Building Inspection, Diagnosis & Repair Info

Photograph of  This new compressor was placed directly against a brick wall. One third of its condenser coil cooling ability was blocked. Air Conditioning Compressor Condenser Unit Inspection Checklist for Owners & Inspectors

Air Conditioner Inspection Checklist:

This air conditioning inspection article discusses the how to perform a simple visual inspection of an air conditioning compressor-condenser unit, including links to more detailed air conditioning inspection,diagnosis and repair articles useful in the evaluation of air conditioner compressor noises, hard starting, lost cooling capacity, and detection of a burned out compressor or A/C compressors at or near end of their life.

Maintenance tips including attention to compressor support pads and avoiding air conditioning refrigerant leaks are addressed.

InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers, products, or services discussed at this website.

- Daniel Friedman, Publisher/Editor/Author - See WHO ARE WE?





ADVERTISEMENT





How do We Inspect an Air Conditioning or Heat Pump Compressor / Condenser Unit:

This Simple Visual Inspection Procedure Can Disclose Damage or Operating Problems

Schematic of an air conditioner compressor unit showing inspection points (C) Carson Dunlop Associates Here we provide sketches and photographs and descriptions of common defects for each A/C component along with visual or other clues that may suggest a problem or probable failure of each component.

We explain how an air conditioning service technician will diagnose certain common air conditioning system failures or defects. We include photographs to assist readers in recognizing cooling system defects.

The (usually) outdoor half of a typical air conditioning system is a unit containing the refrigerant compressor and condensing coil.

The air conditioning compressor motor is a pump which draws heat laden refrigerant gas from the building's indoor components (evaporator coil and air handler), and compresses the low pressure refrigerant gas to high pressure and higher temperature.

The diagnosis and repair of various defects in the air conditioning compressor/condenser unit are discussed in detail using the links provided at the end of this article .

Here is a little visual inspection checklist that any homeowner or home inspector can perform.

Sketch courtesy of Carson Dunlop Associates, a Toronto home inspection, education & report writing tool company [carsondunlop.com].

AIR CONDITIONING & HEAT PUMP SYSTEMS describes the major components of an air conditioning system.

 

If your air conditioning or heat pump system has lost its cooling capacity or won't start
see REPAIR GUIDE for AIR CONDITIONERS.

If the system seems to be working but is inadequate to cool your buildinge see COOLING CAPACITY, RATED of air conditioning equipment.

 

Air Conditioner Compressor Unit Inspection Checklist - Outdoor Unit Observations

Key Air Conditioning or Heat Pump System Diagnostic Articles

...




ADVERTISEMENT





Reader Comments, Questions & Answers About The Article Above

Below you will find questions and answers previously posted on this page at its page bottom reader comment box.

Reader Q&A - also see RECOMMENDED ARTICLES & FAQs

Question: what's inside of a hermetically-sealed compressor unit?

What is inside if the air compressor units if you cut them open (May 10, 2011) Anonymous

Reply: refrigerant gas and a bit of oil.

COMPRESSOR / CONDENSER REPAIR shows what is inside of that sealed A/C compressor motor. There we include illustrations and text.

Question: effects of trees & shade on compressor / condenser units

A question which just came up: A large tree was recently cut back which had provided shade for my outdoor condenser which faces southwest.

Will the efficiency of the unit be adversely affected by this exposure to the hot uninterrupted summer sun? Your comments will be of great help for someone who obviously is not very knowledgeable. Thanks. (June 12, 2011) estelle j.

Reply:

Shade and A/C condenser units: good question Estelle. The outdoor condenser indeed has a slightly easier time of it if located in shade, though the units are designed to be capable of functioning in full sunlight. I have not found a source that gives us actual data on the change of system efficiency when shaded. So I'm reluctant to give a "made-up" number guess.

You can do several things to restore shade to your compressor unit such as:

- temporarily install a beach umbrella to shade the unit

- build a pergola or lattice-work cover above the unit

WATCH OUT - don't put any shade over the compressor/condenser that is so close to the unit's air inlet or outlet or that is so closed as to block airflow over the unit.

Most A/C compressor installation manuals will give the required clearances around all sides and above the unit in order that its airflow is not obstructed. If you can't find that information, and if your shade source is at least six feet above the unit you should be OK.

(Apr 26, 2012) kristopheruu said: that was very helpful

Question: I turned our A/C unit on and it is blowing hot air

I turned our A/C unit on and it is blowing hot air. I checked the outside unit and the fan is on.

I was standing by it when it came on, the fan came on first, then a few seconds later I heard the compressor come on, it was humming pretty loud.

The pressure line going into the unit was very warm. I checked the coils inside the house, (air handler?) and they were pretty warm also. Could this be the start up capacitor? Thanks. (Mar 16, 2012) Jeff

Reply:

See the diagnostic procedures beginning at LOST COOLING CAPACITY

Question: cutoff valves on AC / heat pump refrigerant lines?

My condensing unit is Carrier but the hot gas bypass has a cutoff valve, Can I install a new compressor whithout unloding the system's capability - that is, can it keep running? (May 15, 2012) slam jeme

Reply:

Slam Jeme I haven't seen cutoff valves on refrigeration lines, but if that's what youv'e got it may be that a swap-out ability was what was intended. Just ask your tech how they are going to get all of the air out of the new system and lines during the reconnection process.

Watch out: a shutoff valve on a refrigerant line can prevent proper compressor/condenser operation and may be unsafe to boot.

Question: outdoor compressor fan not running

The outdoor compressor fan is not turning even though the a/c is running. Air does not seem as strong or as cool as it usually is. Should I turn it off in order not to burn up the motor, or what are my other options? Can it be fixed?

The fan on the outdoor condenser is turning, but at a slower speed. The air coming from the top of it is cool, not warm. It makes a sound like a stick being run across a grate periodically as if it's trying to kick into a higher gear. (June 19, 2012) Evilu Pridgeon

The sound lasts about 3-4 seconds. Indoor runs but air is somewhat cool. Capacitor was tested and checks out fine (it was installed last summer). We currently have it turned off. Any suggestions? (Sept 18, 2012) Cathy C.

Reply:

Evilu if the outdoor fan is not turning but the outdoor compressor motor is trying to run it sounds like a fan relay or fan start run capacitor problem.

Watch out: TURN OFF the system to avoid damaging it while you wait for repair.

Cathy:

See FAN, COMPRESSOR / CONDENSER UNIT - if the fan on the outdoor compressor / condenser unit is not working properly

Question: condenser stoppd working, jiggled wires and it starts

My condenser stopped working a few months ago there was no noise of it trying to start just nothing at all. The other day I was looking at it and decided to jiggle the wires coming from the blower and the unit started right up and shut down. I jiggles the again and it started right back up.

I could see the wire nuts holding the wires together and decided to reconnect them better.

When doing so they came out of the wire nuts. I had a blue and yellow wire coming from the condenser.

And a red and white wire coming from the blower. No matter what combination I tried I could not get the unit to work again. And now nothing is working blower, heater, or the condenser. Any suggestions? I have tried all breaker that I know of. (Jan 26, 2013) Dooley

Reply:

Sounds as if in moving wires around you may have blown a fuse or mis-wired the unit. Ask for help from your heating service tech.

Watch out: Meanwhile leave power to the unit turned off for safety.

Question: split system AC display unit blinks on and off

After switching on split AC, and starting through Display unit, Display shows for 7 to 8 seconds and off for 4 to 5 seconds. A C unit dosen't work.

Can any expert tell why this happening? or cause of this? (June 29, 2014) Bapurao

Reply:

Bapuaro

If a display is cycling on and off I'd look for a condition that is causing the system to lose power itself or a loose switch, or an overload causing a system reset.

Question: minimum outdoor temperature for an accurate AC tuneup or freon check

What is the minimum outdoor temperature for accurate tune up/maintenance/ Freon level check? 28 Feb 2015 Phylon said:

Reply:

Pylon

In the inspection points for A/C and heat pumps listed in the article above please see "Temperatures of Operation" where you'll find a link to a detailed article diving operating temperatures and the measurement procedures.


...

Continue reading at A/C - HEAT PUMP CRITICAL DEFECTS or select a topic from the closely-related articles below, or see the complete ARTICLE INDEX.

Or see these

Recommended Articles

Suggested citation for this web page

A/C INSPECTION CHECKLIST - OUTDOOR UNIT at InspectApedia.com - online encyclopedia of building & environmental inspection, testing, diagnosis, repair, & problem prevention advice.

Or see this

INDEX to RELATED ARTICLES: ARTICLE INDEX to AIR CONDITIONING & HEAT PUMPS

Or use the SEARCH BOX found below to Ask a Question or Search InspectApedia

Ask a Question or Search InspectApedia

Share this article:

Search the InspectApedia website

Need to make a private comment? Email editor@inspectApedia.com. We welcome email with your website content critique, corrections, suggestions or questions. Email is monitored daily but our workload may prevent an immediate reply. For immediate results, we hope you'll first try asking your question using the search box just above.

Citations & References

In addition to any citations in the article above, a full list is available on request.



ADVERTISEMENT