What causes flooding in steam boilers - why is the steam boiler water level too high?
Here we explain all of the various causes of excessive water levels in a steam heating boiler and causes of boiler priming or surging, and we suggest the remedy or repair steps for each of these problems.
Keeping the proper amount of water in a steam boiler is a critical function for both safety and to avoid damaging the boiler itself.
InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers, products, or services discussed at this website.
- Daniel Friedman, Publisher/Editor/Author - See WHO ARE WE?
Water level in the sight glass is seen to suddenly surge or move up and down repeatedly while the steam boiler's burner is on.
Note that it is normal for the water level in the sight glass to drop to a lower point during steam boiler operation, rising again to its proper level as condensate returns to the boiler at the end of a boiler-on cycle.
But if you see sudden or rapid up and down movement of water in the sight glass, the boiler is priming or surging.
Watch out: surging in a steam boiler, because it can include intermittent too-low water levels in the boiler, can cause the water feeder to over-feed the boiler, leading to steam boiler flooding.
[Click to enlarge any image]
Our photo shows a typical steam boiler sight glass - a key place to look when checking that the steam boiler water level is set properly. More information about using the sight glass to maintain steam boiler water levels is included in the boiler sight glass article link given just below.
Water level inside the steam heating boiler is above the manufacturer's recommended level.
A flooded steam boiler will have trouble sending steam up into the building's heating system, resulting in poor heat or no-heat complaints.
The sketch at page top shows how to read the sight glass on a steam boiler. If water level in the sight glass is above or below the recommended level the system needs attention.
2017/04/23 Anonymous-2 said:
What causes high water level readings in the site glass.
What causes the water level line in the sight glass to "bounce" up and down when the steam boiler is on?
This question was posted originally
2017/04/18 Anonyous-2 said
I've had a boiler for seventeen years with no problem. When the water in the sight glass goes below a certain level, there's an auto shutoff mechanism that is triggered and a red light goes on. I just fill it until the light goes off and alls well.
Recently I took the sight glass off [of my steam boiler] to clean it No problems for a few weeks, but now the safety/red light is being triggered by it being over the sight line.
Never had that problem before. Drained it and and refilled to proper level and hit reset/on off switch for the shutoff and it light went out, but this morning the water level was above the shutoff level but shutoff triggered/red light on.
The boiler low water cutoff or LWCO is a McDonnell unit. It says McDonnell & Miller ITT. Serial no at top PS-801-24
Any ideas? Thanks for any input. - 2017/04/18 by private email to editor
Reply: It is not likely that simply removing, cleaning, and replacing the sight glass would itself cause abnormally high (or low) water levels in a steam boiler.
High water readings in the sight glass of a steam boiler, also referred to by the pros as a flooded steam boiler are most-likely caused by one of the following, of which surging is perhaps the most common problem.
Here is a RECORDING OF BANGING PIPES at a STEAM BOILER [2MB .m4a sound file recoreded 2015/11/29] provided by a reader whose comments follow.
Play this file with iTunes or Quicktime or Windows Media player.
Under-sized steam piping
leaving the boiler can cause both surging and steam boiler banging or knocking sounds similar to water hammer. An under-sized steam riser at the boiler will cause steam to move upwards at such high velocity that it may pick up and bring water from the boiler itself, causing boiler water level to drop, then return - surging.
The water feeder may then feed more water into the boiler; later as condensate and water return to the boiler the boiler will be over-filled or flooded.
Remedy: Check the steam supply riser pipe size against the boiler's installation instructions.
An over-sized burner or over-fired burner
can over-heat water in the boiler too quickly, also a cause of steam boiler surging. The burner flame should not impinge any surface in the combustion chamber.
Over-firing can in turn cause both bubbling at the point of flame contact with water-containing sections of the boiler and also sooting that reduces heat transfer and increases heating cost.
Remedy: the service technician needs to check the boiler firing rate and the flame for impingement and to adjust the burner (gas or oil) as needed.
Below: an image of some of the interior electrical components of the McDonnell & Miller 801 series LWCO control provided by the reader.
...
Below you will find questions and answers previously posted on this page at its page bottom reader comment box.
STEAM HEATING SYSTEMS & CONTROLS does not say what causes high level of water in the steam boiler.
Why your boiler in the few days became over flooded.
On the steam heating system page that you cite above, you will find this statement:
Also see STEAM BOILER FLOODING / SURGING REPAIR where we explain the causes of water too high in the sight glass or in the steam boiler - causes of high water level in the steam boiler.
But to help out, here's a bit more detail:
An inspection by a trained heating tech will surely be more reliable than an online guess sight-unseen, but here are some common causes of steam boiler flooding:
- Failure to adequately flush the LWCO can leave sludge in the system, or even just dirty boiler water can gum up operation of the automatic water feeder so that it is not closing completely when it should.
- Surges in the water line can cause the automatic water feeder to also surge and insert extra water into the boiler; dirty or oily water in the boiler can cause surging. If this is the case the boiler needs cleaning.
- High pH in your water supply can cause foaming and water feeder troubles; but if your boiler flooding problem is an new trouble on an old system I tend not to suspect this cause - unless your water system source has also recently changed; If you see foamy water in the sight glass this could be the problem.
- Tankless coil leaks - some steam boilers and many hydronic boilers make domestic hot water with a tankless coil. If the coil itself is leaking, because house water pressure (inside the coil) is higher than boiler water pressure, the leak will flood the boiler.
If you have a tankless coil on your steam boiler you might diagnose this by turning off water into the tankless coil and observing if the boiler flooding stops.
- A gravity condensate return with motorized heating zone valves: this explanation is a bit technical, but basically, the operation of the zone valve can interrupt condensate return causing the automatic water feeder to send more water into the boiler.
- Steam boiler running too hot: for example if the oil burner nozzle was changed to a higher gph rate the boiler may be over fired, causing steam to leave the boiler too rapidly for the condensate return rate - I see this as a different type of surge that causes the water feeder to send water into the boiler; then as the condensate later returns the boiler is flooded
- B&G CounterPoint from September 1996. B&G is a producer of heating system control
- Automatic water feeder bypass valve leak: if your automatic water feeder has a manual bypass loop and valve that valve might be open or leaky.
- B&G and some other manufacturers point out that on occasion someone else is adding water to the boiler - improperly - causing boiler flooding
- Steam boiler piping not properly sized or installed around the boiler - but if this is the cause of boiler flooding you'd see this problem probably from day one of the installation.
- Automatic water feeder not properly installed - e.g. too high on the boiler - but if this is the problem you'd get flooding from day one of the installation.
2021/02/03 Reader M.K. wrote:
Hi there, I have a residential steam boiler that keeps flooding and has to be drained for 40 minutes twice a week.
The weird thing is the water is turned off to it and it keeps flooding. Any thoughts? Plugged pigtail? Bad pressure switch. I have seen 15 psi once or twice before draining it. Thank you for your time -
Matt Krewer - mkrewer@towncountryservices.com
Service manager
Town and Country Services
Tonica,Il 61370 USA - offices in Princeton IL and Tonica IL.
Tel: 815.220.5107
Website: https://www.towncountryservices.com/contact/
Typically that is a delayed condensate return problem
Any ideas on what I can check to confirm that?
I think we're maybe people would do if you could hire a heating professional who's familiar with Steam Heat and he or she would try flushing the piping in condensate system
I am a heating professional, familiar with steam heat just a weird situation. Thanks anyway
Oops. Got it. I still think about this some more and I'll see what else I can come up with. At least you should be gratified that I was telling a stranger to call a heating professional.
Definitely! I went over today, cleaned out the pigtail, the pressure switch, replaced the sight glass and cleaned the ports. The boiler is set for 2 psi, the sight glass was 2/3 full. I watched it cycle on pressure but from some reason it keeps flooding with the water turned off to it.
Two things. If this is a residential system is typically should be operating around point five PSI so if someone has said it to 2 PSI that's telling us that they had a problem pushing steam somewhere.
Sometimes, in turn, that's a clue that there is a rust or debris clogged somewhere or that there's improper routing of piping.
Second, if I understand you correctly, you got water turned off at the water feeder.
There should be no other potential water source except for condensate. So if the boiler is flooding that's telling me that there's a condensate blockage and very slow return to the boiler such that while the boiler is operating the water feeder is feeding more water in.
I don't remember if we test on this before but is this a 1 pipe or a two pipe steam system?
It is a one pipe system and he also mentioned a couple radiators had been removed. I’ve only been working on it a couple years but he said the last few years it has flooded. All the way up to the second floor I appreciate your time
Let me say before going further that I don't want to pose as a Superworld a class steam expert. I have worked on in debug some steam systems and of course I'm interested in them and have written about them. The expert of course is Dan Holohan .
What do you think about this? For the system to flood up to the second floor suggests that there may be multiple blockages in condensate return. It seems to me that if the blockage were only on a lower floor that steam entering those radiators would flood those radiators and then stopped entering the radiator so it couldn't produce enough condensate to push water up to higher floors.
Also although we don't know where the problem is yet we know there's been a history of Trouble getting steamed to the various Heated areas otherwise you wouldn't have seen the pressure pushed up to four times normal PSI.
It's just an opinion but I also think that in a one pipe system it's easier to get a clogged and malfunction at a radiator base because you have to have available that flows steam in one way and condensate the other.
It's a bit more complex and it's possible the openings are smaller. In an old building there's plenty of opportunity for us to fall down in the radiator and clogged the condensate return.
What do you think about going to one of the radiators and pulling off he steam entry and condensate return at the radiator bottom to see what you find. If you choose one that's been reported to have been cold frequently are continuously we're more likely to see a lot of rust and crud in the radiator bottom. It may be that the client is facing an extensive cleaning As well as some parts replacement .
You probably know better than I that most of these systems also have other traps In the steam piping besides at radiators so this Stepping in the bugging, following the piping and finding One or more of those .
Watch out: Also double check that the water feed shutoff is fully, truly off.
Awesome thank you for your time. I really appreciate it. I’ll look into this
When I should have been sleeping last night the shutoff valve question turned its squeaky handle until I had to get up and sneak into the living room to send a text about it.
I've seen stop valves that leaked due to a groove in valve seat or a damaged washer, and gate valves that you think are closed but are not fully down (sometimes the stem breaks). A ball valve is often more reliable.
Anyhow as you know, even a slow leak at a stop valve, just like a leaking water feeder, an fill up piping to the top of a building.
It's similar to the problem of a leaky diaphragm on a pressure-reducer water-feeder valve used on some boilers.
I'd check that first before tearing open any piping.
There are actually 2 ball valves between the meter and the valve I’m seriously doubting it would go through 2 and the meter wasn’t turning at all while I was there.
So we have slightly simplified the task;
Think about what else we can eliminate;
In sum it sounds as if enough steam is making it upstairs to then condense and fill piping all the way back down; That is, I'm doubtful that condensate from downstairs would somehow get pushed upstairs
- unless there is a condensate collection container and return pump somewhere in the building - not common on residential buildings with their own steam boiler.
On 2014-10-15 by Ori - too much water in my boiler
I have a 20 year old Peerless gas fired steam boiler. Lately I find my self removing water from the boiler rather than adding water.
The boiler has a manual feed water valve. Every few days theremseems to be more water than before.
Any suggestion?
On 2014-10-15 by (mod) - signs of steam boiler flooding
Yes, usually when the steam boiler water level is too high that means that there is a delay in condensate returning to the boiler followed by an automatic water feeder valve adding makeup water. Then as the system cools off and condensate finally returns, there will be too much water in the boiler
Your heating service tech will look for a clogged condensate return line or clogged steam trap.
(Apr 1, 2013) Luis said:
I have a gas bolier which continues to overflow. The sight glass floods even some pipes that run though the floor ang o up the wall with a steam trap a gauges at the to of the pipes. I called a company but they have not been able to find the problem.
Luis if the steam boiler keeps overflowing, or flooding, most likely the water feeder is out of order.
See details at STEAM BOILER FLOODING / SURGING REPAIR
...
Continue reading at WATER FEEDER VALVE, STEAM or select a topic from the closely-related articles below, or see the complete ARTICLE INDEX.
Or see STEAM BOILER FLOODING REPAIR FAQs - questions & answers about flooded steam boilers, posted originally at this page.
Or see these
STEAM BOILER FLOODING / SURGING REPAIR at InspectApedia.com - online encyclopedia of building & environmental inspection, testing, diagnosis, repair, & problem prevention advice.
Or see this
Or use the SEARCH BOX found below to Ask a Question or Search InspectApedia
Questions & answers or comments about how and when to use and maintain the water feed valve on steam boilers
Try the search box just below, or if you prefer, post a question or comment in the Comments box below and we will respond promptly.
Search the InspectApedia website
Note: appearance of your Comment below may be delayed: if your comment contains an image, photograph, web link, or text that looks to the software as if it might be a web link, your posting will appear after it has been approved by a moderator. Apologies for the delay.
Only one image can be added per comment but you can post as many comments, and therefore images, as you like.
You will not receive a notification when a response to your question has been posted.
Please bookmark this page to make it easy for you to check back for our response.
IF above you see "Comment Form is loading comments..." then COMMENT BOX - countable.ca / bawkbox.com IS NOT WORKING.
In any case you are welcome to send an email directly to us at InspectApedia.com at editor@inspectApedia.com
We'll reply to you directly. Please help us help you by noting, in your email, the URL of the InspectApedia page where you wanted to comment.
In addition to any citations in the article above, a full list is available on request.