Well Pump Diagnostic FAQsThis article provides a table of diagnostic checks and procedures for fixing well water pump problems.
InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers, products, or services discussed at this website.
- Daniel Friedman, Publisher/Editor/Author - See WHO ARE WE?
These questions & answers were posted originally
at WATER PUMP DIAGNOSTIC TABLE - a well pump troubleshooting article: be sure to review that article.
On 2018-10-29 by (mod) - Pedrollo pump stopped after a few seconds
You are on the right pump diagnostic page. I would check the items in the table at WATER PUMP DIAGNOSTIC TABLE.
On 2018-10-29 by joe kenyatta
hi, i use Pedrollo and pressure control unit to pump water from underground tanks to the house . on fortnight i switched on the pump ,it went on and stopped after some 5 to ten seconds .
I checked the pressure unit and no single lamp was lighting.
The power goes first to this pressure unit then to the pump . i even changed the power plug but it has not worked . what can be problem and how can i get help? thank you
On 2018-08-19 16:35:51.923962 by Robert Olson
hose came off presser tank water shot every ware then pump shut down but will not start up again you flip the breaker you can here it engage then shuts off right away no water coming up from well ? checked presser switch all good check power at top of well 120 to both legs ?
On 2018-03-20 22:33:07.958955 by (mod) -
You probably need an on-site service tech, but I would be checking for low voltage, a failing pump bearing, a bad pump impeller, or pump running partly dry with cavitation. I also wonder if your pump is in sun or shade.
On 2018-03-20 18:59:40.639220 by Brandy
Jet pump on well over heats with in 15min of a constant run. Im filling up above ground pool
On 2018-03-15 21:35:09.079659 by (mod) -
If the CUT OUT pressure on the pressure control switch is set above the pressure that the pump can reach, for whatever reason, the pump won't turn off.
OR
The pressure control switch may not be sensing water pressure properly if it's sensor tube is blocked.
See these diagnostic tables
TABLE 2: PUMP RUNS, WEAK or NO WATER PRESSURE https://inspectapedia.com/water/Water_Pressure_Table_2.php
TABLE 3: PUMP RUNS, NO WATER or INSUFFICIENT WATER https://inspectapedia.com/water/Water_Pressure_Table_3.php
On 2018-03-15 21:06:06.511236 by Steve
I can get water using a hand pump but when I hook up the shallow well pump and prime, I don’t get any water. The tank is set to 13 lbs. the pump runs but does not shut off. Builds to 30 lbs any ideas?
On 2018-03-09 2 by (mod) -
An electrical fault in the pump or pump control or pump circuit, such as shorted wires, a shorted or fused well pump pressure control switch, or a seized pump motor - all of which mean leave the circuit off pending repair, as it's unsafe.
On 2018-03-09 by Louise R Schmidt
What causes the fuse to the well to blow
On 2018-02-06 by (mod) -
Mike,
Check for a pressure control switch that is not responding to pressure changes, perhaps due to debris clogging, and replace it.
On 2018-02-06 by Mike tillman
Water trickles then builds up to max. Or reverse sometimes.
On 2017-12-30 by (mod) -
Repl ace the moto r capacitor.
Search inspectapedia.com for MOTOR STARTING CAPACITOr
On 2017-12-29 by John
Pump require to rotate the shaft to run
On 2017-12-19 by (mod) -
Tim
Sounds like a short or failure in the pump that burned the wires.
On 2017-12-17 by Tim
Would appreciate some assistants with my water pump question. Is the motor bad if the wires inside are burned up
On 2017-12-09 by M
Had a guy come out and diagnose the problem(s).
The neighbors have a pressure tank that we didn't realize was regulating everything and the switch probably went bad and then the thing burst and hasn't been doing its job, causing the well pump to short cycle. I'm planning on replacing the pressure tank, pressure switch, piping etc. since I have some experience in that direction.
The guy said to expect the well pump to fail shortly after fixing the pressure tank and he suggested having it all done at once. $1000 to fix a pressure tank, alone, seemed pretty steep, so I'll work on that and then see how long the well pump holds out...
with a well company on standby to drag up the 285 foot deep well pump.
I am concerned there are some other maintenance things needing to be addressed, but the flooded pressure tank seems like the best place to start. The technician guy didn't give a good idea where plastic came from but used told measure output from various parts system and lastly checking the overflow like valve on the pressure tank.
Again, I really appreciate you taking the time to consider what was going on and give a thoughtful response. I guess that sort of thing doesn't get you paid, but in this ever growing, larger world, thoughtful sharing is at a minimum. Thank you for helping to keep the world turning!
On 2017-12-06 by (mod) -
If the pressure tank plastic portion of the liner or broken your attack would be most likely not working and you probably see the pump short cycling on and off.
If the plastic were from the dip tube in a water heater tank it wouldn't show up in the cold water lines like the toilet..
Still I would think that if the plastic particles were coming from the water pump, for example and impeller, I would expect the pump to stop working.
A good move would be to collect a water sample and take it to a local lab and ask them to tell you what's in it.
On 2017-12-06 by M
The plastic bits showed up first in the clean water tank of the toilet. The filters on the showers had very little plastic and the kitchen sink had a bunch. I flushed the water heater and the plastic bits kept flowing out with a bit of sediment. Someone today suggested a broken pressure tank. I don't believe I have one, which I have led to believe could be a separate concern.
Thank you for taking the time to consider this problem. I haven't found anyone willing to even briefly talk over what may be going on, so I can assess how much money I might be expecting to spend this holiday season.
On 2017-12-06 01:48:53.334549 by (mod) -
I might check for a deteriorated plastic dip tube in the water heater
On 2017-12-05 17:30:45.171599 by M (more questions)
I'm guessing some plastic part in the pump/motor died. Someone mentioned the impeller being made out of plastic. Is there any kind of reasonable guess as to how long until the system dies completely with this part broken?
Is it a matter of days, weeks, months? Would sending a camera down there for $300 be worth it or should the whole thing just be replaced ASAP... or when it dies?
On 2017-12-05 14:08:05.493477 by M
Well water is cloudy grey with plastic looking/feeling fibers floating around. Pressure is generally good, with some minor hiccups noticed in the past few months. Any ideas?
On 2017-11-18 16:19:35.082737 by (mod) -
See if you can notice signs that your well is running out of water, just turning off the pump by way of a pump protection switch. You might notice for example diminished water flow at your faucets or you might notice that the pump needs to stay off for a while before you can obtain water again
On 2017-11-18 12:24:31.733962 by Anonymous
Pump keeps on switching off
On 2017-11-09 00:18:38.624729 by Saran
My pump Tripp's while tap is on and would not turn on again.
On 2017-11-07 01:15:00.541521 by (mod) -
Christina,
If water into the building is turned off, and if at the end of a normal pump cycle such that the pump shut off at the cut out pressure, you then see pressure falling in a system I suspect that there is a leak in the well piping that needs to be found and repaired.
On 2017-11-06 18:33:41.349701 by Christina Braun
We had to replace part of a cracked line between our pump and our well. Now the pump won't hold pressure. We have tried again and again to prime it. My husband thinks there may be air in the line between the pump and the well. Any suggestions on how to get air out of that line?
On 2017-10-28 02:16:32.255359 by (mod) -
Sorry to be a little slow but I don't quite understand the question
On 2017-10-28 01:40:13.084964 by Jan Keith Reese
I'm looking pressure but I'm not flooding the prime
On 2017-09-27 22:30:06.628743 by (mod) -
I don't know, Keith, I'm confused too. I'm not sure what's meant by holding water in pipes but can't draw water. If you open a faucet and no water comes out then no water is being delivered. Perhaps you meant you don't see leaks.
The diagnostic table on this page is for a water pump that won't run.
You might want to start at "no water pressure" found at https://inspectapedia.com/water/Water_Pressure_Table.php
On 2017-09-27 21:32:35.533152 by Keith hendrick
My two pipe lines hold water but I can't draw water. Does this should like a bad pump. Please help
On 2017-09-21 18:00:37.757641 by Rick
I have a deep well(2inch) jet pump. The pressure gauge doesn't read higher than 20 so the pump won't shut off. The water pressure in the house is really low.
On 2017-09-16 22:22:28.996169 by (mod) -
Lorne,
I can only guess since I don't have any information about what water supply equipment your building uses.
IF I'm right that you have a conventional residential water pump and pressure tank bringing water from a private well,
then typically there is a pump pressure control switch that senses the water pressure and when pressure drops below the CUT IN level (typically 20 or 30 psi) the switch turns on the pump.
The same switch turns off the pump at the CUT OUT pressure (typically 40 or 50 psi).
If the pressure control switch is debris clogged, say by rust or silt in the water, then it stops sensing the pressure drop when it should. Normally the repair is simply to replace the pressure control switch and to clean or replace the small diameter tube the brings water pressure to the sensor port on the bottom of the switch.
However **IF** the amps current draw your service guy is measuring is abnormally high
and the pump was not starting,
that suggests that the pump motor has failed, perhaps because of a seizing bearing or bad pump impeller - a different problem having nothing to do with the pressure control switch.
On 2017-09-16 14:54:55.963591 by Lorne
Service company said start signal was not cutting out causing breaker to trip and also pump motor was bad and had to be replaced, which it was. Installed new control box and motor and everything ok. What could cause start signal to continue too long? Was it really just the pump motor not actually starting or did the long start signal ruin the motor?
Motor was still under warranty. Service guy didn't really know what was causing long start signal. 26 amps was showing on his meter on the start wire.
On 2017-08-23 11:33:09.943548 by habib
Motor donot pump water forcely from well
On 2017-08-13 02:21:27.299449 by Anonymous
GT15 wired 230V/1 (2-115V hots and ground), jumper is correct. Voltage on both legs-got over 100 amps on each leg before tripping. 40 amps breaker-1.5 hp.
On 2017-08-13 02:19:43.229719 by Alex
Goulds GT15 pump, motor sounds like 3phase motor single phasing or loud electrical noise, breaker trips if left on more than 3-4 seconds. I thought capacitor, so brought a new one, no change. Pump/motor is spinning slowly when it trips or is cut off. I don't think it is a pump problem, seems electrical, but if I knew, I wouldn't be asking.
On 2017-08-10 15:28:11.813305 by (mod) -
Your installer should test for cut, damaged, or shorted well pump wires or a wiring error.
On 2017-08-10 12:53:07.475201 by JoJo
New pressure switch(was burnt through), new pump & still throwing breaker at power box.
On 2017-08-07 21:40:23.475170 by (mod) -
Bernie,
Perhaps the pressure switch has burned contacts or a debris-clogged pressure sensor port.
On 2017-08-07 18:05:21.760839 by Bernie
My water turned off for a couple of seconds and then came back on with a little dirt coming with the water. This has happened a couple of times
On 2017-07-27 11:22:23.517952 by John
I have a deep well yesterday I came home no water in the house,my neighbor came over and we reset it ,but it keeps turning off ,any ideas
On 2017-07-02 13:54:21.473790 by Vance
Bought bladder tank and had a problem getting air pressure and pressure switch right..thought I had it and woke up this morning with pump burned up..what did I do wrong
On 2017-06-28 01:20:57.065096 by Jim w.
I have a problem with sewer fly larva in my sypetic tank. There are so many that the drain leading to the drain field becomes clogged. I clean the drain out about once a month to stay on top of the problem. What is causing this and how can I stop it.
Thanks, Jim
On 2017-06-14 12:29:06.689702 by (mod) -
Martin:
From here in Genoa I can't see enough to be sure, but it sounds as if there is
- a loose wiring connection
- damaged or corroded wiring or connection
- a seized pump motor
If the sparks are extremely tiny and occurring only between the contact points of the pressure control switch then perhaps what's needed is simply replacement of the switch (or its points assembly), as burnt points might arc.
Larger sparks or sparks outside the control? Turn OFF the equipment and ask for help from a licensed electrician or plumber - there could be fire or shock hazards.
On 2017-06-14 11:53:30.612216 by Martin
What is the trouble
On 2017-06-14 11:52:15.254910 by Martin
My pump control box is sparking at the wire metal connection
On 2017-06-13 20:37:37.548827 by (mod) -
On 2017-06-13 20:30:18.180525 by (mod)
Tim:
I suspect you are exhausting the well's water inflow. 15ft of water, if it is a 6" casing, is less than 30 gallons in the static head or water column when the well is fully rested. So when you run water for 4-5 hours you are depending on the well flow rate - rate that water flows into the well. With global warming, seasonal changes, and depending on where you live, with many users pumping out the aquifer, it would be no surprise if the flow rate and yield of your well has been reduced.
When you face this condition again I would
1. immediately turn off the pump as running the pump dry will damage it
2. take a look into the well to see if there is water at all, and if so at what level,
3. take note of the time and then see if you can observe the rate at which water flows into the well enough to re-fill the casing.
Keep in mind that even then, you can't re-start and re-run the pump successfully unless the rate at which water flows into the well is greater than the rate that water is being taken out of it.
If this is the only water source for your sweetcorn, and assuming we can get the well running again but now know that its flow rate is
diminished, I would investigate using a slower watering rate, maybe drip irrigation.
Keep me posted
Daniel
On 2017-06-13 by Tim G.
I have a shallow well used for watering sweet corn. It has over 15' of water and the suction line is less than 25' in total length. Check value has been replaced and all connections for leaks. Problem; it will pump for 4-5 hours then stop delivering water when pump is running. Then impossible to re prime even after 7-10 times. What's happening?
On 2017-06-13 by (mod) sweet corn irrigation well loses prime, runs out of water?
Tim:
Since you report that the well pump was running successfully as an irrigation pump for 4-5 hours before it stopped giving water, I suspect you are exhausting the well's water inflow.
15ft of water, if it is a 6" casing, is less than 30 gallons in the static head or water column when the well is fully rested. So when you run water for 4-5 hours you are depending on the well flow rate - rate that water flows into the well.
With global warming, seasonal changes, and depending on where you live, with many users pumping out the aquifer, it would be no surprise if the flow rate and yield of your well has been reduced.
When you face this condition again I would
1. immediately turn off the pump as running the pump dry will damage it
2. take a look into the well to see if there is water at all, and if so at what level,
3. take note of the time and then see if you can observe the rate at which water flows into the well enough to re-fill the casing.
Keep in mind that even then, you can't re-start and re-run the pump successfully unless the rate at which water flows into the well is greater than the rate that water is being taken out of it.
If this is the only water source for your sweetcorn, and assuming we can get the well running again but now know that its flow rate is
diminished, I would investigate using a slower watering rate, maybe drip irrigation.
Keep me posted
Daniel
On 2017-06-13 by Tim G.
I have a shallow well used for watering sweet corn. It has over 15' of water and the suction line is less than 25' in total length.
Check value has been replaced and all connections for leaks. Problem; it will pump for 4-5 hours then stop delivering water when pump is running. Then impossible to re prime even after 7-10 times. What's happening?
On 2017-06-10 21:49:20.009283 by (mod)
Jon:
If the pump motor stops then I suspect it is overheating OR is being shut down by a pump protection switch that responds to low water in the well.
If the pump is overheating it may be due to a binding impeller, motor bearing, or low voltage.
On 2017-06-10 by Jon
Thtis is an existing pump that has been in use for 3 or 4 years. Recently it started acting up where it produces a small amount of water then the pump will quite running.
On 2017-05-29 by (mod) re: signs of an air leak in the suction line or in the water pump
Gary that sounds to me as if there is an air leak into the suction line or into the pump itself. Inspect the pump and piping carefully as you might also see signs of leaks out at the leak point. If you have plastic piping try adding a hose clamp and tightening it at each connection point.
On 2017-05-29 by gary
i cannot get the jet pump to prime-a 5ft. lift and 30ft. distance-it blows a lot of air out the priming inlet
On 2017-05-19 by (mod) re: how to replace the Goulds J Plus pump diaphraghm
Larry,
Take a look at the parts explosion for the Goulds J-plus pump, as I did, and I think you'll see the illustration shows the seal ring on top of the diaphragm rather than fitting into it.
On 2017-05-19 14:32:34.893290 by Larry
Rebuilding a Gould jplus , should the diaphragm gasket be fitted into diaphragm or placed on top?
On 2017-05-13 by (mod) re: Goulds J7 pump failure report
MJ
Unless all four Gould J7 water pumps came from the very same manufacturing run (check manufacturing dates and serial numbers) it's not likely that the pump is the root problem. Typically short cycling (water logged pressure tank) or low voltage are more likely to cause pump damage as would running the pump dry if your water source were inadequate.
On 2017-05-13 by MJ
We are in our 4th new Gould j7 pump in 4 years. Keeps seizing up and plumbers just replace units without insight into whAts causing failure.
Water supply is drawing from lines submerged in lake wAter which is sufficiently suspended off the bottom and has a screen and foot valve. We removed and replaced the hose going from pump to pressure switch and now it works again. Any idea for why this is a repetitive problem?
On 2017-05-05 by Anonymous
I hope you can help my boyfriend took off the condenser on our water pump because water pump quit working now he dont know how to put new one on
On 2017-04-14 by (mod) re: irrigation pump trips circuit breaker
Bob,
A tripping circuit breaker on an irrigation pump circuit is usually caused by
- a pump motor that is overloading, seizing, failing or otherwise is damaged, drawing high current
- a short circuit in the pump system wiring
It's pretty easy to diagnose those conditions if the electrician is familiar with use of a DMM or VOM and can check the wires for shorts as well as checking the current draw of the pump. I suppose one of your timers could also be shorting.
Watch out: for electrical shock hazards - if you're not trained to do these steps I'd call an electrician.
On 2017-04-14 by Bob
I have a 220v irrigation pump pulling from a lake. The pump is controlled by 2 Hunter timers separately wired to two hunter pump relays. The system has worked flawlessly for a couple of seasons. This season, something keeps tripping the breaker.
I can start the timers manually and the pump will run through complete cycles. It might work automatically for a day or two but then I'll find that the breaker has tripped. I have been unable to determine if the trip occurs while the pump is running or on timer controlled startup. I have replaced the breaker and the wiring from the pump to the relays. I have checked the wiring in the relays and all are tight. This has not fixed the problem. Could a bad pump capacitor be the problem?
On 2017-04-12 by (mod) Re: where a short cycling pump will show up: at the tap
Jo
Short cycling will be observed right at the tap - the water pressure and flow will decliine then increase in rapid pulses of 15 seconds or less.
I suspect your pressure gauge and maybe pressure control switch are debris clogged.
On 2017-04-14 by (mod) re: irrigation pump trips circuit breaker
Bob,
A tripping circuit breaker on an irrigation pump circuit is usually caused by
- a pump motor that is overloading, seizing, failing or otherwise is damaged, drawing high current
- a short circuit in the pump system wiring
It's pretty easy to diagnose those conditions if the electrician is familiar with use of a DMM or VOM and can check the wires for shorts as well as checking the current draw of the pump. I suppose one of your timers could also be shorting.
Watch out: for electrical shock hazards - if you're not trained to do these steps I'd call an electrician.
On 2017-04-14 by Bob
I have a 220v irrigation pump pulling from a lake. The pump is controlled by 2 Hunter timers separately wired to two hunter pump relays. The system has worked flawlessly for a couple of seasons. This season, something keeps tripping the breaker. I can start the timers manually and the pump will run through complete cycles.
It might work automatically for a day or two but then I'll find that the breaker has tripped. I have been unable to determine if the trip occurs while the pump is running or on timer controlled startup. I have replaced the breaker and the wiring from the pump to the relays.
I have checked the wiring in the relays and all are tight. This has not fixed the problem. Could a bad pump capacitor be the problem?
On 2017-04-12 by (mod) re: short cycling pump & diagnosing trouble with a pump returned to service after long disuse
JoOn 2017-04-10 by Jo
One more note, the pressure gauge was not all the way down to 30 when I turned on the breaker, and the pump kicked on. Could this be related?We just moved into a new house a few months back. It was a foreclosure, no one had been in it for a year and the water that came out at first was... dirty.
In the meantime, I started to notice that our power bill was double what we payed before.
So I started testing, turned off the heat for a month and watching electricity usage. We went out of town, and decided to shut of breakers to most of the house, leaving on a few key ones such as water so that the someone could water animals, etc.
I noticed that the electricity had only halved when we went out of town, so I re-examined the 3 breakers that we had not shut off. I shut off the water pump for a full 24 hours and my energy usage halved in that day, leading me to believe something is going on. After some calculations, and close observations, my water pump is using an average of 20KWH per day. There is only two adults in the house, both of which are out of the house for most of the day.
In addition, our electricity usage is significantly higher on "Laundry" Days. We do 3-4 loads. Not a little higher, much higher.
The pump is a submersible pump, and I am not sure how often it is running. On one hand I think it is short cycling because it is using more electricity when water is being used, but that doesn't explain the high electricity usage even when it is not being used (like when we went on vacation and the pets were given water once a day).
I then turned off the water pump for a few hours to see if the water pressure tank holds pressure. I waited overnight, and there is no change in pressure. I ran some water, which lowered the pressure in the tank, and then turned on the breaker. I watched the needle promptly return to 50PSI. Then I ran water again until it was about 40PSI and watched again. Nothing happened, the needle stayed in the same place.
I'm honestly just not sure where to go from here. Can you give any suggestions of what to check next?
On 2017-04-01 by (mod) re: pressure switch won't keep pump running - may not be sensing water pressure
Elton,On 2017-04-01 by Elton
Woke up no water checked well good level of water pulled outside breaker near pump pushed it back in heard tank try to build pressure shut off after 5 seconds went in house had water for 2 to 3 seconds then dry again any suggestionsOn 2017-04-01 by (mod) re: hooking up a garden hose since pump stopped working?
Garr,On 2017-04-01 by Gary
How can I hook up a garden hose to my house since the pump burnt up? I have another well with power a few yards away.On 2017-03-20 by (mod) re: dangerous signs of a shorted well pump or wiring
TrudyOn 2017-03-20 2 by Trudy
My 1/2 HP Single Phase - 3-wire 230V 6Amp submersible well pump in my 81 ft. well quit running; I started with replacing the pressure switch and cleaning out the pipe connecting it to the water line as pipe was 1/2 plugged, rewired same as old switch and when breakers turned on it made breakers crackle, etc. but not turn on the pump. Researched pressure switch wiring on mfg. website and rewired as shown, with the same thing happening. (Further research indicates both ways were correct.)
Bought a new control box; same thing happening. With front off Control Box checked the voltage w/ a voltage tester at the breakers, at in lines at pressure switch, at out lines at pressure switch and at in lines at control box. All checked out 120V single line and 240V for both.
With both the old and new Control Box fronts connected, pump does not run and the breakers crackle and fizzle, but do not when Control box front is off with wires still all connected up to Control Box with voltage readings correct; also plug in still working in pump house.
Can I "assume" there is a short somewhere in the wiring inside the well or the pump motor at this point? Or................. Thanks!
On 2017-03-16 15:39:07.045894 by (mod) re: tapping on the pressure control switch can diagnose clogging or sticky points
Good going, Kristi! I love that diagnostic trick of tapping on the control.On 2017-03-16 14:37:24.730437 by Kristi P
We have a 1 HP Goulds SJ10 pump ( # C48A95A06) 2 days ago woke up to no water. Checked under the house for leaks, checked the pressure in the bladder tank, no issues. Replaced the Water Pump Pressure Switch and everything started working again.
Water worked fine at 7 am this morning then no water again 2 hours later. (of course now my husband is at work!) Went out and tapped on the top of the pump itself and it immediately cut on! Any suggestions will be greatly appreciated!
On 2017-03-14 16:38:23.477307 by (mod) re: signs of a failing pump motor
I suspect that there is a failing pump motor, improper voltage, improper wiring, or wrong capacitor has been installed.On 2017-03-14 12:33:23.935051 by Ed
Pump works fine for about 20 to 30 minutes, then the run capacitor burns out on the submersible motor control model number 2801084910.On 2017-03-11 16:40:06.785650 by (mod)
Ask your plumber to check for lost pump prime, and if that's the problem, you probably need to replace a bad check valve or foot valve.On 2017-03-11 16:05:09.753285 by Vicki
We had a power outage. When the power came back on, the water isn't pumping from our well. We have water for a few seconds from the faucet then it dies down. You can normally hear the faucet pulse/pump and we don't hear that either.On 2017-03-10 03:25:49.115937 by (mod)
AnonOn 2017-03-09 19:45:47.221550 by Anonymous
I got all new 1 horespower pump pipe & foot valve. It 65 feet deep. And I can't get it to pump. Primed it many times and still nothing.On 2017-03-02 17:08:49.984945 by (mod)
Search InspectApedia for LOST WATER PRESSURE to see diagnosis and repair proceduresOn 2017-03-02 00:45:02.363655 by Amy
My well suddenly stopped pumping water. A couple days later it pumped water again for about a week and stopped again. The pump clicks on and then clicks off again.On 2017-02-27 16:12:13.212061 by (mod)
Sounds like an overheating pump motor. Could be a failing bearing.On 2017-02-27 15:22:59.344662 by Geoff
My Artesian well runs fine for around 5 minutes , then it trips the electric . If it is left for around 30 minutes it works again , then trips the electric again .On 2017-02-15 21:00:09.344967 by (mod)
Submersible pumps don't normally lose prime as they're under-water. But you could have a leaky well pipe or check valve.On 2017-02-14 02:28:42.409825 by Clyde
Pump runs to 60 lbs. and drops back to 40 lbs. I have water pressure and water but is my submersible pump loosing its prime, or is there another problem.On 2017-01-27 01:29:38.897398 by (mod)
Anon: sorry if your post was deleted - I didn't do that on purpose but it might have happened by a too-hasty click.On 2017-01-27 01:12:50.765323 by Anonymous
Nice I posted for help with my jet pump only to come back n it's gone. Thanks for that whoever flagged it. Like my life ain't bad enough already. This just makes it worse. Now I know what to do to fix itOn 2017-01-23 18:35:15.655719 by (mod)
Look for a bad check- or foot- valve.On 2017-01-23 15:47:40.054544 by Aldrin stein
Hi , my pump switches on and off after every 10 minutes without a tap being opened, I'm afraid the motor might burn out ?On 2017-01-15 14:13:03.950088 by (mod)
I think you meant the pump will NOT achieve pressure over 20 psi.On 2017-01-15 00:17:11.984835 by -David
I have a jet pump which holds pressure to home but the pump will get over 20 psi ? The pump ran continuously until I lowered the cut off pressure. this is the 3rd pump from Home Depot over a period of 5 years that I have tried. Would it just be a poor pump design.On 2017-01-13 19:11:19.934764 by Mike
I have a sub pump I have very little pressure I replaced contacts checked pressure on holding tank (28lbs) I check voltage ok(240) can see water in filter when I turn pump on pressure gauge stops at 20lbs could gauge be bad pump run all the time help!On 2017-01-13 04:38:54.683474 by (mod)
If the sound is from an electrical problem the installation is very unsafe and should be left turned off. Do you smell smoke or see Sparks?On 2017-01-13 02:20:40.161909 by connie joiner
Well water pump makeing a popping sound.!!! What will cause thst?On 2017-01-12 16:54:53.223136 by (mod)
A short between well wires, short from well wires to well casing, short to ground, seized well pump motor, frozen pump contactor switch. Or less likely: a defective breaker.On 2017-01-12 16:38:27.510247 by Richard
My well pump keeps blowing the circuit breaker what could be wrong(May 23, 2011) Anonymous said:
This guide was the perfect answer to our problem. Thank you so much for this donation of knowledge.
...
Continue reading at WATER PUMP DIAGNOSTIC TABLE - topic home, or select a topic from the closely-related articles below, or see the complete ARTICLE INDEX.
Or see these
WATER PUMP DIAGNOSTIC TABLE FAQs at InspectApedia.com - online encyclopedia of building & environmental inspection, testing, diagnosis, repair, & problem prevention advice.
Or see this
Or use the SEARCH BOX found below to Ask a Question or Search InspectApedia
Try the search box just below, or if you prefer, post a question or comment in the Comments box below and we will respond promptly.
Search the InspectApedia website
Note: appearance of your Comment below may be delayed: if your comment contains an image, photograph, web link, or text that looks to the software as if it might be a web link, your posting will appear after it has been approved by a moderator. Apologies for the delay.
Only one image can be added per comment but you can post as many comments, and therefore images, as you like.
You will not receive a notification when a response to your question has been posted.
Please bookmark this page to make it easy for you to check back for our response.
IF above you see "Comment Form is loading comments..." then COMMENT BOX - countable.ca / bawkbox.com IS NOT WORKING.
In any case you are welcome to send an email directly to us at InspectApedia.com at editor@inspectApedia.com
We'll reply to you directly. Please help us help you by noting, in your email, the URL of the InspectApedia page where you wanted to comment.
In addition to any citations in the article above, a full list is available on request.