Gas Fireplace Direct Vent Termination Cap Clearance DistancesDirect vent chimneys or exhaust for gas fireplaces & gas fireplace inserts:
This article gives typical clearance distance requirements between the termination cap of a gas fireplace or fireplace insert and other building or site features such as windows, doors, other mechanical system components, air intakes, exhausts.
This article series describes side wall vent systems for conventional & mid-range-efficiency heating boilers, furnaces & water heaters. We include for comparison, low temperature side wall vent systems used by high efficiency or condensing boilers, furnaces & water heaters.
InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers, products, or services discussed at this website.
- Daniel Friedman, Publisher/Editor/Author - See WHO ARE WE?
The clearance distances shown above and at the top of this page are between the vent termination cap of a gas fireplace and the air inlet side of an A/C or heat pump compressor/condenser.
At CLEARANCE DISTANCE, HVAC a reader commented that his building inspector did not accept the safety of this installation.
We agreed.
Watch out: Reviewing manufacturer's installation instructions for a typical gas fireplace direct-vent exhaust termination cover or cap we find that the clearance distances to other building features or mechanical systems are similar but not necessarily identical to the Direct Vent Gas Appliance clearances given
in GAS APPLIANCE / HEATER DIRECT VENT CLEARANCES
This may be because that a typical gas fireplace heater does not use a power-exhaust vent or also because of different BTUH ranges.
Minimum Clearance Distance Requirements for the Exterior Vent Termination of a Gas Fireplace Heater8 |
||
| Direct vent gas fireplace exhaust termination item clearance distance | Distance required (Canada)1 | Distance required (USA)2 |
| Clearance above paved sidewalk or a paved driveway located on public property | 84" (2.1m)3 | [Note 5] |
| Clearance to a mechanical air supply inlet 3' (91cm) above if within 10' (3m) horizontally |
72" (1.8m) | 36" (90cm)5b |
| Clearance distance from gas vent termination cap to adjacent building | 48" 8 | |
| Clearance distance from gas vent termination cap to any mechanical air-supply inlet | 48" (Travis 2016) | |
| Clearance to the side of any non-mechanical supply air inlet | 36" (Travis 2016) | |
| Clearance to each side of center line extended above [the gas] meter/regulator assembly | 36" (90cm)5a | [Note 5] |
| Clearance to gas service or gas meter regulator vent outlet | 36 " (90cm) | [Note 5] |
| Clearance above any non-mechanical supply air inlet | 36 "(Travis 2016) | |
| Clearance distance to bushes, garden sheds, fences, decks or utility buildings | 24" (Majestic 2016) | |
| Clearance distance horizontally to any surface such as exterior walls, for vertical terminations | 24" (Travis 2016) | |
| Clearance distance to any vinyl surface | 24" (Travis 2016) | |
| Vertical clearance to ventilated soffit located above the terminal within a horizontal distance of 2 feet (61cm) from the center line of the terminal (check with the local code) |
18" (46cm) | 18" (46cm) |
| Clearance below a veranda, porch, deck or balcony (must have two open sides) | 18" (Travis 2016) | |
| Clearance below ventilated soffits | 18" (Travis 2016) | |
Clearance to or below any unventilated soffit or below any roof surface |
15" (38cm) | 15" (38cm) 11" (Travis 2016) |
| Clearance distance above the roof line (for above-roof vents) | 12" (Travis 2016) | |
| Clearance distance to vinyl surfaces such as vinyl siding or vinyl trim | 12" 8 | |
| Clearance above any grade, veranda, porch, deck, or balcony | 12" (30 cm) | 12" (30 cm) |
| Clearance to window or door that may be opened | 12" (30 cm) | 9" (23 cm)8 |
| Clearance to permanently closed window | [Note 5] | [Note 5] |
| Clearance to outside corner / corner walls: with approved Termination Caps | 12" (30cm) | 12" (30cm) 3" (Travis 2016) |
| Clearance to inside corner: with approved Termination Caps | 12" (30cm) | 12" (30cm) |
| Clearance to roof eaves | 6" (Travis 2016) | |
| Clearance to outside corner: with Manufacturer's Special Termination Cap 6 | 6" (15cm)6 | 1-6" (15cm)6, 8 |
| Clearance to inside corner: with Manufacturer's Special Termination Cap 6 | 6" (15cm)6, 8 | 1-6" (15cm)6, 8 |
| Clearance to non-mechanical air supply inlet to building or the combustion air inlet to any other appliance | 12" (30cm) | 9" (23 cm) |
| Clearance under balcony, porch, or veranda | 12"(30cm)4 | [Note 5] |
| Clearance from outside corner walls | 3" (Travis 2016) | |
The table of gas fireplace vent clearances above is derived from the codes, standards, and example gas fireplace installation manuals cited in this article.
Watch out: the final legal authorities for acceptable clearance distances from the direct vent opening/hood on a gas fireplace to building features are the manufacturer of the specific gas fireplace (see the I&O manual for your fireplace) and your local building code inspector.
Be sure to check the Installation & Operation manual for your fireplace as the manufacturer's specifications could differ from the gas fireplace vent opening clearances table above.
Notes from the original source cited below:
1. CSA B149.1, Natural Gas and Propane Installation Code
2. ANSI Z223.1/NFPA 54, National Fuel Gas Code
3. A vent shall not terminate directly above a sidewalk or paved driveway which is located between two single family dwellings and serves both dwellings.
4. Permitted only if veranda, porch, deck, or balcony is fully open on a minimum of two sides beneath the floor.
5. Clearance in accordance with local installation codes and the requirements of the gas supplier
5.a 3 feet (91cm) within a height of 15 feet (4.5m) above the meter / regulator assembly
5.b 3 feet (91cm) above - if within 10 feet (3m) horizontally
Additional Notes:
6. This is the author's OPINION considering that heat from the gas exhaust vent blowing onto an A/C compressor unit condensing coil could impact the coil's ability to condense refrigerant back to liquid form, affecting the condenser unit's efficiency and life. I'm considering the situation in which the hot gas exhaust blows onto the air intake side of a condensing coil.
(Most modern condenser units draw cooling air in from the unit sides and push it out the unit's top). Also
7. This is a Regency Fireplace Products termination cap; other manufacturers may have similar options. See the additional sources below.
8. Watch out: check with the manufacturer of your heater and venting system for specific venting instructions and clearances to combustibles or to other features as these distances may vary from one appliance and manufacturer to another. For example the Travis Industries direct vent clearances include some distances that are different from the tables given above.
DuraVent (and other manufacturers) warn that if a gas appliance, fireplace heater or other heater is not properly installed the system may be unsafe.
A major cause of vent related fires is failure to maintain clearances (air spaces) to combustible materials. It is of utmost importance that double wall direct vent pro be installed only in accordance with these [the manufacturer's] instructions.
Above: a gas log fireplace operating in San Miguel de Allende, Mexico. [Click to enlarge any image]
The photographs shown here illustrate the cutting of a direct vent opening to the building exterior that, combined with a small exhaust fan, allowed the operation of a gas log fireplace in a masonry fireplace that had previously been served by an actual masonry chimney. The chimney was removed and its bottom opening blocked-off by previous building owners when an upper floor addition was constructed.
Watch out: At least some, but depending on where you buy them, not all gas log fireplaces now include an O2 depletion sensor intended to shut down the fireplace should the indoor oxygen level fall too low.
Photo above: covering the gas log fireplace during cutting of an exterior vent opening.
But a best installation of an indoor gas fireplace heater or gas log fireplace will include provision for outside combustion air as well as for exhausting the combustion gases to the building exterior.
Providing plenty of outdoor combustion air helps reduce the risk of both dangerous CO (carbon monoxide) production and also the risk of oxygen depletion that could kill building occupants.
Photo below: exterior view of an opening cut to exhaust the gas log fireplace shown above.
Watch out: do not even think about modifying or using a gas log fireplace without being sure that you have properly located, installed, and tested carbon monoxide detectors (as well as fire and smoke detectors) in your building; otherwise there is risk of fatal carbon monoxide poisoning.
We have observed that even when running supposedly safe gas log fireplaces that did not have a direct powered vent to the building exterior of the building CO detectors sounded off, telling us that there was dangerous carbon monoxide accumulating indoors.
Photo below: at a similarly vented gas log fireplace we illustrate using a conventional screen to prevent insects or other pests from entering the building through the vent opening. Because this vent is in a sheltered location, protection from wind and rain were not necessary. Other photos and text on this page illustrate using a listed, manufacturer-supplied direct vent exhaust termination cover for other gas fireplace products.
Watch out: even with an adequately-sized vent opening you may find, as this installer did, that a small exhaust fan was needed to assure that combustion gases from the gas log fireplace vented to the outdoors rather than back out of the fireplace front opening into the occupied space.
That's because when you eliminate the chimney you remove the source of updraft and thus natural venting that a chimney provides and that a hole in the side-wall does not.
Watch out: have your gas log fireplace and any venting changes you or your contractor design inspected and approved by your local fire and building inspectors to be sure the vent system and combustion air provision are safe and adequate.
...
Below you will find questions and answers previously posted on this page at its page bottom reader comment box.
Does my direct vent gas stove exhaust require a cap/shelter hood of sorts to protect from the elements? (The old contraption above it will be removed and serves no purpose currently) On 2021-06-08 by Melinda
by danjoefriedman (mod)
@Melinda,
A direct-vent gas appliance wall termination like that in your photo, provided you used all of the parts and installed it following the manufacturer's directions, is intended to be able to be exposed to the weather.
In your photo the installation is improper - lacking clearance from what looks like wood combustibles - until you remove the remains of that old chimney and its brackets.
Hello we are currently building a covered patio and the edge of it is getting pretty close to the fireplace vent. Would this fail any home inspections if we decide to sell the home in the future? On 2021-05-07 by Brian
by danjoefriedman (mod)
@Brian,
In my OPINION your vent is a bit close to framing and may also be a bit close to an operable window (9" U.S. or 12" Canada).
The concern would be more-immediate than a re-sale issue and is rather one of safety and possible admission of flue gases into the building interior.
Remember that it's your local building code official who is the final legal authority on this question; ask her for an opinion and let me know what she says.
Is there a minimum distance between brick houses in Toronto for venting termination of a fireplace using direct vent? - A.W., 12/30/2012
Reply: 4 feet or local codes
I have not found building code citations that refer to nearby or adjacent buildings when specifying clearances for direct vent fireplaces, though some of the fireplace installation manuals we reviewed specified a minimum of four feet to the nearest separate building.
It seems likely that your local building code inspector would agree that the clearance requirements for the building in which the fireplace is installed would set the minimum acceptable clearances that would then apply also to a nearby or adjacent building.
In other words, if the fireplace vent distances and position relative to your own building windows or doors were LESS THAN those to the windows & doors on the building where the fireplace is installed, and presuming for a moment that the fireplace was installed properly, meeting local building permit and code requirements, then a violation probably exists.
If the fireplace vent distances and position relative to your own building windows and doors is GREATER THAN those to the windows and doors where the fireplace is installed, and presuming for a moment that the fireplace was installed properly, meeting local building permit and code requirements, then a violation probably does not exist.
Take some some sharp photos of the installation that concerns you, or make a sketch and send those along and we may be able to comment further.
Hello i had a metal flashing installed above my vent will this be okay? On 2020-12-16 by Vinny
by (mod) - NO: never obstruct the gas fireplace vent outlet
Vinny:I’m raising my fire place. Can I leave the exhaust at a downward slope or do I have to cut into my exterior wall and raise the exhaust vent to keep the exhaust pipe level? On 2020-12-12 by John
by (mod) - No do not ever vent your gas fireplace through a vent that slopes "down"
John:
Watch out: No, do not ever vent your gas fireplace through a vent that slopes "down". Doing so is unsafe and could risk fatal carbon monoxide poisoning.
Check the installation instructions for your own brand and model gas fireplace, but here is an example installation instructions - these and others are found
at GAS FIREPLACE / LOG MANUALS using this example:
BLAZE KING GAS FIREPLACE HEATER MANUAL [PDF], Clarity Model CL2118 . SP
Excerpt:
Watch out:
NOTE: ALLOWING HORIZONTAL VENT PIPE TO SLOPE DOWN TOWARDS THE VENT TERMINATION COULD CAUSE POOR COMBUSTION AND/OR HIGH TEMPERATURES THAT MAY PRESENT A FIRE HAZARD.
What is the minimum vertical distance I can install a direct vent fireplace vent below an existing direct vent fireplace vent? On 2020-12-08 by Scott
From the table provided, it states "Clearance to non-mechanical air supply inlet to building or the combustion air inlet to any other appliance" is 9" in US. I see the same information in the fireplace manual. Is this the correct code I must follow?
by (mod) -
I don't think so, Scott as you are describing two outlet vents, not an air intake vent next to an outlet vent.
As both vents are outlets I have not seen a specification for how close they can be together.
However you might want to consider increasing, even doubling, the clearance distance from your pair of outlet vents to any building air inlet as you've doubled the outflow volume.
I hate having to duck and weave on a question for which we can't find an authoritative answer, but in such cases we're left with "Check with the manufacturer of your specific direct vent fireplace - as their customer support or engineering department may have an additional specification for your case. "
For example the Valor Horizon DIRECT VENT GAS FIREPLACE / HEATER MANUAL l [PDF] given above on this page specifies a minimum of 72" to a mechanical air inlet but that's assuming a single direct vent heater outlet.
And none of the installation guides I've reviewed discuss juxtaposition of two or more direct vent gas fireplace or other fireplace exhausts. So we don't know if simultaneous operation of your two (or more) direct vent fireplaces will cause interference between them and thus a safety hazard.
Beyond "check with the manufacturer" it also makes sense to double check that fire, smoke and CO detectors are properly installed and tested.
Tell us the brand and model of your fireplaces and perhaps we can find more specifics.by Scott
Thanks for the input. I was using this referenced code since both of the direct vent fireplaces are using coaxial pipes for the intake and exhaust air from the fireplaces. There would, therefore, be an intake at the locations along with the exhaust. I will see what information I can get from Heat&Glo.
by (mod) -
Aha
Thanks for that clarification.
I'd be a little worried about interference; the manufacturer probably has a separation guideline as they've probably had other installations where multiple fireplaces are installed close to one another.
Please let me know what they suggest as that will help other readers.
You mentioned that side vent caps can get very hot while fireplace is in use. How hot? Do I need to worry about my children burning their hand if touched? On 2020-10-28 by John by (mod) - direct vent gas fireplace terminations may be very hot
Yes, John s
Watch out: some caution is in order, though I think that not all side vent terminations get burning hot.
At least some fireplace vent caps are embossed with a"HOT" warning.
An example is this Pro Square direct vent cap shown here, and plainly marked HOT
I take that to mean that the manufacturer is warning you of a burn hazard.
I thought about building a storage shed in this dead space for my winter equipment and tires.
If I were to build it similar to my neighbor's, my gas fire sidewall vent is in the way and don't believe it would be a safe thing to have it encapsulated in the shed once it's all built.
Is it possible to redirect and extend out the vent so it's 24" above the shed roof?
As well, is it safe for me to leave the furnace flue pipe in the shed? Thank you On 2020-06-30 by Joe
Suggestions by (mod) -
Joe, thanks for a helpful gas venting question.
Depending on the length and number of bends (kept to a minimum) you may be able to extend the gas vent.
Let's start by identifying the brand and model heating equipment that's being vented,
then
let's get a hold of the IO manual for that equipment.
There the manufacturer will give us the permissible routing length, elbows, fire clearances.
Also see
DIRECT VENT INSTALLATION, SNAFUS & SPECS Watch out: that toddler could get a nasty burn if she or he touches the direct vent cover - that can be quite hot. Prevent access by children.
Could a vertical vent cap be located or mounted inside a cupola? Or, turn out 90 degrees on the back side out of view? On 2020-05-09 by Dave K.
(mod) -
Possibly, Dave provided
- you respect the manufacturer's specifications on fire clearances
and
- you respect the manufacturer's specifications on sufficient vent opening such that the venting is not reduced or obstructed
Venting for a new direct vent fireplace was dented during installation. Does this pose a fire risk? On 2020-04-27 by Barbara
Opinion / answer by (mod) - more likely an exhaust blockage or operating hazard + other subtle risks
Barbara
The best people to ask are the manufacturer.
In my OPINION there could be a subtle, perhaps long-term hazard of cracking and leaks in the vent when the vent is combined with thermal stresses.
I can't say if the dent is sufficient to impede venting,
(I suspect not)
and most important,
I can't say a thing about whether or not this vent is fire-safe. Does it meet the clearance to combustibles specified by the manufacturer?
To answer the question we'd need to know the brand and model of direct vent fireplace and thence to see the clearances in the IO manual.
I hope that your installer left that manual with you - as they should have, but if not, one can obtain a copy from the manufacturer.
I want to install a hot tub near my house, but there is a fireplace exhaust vent there.
How much distance do I need to leave? I tried to attach a picture to help describe the exhaust vent. Thanks On 2020-04-14 by Bev
Answer by (mod) - gas fireplace sidewall vent clearance distance to hot tub & to deck surface
Bev,
You don't give the hot tub construction materials, but a general guide would be no less than 24" clearance from the nearest surface of the vent to the hot tub.
Watch out: I would prefer a greater distance considering that if the fireplace is in use and people are using the hot tub, even though you may have met the manufacturer's specifications (let's check the clearances for your specific fireplace and its vent system for your brand and model- that you've not yet given) -
... still there could be a gas exposure or odor or exhaust safety issue for people using the hot tub.
Watch out: your vent may already be improperly located and unsafe if it doesn't meet the 12" or more clearance above the deck surface.
Please check the vent clearance distances given in the tables above on this page and don't hesitate to ask follow-up questions as needed.
"6. This is the author's OPINION considering that heat from the gas exhaust vent blowing onto an A/C compressor unit condensing coil could impact the coil's ability to condense refrigerant back to liquid form, affecting the condenser unit's efficiency and life.
I'm considering the situation in which the hot gas exhaust blows onto the air intake side of a condensing coil."
I doubt anyone will be using their gas fireplace at the same time their AC is running. But who knows. On 2019-08-07 by Frederico Fredericks
by (mod) - yes
Frederico
Good question, thank you.Be warned, however that we cannot guess at all possible use combinations and circumstances for any HVAC or heater or fireplace use. Your comment expresses common sense - something that is not 100% assured.
We might also worry about a home that has not a simple air conditioner but a heat pump - that runs in cold weather, the same time as one might use a gas fireplace.
We might also be concerned about corrosive effects of gas fireplace exhaust on an A/C or heat pump's condensing / evaporating coil.
Hello we had Valor Horizon DV gas fireplace insert installed in our basement. This is our 2nd one, last one was over 20 yrs. No problems. New vent sits lower outside than previous. Partly below grade.
Shouldn't there have been a drain installed to help with water? Thank you. russmacintosh@rogers.com On 2019-03-22 by Macintosh
by (mod) - Direct Vent Gas Fireplace clearances and slope and height to avoid water damage to the vent
Here is the Valor Horizon DIRECT VENT GAS FIREPLACE / HEATER MANUAL l [PDF] if you don't already have a copy
The vent must be at least 12" above grade level - per the manual p. 24
As shown in your drawing water can enter the vent assembly causing rust, damage, safety concerns.
I have a builder building a home for me with a direct vent fireplace in the great room. He vented the fireplace outside to an area they call the lanai which is an area under the second floor of the home.( approx. 11'-0 from the outside of the building).
This seams like a very dangerous practice as the exhaust gases can and probably will gather under the roof and then seep into the area above the vent into the second floor of the house. Also there is a door to the great room very close to the vent I believe gas fumes can also seep into the great room .
Does this sound like a bad situation to you .
The builder has installed these fireplaces in the same house at least 4 or 5 examples I have seen and ran a chimney up through the house like I expected On 2019-01-16 by John Revtai
by (mod) - direct-vent fireplace manufacturer's clearance distance specifications
John
the table in the article above gives a summary of all of the direct-vent fireplace manufacturer's clearance distance specifications I've found.
The manufacturer can't anticipate every possible installation situation, so for a question such as yours, which I consider perfectly reasonable, the best approach would be to
1. identify the brand and model of your direct vent fireplace
2. find the installation and operation manual for that fireplace
Check GAS FIREPLACE / LOG MANUALS
as we may have already provided that information.
3. Use the manufacturer's contact information to give their technical support line a call.
4. Let me know what you are told, and post a photo of your installation inside and outside, and we can comment further.
...
Continue reading at DIRECT VENTS / SIDE WALL VENTS - topic home, or select a topic from the closely-related articles below, or see the complete ARTICLE INDEX.
Or see GAS APPLIANCE DIRECT VENT CLEARANCE FAQs - questions & answers posted originally at the end of this page.
Or see these
GAS FIREPLACE VENT CLEARANCE REQUIREMENTS at InspectApedia.com - online encyclopedia of building & environmental inspection, testing, diagnosis, repair, & problem prevention advice.
Or see this
Or use the SEARCH BOX found below to Ask a Question or Search InspectApedia
Ask a Question or Search the InspectApedia website using the box just below.
Need to make a private comment? Email editor@inspectApedia.com. We welcome email with your website content critique, corrections, suggestions or questions. Email is monitored daily but our workload may prevent an immediate reply. For immediate results, we hope you'll first try asking your question using the search box just above.
In addition to any citations in the article above, a full list is available on request.