wood floors or subflooring around its perimeter if those edges are to be covered by a wood floor trim.

See details at ASBESTOS PRODUCTS in AUSTRALIA

Reader Comment: photos and testing results of 1960s Australian flooring

I discovered 9” by 9” vinyl tiles under my kitchen flooring recently in Victoria, Australia in my 1960’s home. Had them tested and all layers including tile, hessian backing, blue paper/felt and adhesive came back with no asbestos detected.

Happily pulling them up now and they have “NAIRN-AUSTRALIA” printed on the back. Did a bit of digging online and found a Nairn Australia catalogue from 1961 which had a few different tiles available, some of which contained asbestos in the catalogue, but luckily the builder used the non-asbestos type in my home. - On 7-13-2024 by Oliver

1960s Australian Nairn non asbestos flooring, backing, adhesive (C) InspectApedia.com Oliver

And although difficult to read, here are two pages from the Royal Australian Institute of Architects Yearbook 1961-1962, showing references to asbestos in some Nairn flooring products. Thanks to Oliver for this reference.

Royal Australian Institute of Architects Yearbook 1961-62 Cited and discussed at InspectApedia.com ...

ROYAL AUSTRALIAN INSTITUTE OF ARCHITECTS YEARBOOK 1961-1962 [PDF], provided by Trove, retrieved 2024/7/14 at https://nla.gov.au/nla.obj-3130302690/view?sectionId=nla.obj-3135983866&partId=nla.obj-3130423728. Trove is a collaboration between the National Library of Australia and hundreds of Partner organisations around Australia. They provide collections from Australian libraries, universities, museums, galleries and archives. https://trove.nla.gov.au/

Royal Australian Institute of Architects Yearbook 1961-62 Cited and discussed at InspectApedia.com

Question: 1979 Congoleum The No Wax Shiny Vinyl - 20% Chrysotile Asbestos

Congoleum No Wax Vinyl 20% Chryotile Asbestos (C) InspectApedia.com Debbi M

I appreciate your website and have spent an extensive amount of time researching a flooring that we're removing from our house.

We got halfway through the floor removal before we realized we should worry about asbestos (yikes!).

I've ordered an in-home test kit but in the meantime I wondered if you had any thoughts on the attached photos?

Our home was built in 1979. The kitchen and dining room was covered in 12-foot wide vinyl sheet flooring made by congoleum.

On the backer, which is white, the Congoleum name appears, along with what appears to say "The No Wax Shiny [vinyl?]" There's something written above congoleum but I cannot make it out.

I appreciate any help or direction you can give us.

Also, I thought it would be helpful to future viewers of your website to see another sample. - Anonymous by private email 2018/12/03

Reply:

Congoleum no wax vinyl floor containing asbestos - 1979 (C) InspectApedia.com Debbi

With no other more precise date information you need to either treat the floor as presumed to contain asbestos or have a sample tested.

If you can remove the floor without making a dusty mess you might eschew testing.

Reader follow-up: 20% chrysotile asbestos in this Congoleum No-Wax vinyl flooring

Congoleum no wax vinyl floor containing asbestos - 1979 (C) InspectApedia.com Debbi

Just an fyi...this flooring came back 20% chrysotile asbestos in the flooring itself, none in the mastic glue.

Reply: thank you

Thank you Anon. Other readers will benefit from your report confirming asbestos in this 1979 Congoleum No-Wax Shiny Vinyl sheet flooring.

In my experience often the white backer of sheet flooring from the 1970's contained Chrysotile asbestos.

If the flooring adhesive can be dissolved - sometimes by mere water - enough that the flooring can be rolled-up and removed, you will have avoided creating potentially-hazardous asbestos-contaminated dust.

Mod.


...

Continue reading  at 1980 CONGOLEUM NO-WAX SHEET FLOORING - With Asbestos-Content., or select a topic from the closely-related articles below, or see the complete ARTICLE INDEX.

Or see this

Article Series on Congoleum Flooring

Suggested citation for this web page

1970's CONGOLEUM FLOORING at InspectApedia.com - online encyclopedia of building & environmental inspection, testing, diagnosis, repair, & problem prevention advice.

Or see this

INDEX to RELATED ARTICLES: ARTICLE INDEX to ASBESTOS HAZARDS

Or use the SEARCH BOX found below to Ask a Question or Search InspectApedia

Ask a Question or Search InspectApedia

Share this article:

Search the InspectApedia website

Need to make a private comment? Email editor@inspectApedia.com. We welcome email with your website content critique, corrections, suggestions or questions. Email is monitored daily but our workload may prevent an immediate reply. For immediate results, we hope you'll first try asking your question using the search box just above.

Citations & Reviewers

In addition to any citations in the article above, a full list is available on request.

  • NC, Forsyth Co. Asbestos Forsyth County Office of Environmental Assistance and Protection (Office), Winston-Salem NC - retrieved 2026/09/02, original retrieval 12/08 discusses handling asbestos in a single family dwelling including requirements for permits for renovation, demolition,etc.
    Excerpt:
    The information provided on this webpage is specific to rules governing asbestos under NESHAP. 
  • MN DOH, Asbestos Floor Tile Removal (Minnesota DOH Website) (2024) the University of Minnesota's advice on removing VAT (vinyl asbestos or asphalt asbestos floor tile)
  • In addition to citations & references found in this article, see the research citations given at the end of the related articles found at our suggested

    CONTINUE READING or RECOMMENDED ARTICLES.


ADVERTISEMENT