Water Pump Won't Stop Running
FAQs for a water pump won't stop running:
Questions & answers help diagnose & fix a water pump that doesn't shut off: this article series explains how to diagnose & repair a bore hole or well water water pump that keeps on running and won't shut off.
InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers, products, or services discussed at this website.
- Daniel Friedman, Publisher/Editor/Author - See WHO ARE WE?
If you hate reading FAQs, even though your question may be answered here, please see the lead article on this topic at WATER PUMP WONT STOP RUNNING where we explain what to do if the well or water pump won't stop running.
Also see our index to all Q&A about diagnosing and fixing a water or well pump that won't turn off, found at WATER PUMP WON'T STOP RUNNING FAQs
...
Hi, we have well water in our rental house. The pump froze and finally warmed up enough to come back on. Now the pressure is very high and the pump doesn't shut off and runs continuously. What can we do? Thank you! On 2021-02-15 by Janis
by (mod) - pump froze and now won't turn off: high pressure!
Janis
Watch out: IMMEDIATELY TURN OFF ELECTRICAL POWER at the pump
because if the pressure becomes great enough to burst the tank someone can be injured
and because we don't want a burst pipe and flood
and because we're also risking burning up the pump motorWhen the pump is off we can investigate further - or your plumber can:
A list of diagnostic checks for a pump that won't turn off is found at
WATER PUMP WONT STOP RUNNING - topic homeI'd probably start with
My pipes froze downstairs; its below 0 here.
But I had water upstairs except the toilet wouldn't flush. Someone told me to let the sink run with a little water coming out of the spigot.
Next thing I knew, I had no water upstairs either, and now my pump wont stop running.
I shut it off since there is no pressure. Any ideas? On 2022-12-26 by Mona
by InspectApedia (Editor) - finding & thawing frozen pipes
@Mona,
I agree that it's smart to turn off the pump to avoid burning up the pump motor.
Advice on finding & thawing frozen pipes is at
FROZEN PIPE THAW-OUT
It's a common but questionable tip to "leave water running slowly to avoid frozen pipes" because of the risk that that low-volume of water may freeze and block or even break a building drain line outside the building.
But indeed when the pipes are almost solidly frozen or during the thaw-out effort I might open all of my faucets wide open for a time. Once water begins to run, even slowly, moving water faster and faster through the pipes as the moving water helps melt the now partially-un-blocked iced-up section of piping, will speed up the pipe thaw.by Mona
I have just plugged a heater in inside the closet where the pump and everything is to possibly help the thaw. I will now turn on all my faucets and see what happens. Thanks alot for the help!
by InspectApedia Publisher (mod) - follow water pipes to look for a spot that's particularly cold
@Mona,
Good, now keep me posted.
Also you can try following your water pipes to look for a spot that's particularly cold.
see details at PIPE FREEZE-UP POINTSFollowup by Mona - I left the pump running for an hour but got no water
@InspectApedia Publisher, Hi, I've checked for any cold spots and there are none. My pump has no switch to hold at a 45 degree angle to reset the pump because of the set up. Its hooked up to a softener.
I did hear a trickle of water and thought it must be working but no, the gage on the pump still won't move.
I ran it for almost an hour but nothing. I'm thinking I'll just have to wait a couple more days until the temps climb a bit higher to the 40s and 50s. Other than that, I'm at a loss.
I've also noticed the pump is hot. Is that normal? I did let it run for about an hour just to see if anything happened. No. But I have 30 pressure in the tank as well. So I guess all I can do is wait for the thaw and keep checking.
by InspectApedia Publisher - leaving the pump running too long, risks damaging the pump itself
@Mona,
It seems likely that a pipe is frozen somewhere in your system.
I warn again that leaving the pump running to long, if it is not actually water filled nor moving water, risks damaging the pump itself, so don't leave it on for hours at a time.
Watch out: also about running a heater in a too-small space: be sure your heater is used in a way that's fire-safe - not close to combustibles. Usually there are clearance instructions provided with or even right on the heater.If the pump motor is too hot to touch then it's definitely at risk of damage- leave it turned off.
Sorry.
Post a photo of your pump and its control and we may be able to see and say more.by Mona - pump isn't hot any more but still no water
@InspectApedia Publisher, I guess all I can do is wait for the thaw and keep checking.
Pump is not hot anymore. Someone who was just here said it was but I checked it and it is not hot at all. Must have been because of the heater I had out there which now I took away. If you still need a picture, I can send it. Thanks
by InspectApedia Publisher - Ace 2-line jet pump
@Mona,
OK so at last we can see your water pump: it looks like an Ace 2-line jet pump.
I don't understand what you mean by
" the switch has no switch".
Any water pump will need a pressure control switch though it may not be mounted right on the pump itself.
This photo of a newer-model Ace 2-line jet pump similar to your Ace Jet Pump model - you can see that a pressure control switch, in this case mounted on the side of the pump, senses pressure by a small flexible (black plastic) tube that conducts water pressure from the pumping impeller chamber to the switch bottom. 2-line-by Mona - there's no "switch" on my pump?
@InspectApedia Publisher, I was told it had no switch because of the set up (softener) I have. I'm sending you a photo of where I thought the switch wouid be. Regardless, I still have no water nothing thawed enough yet. I check the pump daily to see if the gage moves after a couple minutes and when it doesnt I turn the pump off. But anyway, here is a pic of where I thought the switch should go.thanks
Now I'm told the pump does have a switch. I didn't mean the switch doesn't have a switch..sorry. anyway, I was told the pump is hardwired so it has like a light switch. Regardless I'm not sure much good the switch could do anyway if the lines are frozen. Sorry this is so confusing. I'm just told one thing then told another.
by InspectApedia Publisher - if pipes are frozen , the pump can't deliver water
@Mona,
We are in agreement that if you have frozen pipes, the pump can't deliver water.
Pretty much every water pump will have to be controlled - turned on-and-off by a switch somewhere.by Mona
@InspectApedia Publisher, hi, so you're also in agreement with me that I may as well just wait until everything thaws and see what happens,, thanks so much for your trouble!
by InspectApedia Publisher
@Mona,
Do take a look at the discussion, your questions, our replies, and the advice in the article above.by Mona - getting some water, gauge still reads zero
Thank you, I am starting to get a little water out of my faucets but the pump, it still runs but the gage wont move from zero. I'm sure it needs primed, but since it's hard wired, I have no lever to hold at a 45 degree angle. The thaw is continuing.
Now a new question. My pump is hard-wired, so it has no pressure switch to hold at a 45 degree angle to prime the pump. How do I prime the pump? Do I need to put water in it somewhere? Last it was checked, the pump had 30 in pressure. Used a tire gage to check it. Thanks
by InspectApedia Publisher (mod) - NO water pump is hard wired in such a way that it does not require a pressure control switch
@Mona,
NO water pump is hard wired in such a way that it does not require a pressure control switch, though some water pumps might include the pressure control built-into the pump itself.
I appreciate that you've done your best to describe the situation and the trouble you're facing getting water pressure, but as you're not a plumber and don't know where to look or what parts look like, our own ability to see and understand and thus give advice about your water and pump system has us peeping in near darkness through the eye of a needle: we just can't see enough to give any more advice than I've given that would not be so speculative as to be of little use.
You need an on-site experienced plumber to examine your pump, water pressure tank, pump controls, piping and fixtures to understand if the "no water" problem you have is due to
- simply frozen pipes
- a burst and leaking pipe or fixture
- a damaged pump control
- a damaged water pump
- no water in your well or other water source
- something else that we haven't considered
Please get someone ON SITE to help you with this and keep us posted. We want you to have water asap.Also read PRIME the PUMP, HOW TO
by Mona - primed the pump and now we have wagter
@InspectApedia Publisher,
@InspectApedia Publisher, yes, thank you. Someone is coming today to try and prime the pump by pouring water in it. Hopefully it helps and I get water back.
...
I now have water! He put about a quart of water in the pump and now works! We expected it to take more but he said it only took a quart so good! Thank you for the help!by InspectApedia Publisher
@Mona,
That sounds right. Do let us know what you're told and what works - that will surely help other readers who are without water after freezing weather.
...
The pump pressure switch won't kick on and when you manually start it it won't shut off.
The other issue is pressure switch set to shut off at 50psi but water pressure goes to 90psi and the pump continues to run.
We have replaced the switch which new switch is set at 30psi on 50psi off and it continues to do the same thing . On 2017-07-04 by Jim
I would NOT run the pump under these conditions until the problem is
by (mod) re: pump won't turn on and if we turn it on ourselves it won't turn off
Jim,
Watch out: The fact that the pump continues to pump past its 50 psi cutoff setting is DANGEROUS risking a burst pipe or tank and injuring someone nearby.fixed.
Turn OFF the pump and open faucets immediatelyuntil the water pressure falls down to 30 psi or below.
Then let's be sure that the pressure tank air pre-charge is right.
With the pump turned OFF, drain water from the system until no water flows from a low faucet or from the tank drain.
Then check the pressure in the water pressure tank.
For a 30/50 pressure control switch set the tank air pre-charge (when pump is off and water has run until it stops) to 28 psi.
Explanation: with no water pressure in the building pipes and pump, if the water pressure tank's air pre-charge pressure is above the pump's CUT-ON pressure then switch will never turn on the pump.
If that is NOT the problem for your pump, then as you replaced the switch and the problem continues I suspect that either there's a wiring error or your switch is unable to properly sense water pressure in the system - for example that could be due to a clogged tube or pipe nipple that conducts water pressure to the switch.
My pump turns off at 85 psi - blew a pipe!
My pump blew a water hose. After getting it back together I saw it would turn on at 35psi and off at 85.tried adjusting the cut off but nothing changed even when nut was almost completely loose . I'm thinking the switch is bad ? On 2016-12-21 by Rob
by (mod)
Watch out: Indeed that's a dangerously-high pressure.
Your pump swich should be set to a CUT-ON of 30 psi and CUT-OFF of 50 psi at most.
Check for a pressure switch tube between switch and pump that's clogged with debris.
If cleaning that doesn't get the switchto work properly and if you can't re-set the switch to work properly I'd replace it.
...
We have a deep well. Bladder is 37 years old, but the problem existed for many years, even with a new pump. The problem is the pump stays on after using water for a few minutes, or if toilet is flushed. No water pressure to use the garden hose.
The pump will shut off after flipping the breaker switch.
We've learned to deal with the minor inconvenience of flipping the breaker switch off and on, but still wonder what life would be like if we didn't need to do that, and have enough water pressure to use the garden hose. On 2017-04-09 by Mark
by (mod) re: pump stays on
Mark:
Indeed flipping a power switch on and off is not a durable nor entirely safe long term solution to the problem you describe.
It's possible that the pump can't reach cutoff pressure due to impeller damage or wear, low voltage, piping leaks, or other problems described in thearticle WATER PUMP WONT STOP RUNNING.
Explanation: when you turn OFF power to the pump at the circuit breaker and then turn it back on (described at WATER PUMP ELECTRICAL SWITCHES), the reason the pump stays OFF at that point is that the pressure in the system is ABOVE the pressure control's CUT-IN pressure.
But when you run water and pressure drops BELOW the pressure controlc CUT-IN pressure, then the switch turns on the pump.
But if the pump is unable to reach the CUT-OFF pressure, (perhaps because the pump impeller is damaged, there's a well pipe leak, or the well flow rate is inadequate, or the pressure control switch sensor tube is partically clogged), then the pump simply keeps running.
Watch out: Look at the WATER PRESSURE GAUGE, or make an indepedent (and more accurate if your pump gauge is clogged too) WATER PRESSURE MEASUREMENT (how to): if when the pump is running on, if the pressure you see is BELOW the CUT-OUT pressure on your control switch (typically that's 40 or 50 psi) then the problem is in the pump or water supply.
But if the pump is continuing to run and the pressure is ABOVE the CUT-OUT pressure then the system is unsafe (risking a burst water tank or pipe) and the pressure switch and its pressure sensing tube need to be replaced. - Daniel
...
Good day sir. We replaced the pressure tank in our house recently and after intalling the same pressure tank our motor pump won't stop running.
The pressure control switch was set 25-35 psi but it only reaches about 32 psi that's why it won't stop. What could be the reason behind? I'm just a houseboy and I wanted to fix this thing as soon as possible before any damage occurs. Maybe you can help. Thank you. On 2016-10-25 by nathan
by (mod)
Nathan,
When the pump won't reach a reasonable shut-off pressure such as the one you specify something is limiting its pressure output: suspect one of the problems listed in the articleWATER PUMP WONT STOP RUNNING.
1. TURN OFF the pump asap so you don't burn up the pump motor.
2. The switch may itself be defective or may be debris clogged. Mud or silt in the water supply easily clog the small opening on the bottom of the pressure control switch through which water pressure has to tell the pump just what the pressure is. Burned or damaged switch contacts can also be the problem.
Other causes such as inadequate water in the well or a leak in well piping are described in WATER PUMP WONT STOP RUNNING. The simple things to try first are
1. turn off water into the building to rule out the problem being water running inside the building itelf
2. look for obvious leaks
3. replace the switch4. look for a damaged, cracked, broken, or clogged pump impeller or injector nozzle
by Deep well convertible jet pump (pump runs on, no pressure) - Problem Solved: Clogged nozzle.
RE: Grundfos (Aug.17) - Problem Solved: Clogged nozzle.
This was a tough one. I followed your helpful troubleshooting charts all the way through to pulling the hose and looking in the venturi. There was a clump of rusty clay the size of a small pea clogged in the metal nozzle tip under the plastic venturi.
One thing I wish I'd known first, and a caution to others... Don't fully remove the screws from the split well seal cap.
I lost both halves down the well and had to buy a new one - they're still down there.
Thanks again for this terrific website (and advice - "Don't Give Up"), I kept it open as an informative reference the entire time I was troubleshooting my well problem, which you helped me to eventually solve.
We got a new pressure switch and a new water tank because we were having different problems. I would like to know if I am watering the garden for 20-30 minutes, should the pump constantly run or should it shut off periodically in this time? Seems if we flush a toilet it doesn't always turn on right away and but sometimes it does. Our pump is underneath our house and sounds a lot quieter since we replaced the two items. On 2016-06-22 by Kimberly
by (mod)
If the rate at which you are taking water out of the system exceeds the ability of the pump (or pump and well if there 's a pump protection device installed) to deliver water, then yes, you'll be running water fast enough that the pump never reaches the cut-off pressure.
When you stop running water the pump should be able to reach cut-off pressure and then it'll stop: typically in just 1-3 minutes
Do you have any well service companies in the Wichita, KS you would recommend? I am not comfortable fixing any if this myself, and I would appreciate a recommendation from your site... this is the most in-depth well & pump info I've ever found!
Years ago I contacted a service to look at our old well pump (at least 15 years; the very rude technician told us they don't even make mine any more.) that was running continuously.
They came out & replaced the pressure switch. Now I've got the same problem, no water being used in the house and running constantly, very low pressure, gauge showing 0. I tapped on the tank & it sounds empty.
I shut off the pump via the breaker and am waiting 3 hrs minimum per your site to turn on. This is our only water source so I am scared! No idea how old or deep well is - house was built in 1929. On 2016-06-05 by Sarah
by (mod)
Sorry Sarah as there as so many thousands of well service companies around the world, we've not tried to compile a directory to that level of details. Good work on fixing the toilet; by the way, running water like that can also cause apparent water pressure and well problems; give your well a chance to recover now -if problems remain afte 24 hours, it's time to call an expert.
As I don't know details of what's going on at your system, and PROVIDED you have already made double sure that no water is running anywhere in your home, I can just suggest this simple test for selecting a contractor.
Ask the contractor a question that has just a little bit of technical detail like "how will you go about figuring out if my well is out of water?"
You don't have to know the right answer, Just listen to see if the contractor gives you an answer that contains information and sounds intelligent rather than posturing and bullying or arm-waving. IF the contractor says "Don't worry about it honey, we'll take care of it" that's reason enough to look further.Follwoop by Sarah - jiggling the toilet flush handle stopped my pump running-on problem
Hello again! I completely forgot to check the mudroom and a toilet in there we (obviously) never use, and guess what? Just basically had to jiggle the handle lol, and within a few mins the pump stopped & water pressure back up. Hooray! I feel like an idiot, but hey that's cheaper than repairs! Love the site, I will save it for next time! :-)
Last nite house "water-to-air" cooling system shut down -- safety switch shuts it down when water is not available. Well pump had stopped running.
Replaced well pump pressure switch and pressure guage. Well pump then reached 48 psi and ran continuously at that pressure even though ALL house fixtures and cooling system were shut off !!
The well pump would not reach the 60 psi cut-off point that was preset in the new pressure switch. I then tightened down of the large spring in the pressure switch. With all house water requirements turned off and turning the large spring tighter, the pump would not come above 48 psi and ran continuously. So then I loosened up on the large spring.
Now the pump turns off at about 46 psi. The pump is above ground, single-pipe, jet pump, about 25 years old. Also checked all pipes -- no leaks. This situation really mystifies me. I will appreciate any and all ideas, thiughts, suggestions. I would like to see it cut on around 30-35 and cut off around 50-55 approx. Thanks, Stan
This situation really mystifies me. I will appreciate any and all thoughts, ideas, suggestions - Stan L. Liteborn, liteborn@comcase.net
Reply: sounds like well runs out of water
Stan, the part of your well pump problem description that reads
"Replaced well pump pressure switch and pressure gauge. Well pump then reached 48 psi and ran continuously at that pressure even though ALL house fixtures and cooling system were shut off !!"
Suggests to me that either your well flow rate is inadequate - the water available from the well is insufficient - or there could be a leak in the well piping between the well and the house. Other problerms can look like an inadequate well flow rate, such as a leak in well piping.
Reader follow-up:
Here's present situation: Well pump worked last nite (7/21) and most of today. Late this afternoon, cooling system shut down again. Well pump motor was running, pump itself was too hot to touch and no water was available (opened tank drain faucet and only air came out). I shut off power to well pump, closed main water valve between tank and house and connected up to neighbors well.
This has better pressure than I've ever had but not enough volume to run the cooling system (too long a run with hoses from neighbor to me).
I will leave it this way till morning and then inspect along pipe route from house to my well, to see if any water is coming out of ground. Higher pressure from neighbors system may thus reveal your suggested .."leak in the well piping between the well and the house". If thats not it, looks like I have either a well or a pump problem --- or both
How to check well itself for broken/rusted out/cracked pipe? How to check for bad foot valve in well?
How to check for well sufficiency / water availability in well. How to check if pump is working, if it will pump water or is broken / worn out? Or is it the best approach to replace 1 item at a time till the problem is solved?? Where to start? Again, I really appreciate your interest and concern to assist with suggestions thus far. Hoping to hear from you with some thoughts about present situation and questions. Thank you so much, Stan
Reply: a hot to touch well pump sounds like the pump is running dry - things to check:
Stan, pump too hot to touch sure sounds like a pump running dry - and maybe a well without water. If you shut off all water into the house and water pressure still drops then that's why I suggested there may be a leaky check valve foot valve or piping. But your description makes us think it's a well problem.
In general it's reasonable to try replacing the less costly, easy to access questionable components first; Also if you end up needing to pull the well line for inspection/repairs, I would always install a new foot valve at that time.
...
...
Continue reading at WATER PUMP WONT STOP RUNNING - topic home, how to fix a pump that won't shut off, home page, or select a topic from the closely-related articles below, or see the complete ARTICLE INDEX.
Or see these
WATER PUMP WONT STOP FAQs-6 at InspectApedia.com - online encyclopedia of building & environmental inspection, testing, diagnosis, repair, & problem prevention advice.
Or see this
Or use the SEARCH BOX found below to Ask a Question or Search InspectApedia
Search the InspectApedia website
Need to make a private comment? Email editor@inspectApedia.com. We welcome email with your website content critique, corrections, suggestions or questions. Email is monitored daily but our workload may prevent an immediate reply. For immediate results, we hope you'll first try asking your question using the search box just above.
In addition to any citations in the article above, a full list is available on request.