Heating Zone Valve Flow Rates
This article describes the flow rates and gpm delivery capacity of hot water by heating system zone valves.
Page top photo: a bank of six heating zone valves each controlling a separate heating zone in a New York home. Usually these valves and heating zones are piped in 3/4" copper.
InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers, products, or services discussed at this website.
- Daniel Friedman, Publisher/Editor/Author - See WHO ARE WE?
Question: the effect on heat delivery if we install a smaller-diameter zone valve on a hot water or hydronic heating system.ac godbout
We live in a condo, our zone valve was changed recently and reduced from 3/4 to 1/2, what effect will that have on heating in colder temperature like -35degrees Celcius - 2021/11/10
This Q&A were posted originally
at HEATING SYSTEMS - home
Photo at left: Honeywell (TM) 1/2" diameter sweat-type zone valve.
[Click to enlarge any image]
Thanks that's a helpful question: the effect on heat delivery if we install a smaller-diameter zone valve on a hot water or hydronic heating system.
Bottom line: there will be no noticeable difference between the heating water flow rate through a 3/4" zone valve and a 1/2" zone valve, if we simply take as an example the Flow Capacity (Cv) ratings given for each of those products (illustrated above).
Both the Honeywell 1/2" sweat-fitting zone valve (#V8043E1004) and the Honeywell 3/4" sweat-fitting zone valve (#V8043F1036) have identical Flow Capacity (Cv) ratings of 3.5 according to the manufacturer's literature.
FYI Flow Capacity or Cv is defined as
the volume of water at 60°F (in US gallons) that will flow through a valve per minute with a pressure drop of 1 psi across the valve.
Below in a fancier calculation I set out to demonstrate why the two valves can deliver essentially the same heat rate in gpm or BTUs.
The Flow Characteristic Cv Charts shown below give data for three different zone valve settings or capacities, at Cv's of 1, 3.5 and 8, excerpted from the Honeywell zone valve installation instructions cited at the end of this article. 3.5 Cv is the standard rating for these zone valves.
[Click to enlarge the Cv chart shown below.]
You will want to take a look at
WATER SUPPLY PIPE DIAMETER vs FLOW
where we argue that changing pipe diameter in any water flow system does have some effect, potentially significant, on flow rate.
On that page we give some data
But if ONLY the zone valve diameter was reduced from 3/4" to 1/2" - that's just about 3-4 linear inches of piping, in our OPINION you won't be able to detect the reduction in heating water flow nor BTU delivery to the occupied space .
That's because the impact on flow rate is small until the linear feet of change in pipe diameter is quite a bit more than 3-4 linear inches.
Here's an example using PEX tubing: (I know yours is probably copper but this is just data that we already had and that allows a clear example)
So while the pressure drop is significant when the diameter of piping gets smaller, notice that it's per 100 ft. of run.
Going from 3/4" to 1/2" gives us a drop of 1.36 gpm over 100 ft.
Now if we calculate the pressure drop over 4 inches: I make that to be
(4/1200) x 1.36 = 0.0045 gpm reduction in flow rate - or really really tiny.
A typical hydronic heating circulator pump like a Taco 007-F5, at 1 ft. of head, pumps at about 22 gpm.
So your reduction in gpm would be
0.0045 / 22 = 0.002 or about 0.2% reduction in the gpm delivery rate of hot water through your heating baseboards or radiators - not much, right?
Ask your heating service company if they have a different way to calculate the effect we're describing.
Watch out: Reducing large lengths of heating pipe in diameter can make a significant reduction in the rate of heat delivery in the building.
Illustration courtesy of Carson Dunlop Associates, a Toronto home inspection, education, and report writing tool firm.
...
Continue reading at ZONE VALVES, HEATING, or select a topic from the closely-related articles below, or see the complete ARTICLE INDEX.
Or see these
ZONE VALVE SIZE vs GPM at InspectApedia.com - online encyclopedia of building & environmental inspection, testing, diagnosis, repair, & problem prevention advice.
Or see this
Or use the SEARCH BOX found below to Ask a Question or Search InspectApedia
Search the InspectApedia website
Need to make a private comment? Email editor@inspectApedia.com. We welcome email with your website content critique, corrections, suggestions or questions. Email is monitored daily but our workload may prevent an immediate reply. For immediate results, we hope you'll first try asking your question using the search box just above.
In addition to any citations in the article above, a full list is available on request.