Air conditioner or heat pump compressor burn-out diagnosis & repair:
This air conditioning repair article discusses the how to diagnose and replace a burned out air conditioner compressor, including evaluation of air conditioner compressor noises, hard starting, lost cooling capacity, and detection of a burned out compressor or A/C compressors at or near end of their life.
Here we catalog and describe the causes of air conditioner or heat pump compressor failures and we suggest compressor motor diagnostic steps.
InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers, products, or services discussed at this website.
- Daniel Friedman, Publisher/Editor/Author - See WHO ARE WE?
When is a compressor at or near end of its life? Criteria for deciding that an air conditioner, heat pump, or refrigeration compressor needs to be replaced.
Hard starting air conditioner compressor. Increased air conditioning electrical bills. Air conditioner compressor defect diagnosis & repair guide.
Air conditioning condenser unit fan diagnosis/repair.
When to replace a failing or failed A/C or heat pump compressor. Common causes of A/C or heat pump compressor motor failure
When a sealed compressor motor has "burned out" this means that the internal wiring of the motor has become irreparably damaged: the compressor motor windings may be burned and shorted together or shorted to the steel shell of the motor, or the windings may have burned and simply become "open" or disconnected. If the motor has burned out in either of these ways it needs to be replaced.
When an air conditioner / heat pump compressor can no longer develop proper pressures, even if its electric motor has not burned out, the unit will still need to be replaced. Below we give refrigerant pressure details that help make this decision.
Air conditioner failure warning signs: Before an air conditioning compressor fails solid you may notice that the unit is hard-starting, particularly when starting against a head pressure - someone switched the system off while the compressor was running, then tried turning it right back on. The result can be a damaged or destroyed compressor motor.
At REFRIGERANT FLOODBACK, LIQUID SLUGGING we explain how liquid refrigerant entering a heat pump or air conditioner compressor motor can destroy it and we discuss the recommended time that the system should be LEFT OFF if was switched off while it was running
See CAPACITORS for HARD STARTING MOTORS
and
see MOTOR OVERLOAD RESET SWITCH.
Another sign of a failing air conditioning compressor is noisy motor operation, such as buzzing or clanking sounds coming from the outside unit housing the compressor motor.
See NOISES, COMPRESSOR CONDENSER.
Another sign that might indicate a failing air conditioner compressor motor is an increase in the building's electrical bills even though the air conditioning system "on" time has not changed.
See TIGHT or SEIZED AC COMPRESSORS where we provide additional details about examining and measuring A/C and heat pump compressors to continue compressor condition diagnosis.
Watch out for shock hazards or equipment damage:
The compressor won't start, perhaps just hums, and the motor star/run capacitor(s) are ok or you've tried replacing that part
As soon as the compressor tries to start the circuit breaker trips or fuse blows. The compressor motor has burned out, is internally shorted or grounded. A service technician will use a VOM and typically will find low resistance (low Ohms) between one or more compressor terminals and ground.
A VOM connected to the compressor circuit indicates that no current is being drawn, but the condenser fan is running properly.
Watch out: before assuming that the compressor motor is bad, when the unit won't start at all, check for a loose or disconnected electrical connection or a bad contactor relay. An overheated motor may also leave the compressor motor "off" due to a tripped internal overload switch or a switch that has simply failed.
If this is the problem, the motor should start normally once the unit has cooled down. (Some readers describe spraying water on the condenser unit to speed cooling - (don't wet electrical switches & components.)
Watch out for shock hazards or equipment damage:
When an air conditioning compressor has "burned out" by shorting of internal components - it will fail to start at all. This failure is detected by disconnecting all power and wiring from the unit and measuring resistance (ohms) between the motor start/common and run/common terminals.
Meaning of Zero resistance: If there is zero resistance there is (probably) no break in the wire or circuit being tested. Zero resistance also can mean that wires are shorted together or are shorted to ground.
Watch out: while finding very low or zero resistance would be normal for a simple length of electrical wire, for some circuits and equipment, finding low or no resistance where there should be some can indicate a short circuit. Another problem to watch for is testing electric motor windings; a winding may appear intact, with low resistance, but it may open (showing high or infinite resistance) only when the motor begins to spin.
More details are just below and also
at ELECTRIC MOTOR DIAGNOSTIC GUIDE.
Meaning of Infinite resistance: If you measure the resistance across a compressor winding and your meter's needle is stuck over at infinity, or "OL"/"OVER" on a digital meter, that would indicate the compressor winding is open (burned through). The same effect can be observed from simply connecting the meter to absolutely nothing.
Typically if just one winding is "open" you'll see infinite resistance at one check point and in contrast (for the non-open windings) you will read zero resistance ("continuity") between the Common terminal and the Start or between the Common terminal and Run terminal.
Low resistance: If the resistance measured across the air conditioning compressor winding is too close to 0 ohms, it's shorted.
The compressor should blow the fuse or trip the circuit breaker when power is turned back on. But watch out: we get field reports of equipment burn ups and even fires when the air conditioning circuit breaker for the compressor happens to be an old FPE Stab-Lok or Zinsco unit.
If there is resistance but not infinite resistance between the motor terminal and the motor casing, the motor has become shorted to ground internally and the unit needs to be replaced.
If there is no resistance between the start and run terminals to common, but there is resistance between the start and run terminals, this means that the internal motor overload protection circuit is open. In this last case, allow the motor to cool and re-test it before replacing it.
See COMPRESSOR MOTOR REPLACEMENT.
For details about measuring RLA / FLA, and definitions of RLA, FLA, and LRA,
see TIGHT or SEIZED AC COMPRESSORS
2016/09/10 johnteh said:
I had the summer A/C inspection done was told the compressor capacitor was indicating a short life because the compressor mega ohms was 200 which is very low for a unit that is only 2 years old. recommendation was to replace compressor capacitor with a hard start to prolong compressor life.
Are compressor capacitors difficult to replace/install? They don't seem to be, since they have only 2 wires.
This question was posted originally
at CAPACITORS for HARD STARTING MOTORS
Jon
Start capacitors are usually easy to install as they're external to the motor and the wiring is pretty obvious.
Details about choosing and replacing an electric motor or AC compressor motor start/run or hard-start capacitor are
at CAPACITORS for HARD STARTING MOTORS
But I'm confused about the compressor diagnosis. Very low resistance across a compressor motor is not a diagnostic I understand. High current draw (measured in amps not ohms) is a well-known indicator that a motor is struggling and may indicate failing or seizing bearings and thus end of life.
Ron Walker, over at hvactrainingsolutions.net gives this nice summary of AC Compressor troubleshooting by measuring resistance across air conditioner or heat pump motor windings from which we excerpt and expand.
Mr. Walker notes that these measurements are difficult to obtain as the compressor motor wiring connector can be itself hard to access and he suggests obtaining an old motor wiring harness and connector plug to extend the wires out to where you can reach them - a great idea.
Ohms measurements across the windings terminals of a good electric motor such as is used in an air conditioner or heat pump system will read something like this:
Mr. Walker adds that:
If any of these readings read infinite or over range on your ohm meter, you have an open winding. A reading of zero ohms indicates a short in a winding.
Very high or infinite resistance across the windings of a motor would typically indicate that a winding wire is broken. What's tricky about this motor winding resistance measurement in ohms is that a winding wire may be damaged but may "open" or "break" only when the motor is trying to spin or only when the motor gets up to full speed.
So you can see that NONE of these air conditioner or heat pump motor ohms test measurements is even close to 200 Ohms and that to me, 200 ohms sounds high, not "very low".
Before trusting such a measurement I'd be checking my ohm-meter, probes, quality of contact, and other measurement conditions including of course that power is OFF and disconnected from the motor.
A different air conditioner / heat pump compressor (or fan) motor test that involves measuring resistance is a check for shorted motor windings. Measuring between each motor pin and ground (typically the compressor motor case) should give "infinite" resistance, meaning no current is flowing. If you see some lower resistance with the -to-ground measurement then there's an internal short.
Before changing the start/run capacitor - which may be fixing the "wrong problem"
- I suggest that you give the service manager at your AC repair company a call and that you ask for clarification and if needed, ask for a visit from a senior, experienced HVAC technician.
Either there has been a misunderstanding or what your tech told you needs some further explanation vis-a-vis what other experts say about AC troubleshooting by measuring ohms across motor windings.
Watch out: for a mechanically frozen compressor: a compressor may pass all of these electrical tests and still require replacement. The tests above only test electrical connections and windings. An air conditioner or heat pump or refrigeration compressor that has jammed up mechanically internally will still refuse to start (perhaps will hum) when all of the electrical tests, contactor relay, start capacitor, etc. are tested as perfectly fine.
A compressor with broken internal parts may also not be frozen, that is its internal electrical motor may start and run, but the compressor fails to produce any refrigerant pressure at its outlet side. In this case internal parts or valves in the unit have broken without jamming the motor itself. In this case, all of the electrical components and tests will look "OK".
A compressor with broken internal motor mounts may make a rattling or clanking sound and needs replacement. It will continue to run but could become shrapnel at any time.
A compressor with bad internal valves will continue to run but is inefficient and should be replaced. The symptom is very quick equalization of high and low side pressure as soon as the motor stops.
Some compressor motor failures are so apparent that there's no question: an electric motor burnout that draws high amps or is internally shorted, for example.
But what about a compressor motor that may be just "worn" ? An HVAC compressor should be able to pull at least 15" of vacuum against 100 psi head pressure or else it is inefficient. Of course to make this test you must be able to isolate the compressor from the rest of the cooling or heat pump system, so this test is not rapidly made in the field.
Bad air conditioner reed valves will be unable to pull pressure down on the low side of the system. A leaky discharge reed valve (on the compressor output side) pulls hot gases back into the compressor cylinder and recompresses them, causing abnormally high head pressures at the compressor motor. And as a result the compressor won't be able to move vapor.
In sum, HVAC compressors do fail and need replacement, but only when you have tested and ruled out the other 80% of the causes of common air conditioning, heat pump, or refrigeration problems (usually electrical in nature) do you go ahead and replace the compressor unit.
Details of compressor/condenser unit fan inspection, diagnosis, and repair are
at FAN, COMPRESSOR / CONDENSER UNIT. Basic advice follows:
A failed compressor/condenser fan can cause the air conditioning system to shut down due to an overheating compressor or excessive pressures developed inside the compressor. If your compressor/condenser unit does not include a safety override switch to perform this shutdown and if the condenser unit fan is not working, your compressor motor may be permanently damaged.
at NOISES, COMPRESSOR CONDENSER we include some condenser fan noise problems are traced to the cooling fan motor, bearings, fan blades, obstructions, etc.
Watch out: if your compressor/condenser unit motor is running but the fan itself is not blowing air, the system will not work and may be seriously damaged. The outdoor cooling fan or condenser unit fan is needed not only to cool high pressure, high temperature refrigerant in gas form so that it can condense back to liquid form.
That cooling step also cools down the compressor itself and keeps the compressor internal pressure from becoming too high. Most modern compressor / condenser units include an overpressure sensor that will shut the equipment down if compressor pressures become too high. Some older models and some modern economy air conditioner compressors may lack this function.
Example: testing a blower fan motor winding: referring to the electrical diagram for your equipment, unplug electrical connectors at the fan motor. Measure the resistance between each lead wire with a multimeter or VOM. The multimeter should be set in the X1 range. For accuracy, don't measure when the fan motor is hot, allow it to cool off.
When the resistance between each lead wire are those listed in the specifications for your equipment the fan motor should be normal. Zero resistance or infinite resistance are indicators of a problem. More examples of checking wiring:
See HARD STARTING COMPRESSOR MOTORS
also TIGHT or SEIZED AC COMPRESSORS for more details about old or failed compressor motors.
Also see TEST a MOTOR STARTING CAPACITOR
The text above describing causes of refrigeration compressor damage is indebted to HVACR experts Norm Christopherson [2] and Joe Marchese [6], as well as Warren Hilliard [1].
...
Below you will find questions and answers previously posted on this page at its page bottom reader comment box.
On 2020-08-25 by (mod)
Code 4 on a thermostat may vary by thermostat brand and model but in many cases it means that there is an open circuit OR an outdoor temperature sensor is out of operating range (temperature too low, for example) so the heat pump will be "locked out" or left off by the system.
Your backup heat or furnace should still operate.
On 2020-08-25 by Nathan
Code 4 on thermostat. fan not kicking on outside. Pulled the relay and reinserted it. turn off the circuit also. No change once switched back on. Feels like cool air is blowing in thru the vents, but it's 80 in the house and the fan still hasn't kicked on outside.
On 2020-06-07 - by (mod) -
Holly
Thanks, that's an interesting question.
I'm not sure there is an unequivocal inspection or test that can distinguish compressor failure due to "age" versus due to a power outage, but possibly this: power surges that occur during a power outage can sometimes cause a burned-up electrical component, while a compressor motor that has failed bearings or an open winding or similar failure can be detected by electrical tests of the motor itself.
On 2020-06-07 by Holly Hawk
How would you be able to tell if your compressor went out due to several power outages or due to the ripe old age of 14 yrs old, and if coils are replaced would then the compressor also be replaced
On 2019-10-26 - by (mod) -
Loretta Lynn could be something as simple as a loose fan blade or mounting bolt or a serious as a refrigerant loss and a failing compressor. If you look in the article index found above you'll see a guide to diagnosing different air conditioning system sounds. Take a look because that might be helpful.
On 2019-10-25 by Midori S
Hi! My AC unit is Heier ESA408N & it had been making some rattling sounds. It's been getting louder with some other loud noise mixed together like a rusty metal spinning sound. I cleaned the outside part but that didn't fix it. I don't use my AC everyday, but this week has been really hot so I kept using it even though it was loud.
And yesterday, I should've known it was only a matter of time but, it stopped working.
It made a very loud one last rattle/squeak & went silent (with a hum).
It almost sounded as something that was spinning had either fallen off from somewhere or gotten stuck.
Now when I turn the unit in, I hear the electrical starting sound & hum but the fan blade is not spinning & there's no air coming out.
And I've been trying to get the front panel off to look at it but it won't come off.
If you could tell me the possible problem & the fix, or if it's easier/cheaper to buy a new one, that would be great. Thank you!
On 2019-04-02 - by (mod) -
An A.C compressor that is no longer usable.
The underlying causes can be any of a variety of problems such as liquid refrigerant slugging, low voltage, control or switch failure, overheating, debris in refrigerant, etc. even age.
On 2019-03-17 by feasts
my air condition works for 5 mins and seize my generator what could be the cause?
On 2018-11-16 - by (mod) -
On 2018-01-18 by (mod) - jammed thermostatic expansion valve can cause coil icing or freezing
A TEV can jam from dirt and debris or other contaminants including moisture that can actually freeze in a TEV. It's not a part you can change out yourself.
On 2018-01-18 by Dan
By you Saying Frozen I'm Assuming you Meaning by that Seized Up or do you Mean 410 refrigerant froze up in Compressor and Valves?
Service Techs are Exactly Why my Unit is Messed Up High Prices and Shotty Repair Work and Parts Changers when the Parts were not even Bad most of the time.
...
Continue reading at CAPACITORS for HARD STARTING MOTORS or select a topic from the closely-related articles below, or see the complete ARTICLE INDEX.
Or see BURNED-OUT COMPRESSOR FAQS - questions and answers posted originally on this page
Or see these
BURNED-OUT COMPRESSOR at InspectApedia.com - online encyclopedia of building & environmental inspection, testing, diagnosis, repair, & problem prevention advice.
Or see this
Or use the SEARCH BOX found below to Ask a Question or Search InspectApedia
Try the search box just below, or if you prefer, post a question or comment in the Comments box below and we will respond promptly.
Search the InspectApedia website
Note: appearance of your Comment below may be delayed: if your comment contains an image, photograph, web link, or text that looks to the software as if it might be a web link, your posting will appear after it has been approved by a moderator. Apologies for the delay.
Only one image can be added per comment but you can post as many comments, and therefore images, as you like.
You will not receive a notification when a response to your question has been posted.
Please bookmark this page to make it easy for you to check back for our response.
Our Comment Box is provided by Countable Web Productions countable.ca
In addition to any citations in the article above, a full list is available on request.