Building Inspection, Diagnosis & Repair Info

Low Voltage Transformer (C) Daniel Friedman Low Voltage Transformer FAQs

  • POST a QUESTION or COMMENT about wiring & testing low voltage transformers for HVAC equipment like air conditioners or heaters & in low voltage wiring systems

Low voltage (12-24 VAC) transformer repair questions & answers:

Diagnosis and repair of low voltage transformers used on air conditioners, boilers, water heaters, doorbells, etc.

This article Series explains how low-voltage transformers are used on heating, heat pumps, & air conditioning systems to provide power for thermostats, zone valves, and other relays and controls.

InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers, products, or services discussed at this website.

- Daniel Friedman, Publisher/Editor/Author - See WHO ARE WE?





ADVERTISEMENT





Low Voltage HVACR Transformer Questions & Answers

Low voltage transformer for heating or air conditioning (C) Daniel Friedman

These questions & answers about building electrical systems, wiring, & components were posted originally

at LOW VOLTAGE TRANSFORMER TEST - be sure to see the suggestions at that page.

Question: Can a transformer be tested for proper output voltage while connected and furnace running?

(Feb 24, 2013) Brad said:
Can a transformer be tested for proper output voltage while connected and furnace running?

I have a Carrier Weathermaker SX 58sxa080-101gg; the system won't hold temp set, it completes one heat cycle stops then won't restart to keep the set temp.

The transformer is behind the blower door; when I cycle the power to the furnace or remove and re-install the blower door, the furnace resets and works again for another heat cycle.
When I test for 24v T-Stat voltage while running I get 0v, I get 26v with the transformer disconnected on the 24v side.

Will a bad transformer reset and work for awhile after the 110v power has been cycled?

How can I test the components behind the blower door during a no-start situation when everything reset to working condition after the power is cycled (when I remove the blower door)?

Reply:

I would disconnect the wires from the low voltage terminals and check the output with a VOM to confirm the output voltage level.

 

Comment: The frequency is NOT changed by running an AC signal through a transformer.

(Jan 15, 2015) Kurta said:
"Low voltage transformers convert 50Hz or 60Hz (cycle) line voltage (120 to 240V) AC (alternating current) to low voltage typically 12, 18, or 24 volts AC at a high frequency Hz, possibly as high as 20 to 50KHZ, that's 20,000 to 50,000 Hz."

This is simply wrong. The frequency is NOT changed by running an AC signal through a transformer. In general, transformers are step-up (less current, more voltage) or step down (less voltage, more current). But the conversion takes place at the same frequency and either in phase or 180 degrees out of phase depending on which way you connect the secondary terminals.

Switching power supplies (DC) have high(er) frequency components - but there's a LOT more going on there than in a simple transformer.

Reply:

Thank you for your comments, Kurta; we'll review the article as well as our original technical sources (also cited at REFERENCES for each article).

Here is a direct quote from low voltage transformer experts at just one of our sources over at Pegasus lighting:

Quoting
The output of an electronic low voltage transformer, unless it is a DC low voltage transformer, is high frequency (20,000-50,000 Hertz). This means that there can be a substantial voltage drop if the wires carrying the high-frequency current are long, thin, or far apart.

If you want to be identified as a contributor or have other remarks that you want to suggest you can indicate that here as a comment or you can contact me directly by email - see our CONTACT information at page top or bottom.

Thanks again

Daniel

Question:

(July 8, 2015) steve said:
if the 24vdc transformer is bad will the air handler still come on

Reply:

Maybe not - if that particular transformer controls the thermostat that turns on the air handler or is one that powers a control relay in the unit.

Question: sometimes it seems to hum

(June 13, 2015) mike said:
mine has 2 fuses the glass type sometimes it seems to hum

Reply:

Humming buzzing transformers are discussed in the article above: I'd replace the unit.

Question: no low voltage to the thermostat

No low voltage to thermostat. Will not come on, simple 7 wire. Simple heat, cool, and em settings, plus fan on or off. Is there a fuse or reset button in the system? AMERICAN STANDARD, HERITAGE 11, manufactured Sept, 2000

Reply:

Robert

Check for voltage right at the low voltage transformer, then

see

inspectapedia.com/heat/American_Standard_Thermostat_Wiring_Guide.php#FAQ

with millions of readers, I'd sure be grateful if you'd post a question in just one place.

Question: I disconnected the LV transformer by mistake

(Oct 6, 2015) Fernando said:
I think I disconnected the LV transformer by mistake, thinking it had to do with the phone line. Now when I turn on the boiler the thermostat only registers the heat but does not control it (house keeps getting hotter). Please could that be it?

Reply:

If you disconnected the transformer controlling a thermostat it won't call for heat; it won't work.

Question: using the furnace LV transformer for the air conditioner?

(Nov 21, 2016) Anonymous

We had a repair man rig / hook our A/C up to our furnace transformer to get us A/c this past summer. He said the low voltage transformer went out for the A/C, but he could rig it so we would have A/C through the furnace transformer.

He was to look into replacement cost for A/C transformer & get back to us, but never did & I didn't care because we had air.

Well now we are trying to light the pilot light for the furnace & he must have taken the furnace wire off the transformer. He said he wasn't going to & for us to make sure the outside A/C unit didn't keep running once we started the furnace, but we can't get pilot light to even light. How do we look or tell if he took the furnace wire off from the transformer?

Reply:

You would follow the low voltage wiring from the control board or from the thermostat back to see which transformer is powering those devices.

The repair you describe may be just fine, as long as both transformers provide the same voltage AND provided that the in-use transformer isn't being overloaded by asking it to support too many devices.

Question: low voltage transformer was burning up and now blows a fuse

(Nov 20, 2016) AUTHOR:Anonymous (no email)

COMMENT: I have airhandler that was burning up the transformer. I put a fuse in and took all low voltage wire loose. What is causing the fuse to blow

Reply:

If the circuit blowing the fuse is for sure the air handler, not the outdoor compressor/condenser, I'd be looking for

For 120V circuits:

1. a shorted or loose wire connection
2. a fan or blower motor that is seizing up
3. a shorted relay or control board

For 24VAC or similar low voltage circuits, look for shorted low voltage wires or shorts at a low voltage relay

...

Continue reading at LOW VOLTAGE TRANSFORMER TEST or select a topic from the closely-related articles below, or see the complete ARTICLE INDEX.

Or see these

Recommended Articles

Suggested citation for this web page

LOW VOLTAGE TRANSFORMER FAQs at InspectApedia.com - online encyclopedia of building & environmental inspection, testing, diagnosis, repair, & problem prevention advice.

Or see this

INDEX to RELATED ARTICLES: ARTICLE INDEX to ELECTRICAL INSPECTION & TESTING

Or use the SEARCH BOX found below to Ask a Question or Search InspectApedia

Ask a Question or Search InspectApedia

Share this article:

Search the InspectApedia website

Need to make a private comment? Email editor@inspectApedia.com. We welcome email with your website content critique, corrections, suggestions or questions. Email is monitored daily but our workload may prevent an immediate reply. For immediate results, we hope you'll first try asking your question using the search box just above.

Citations & References

In addition to any citations in the article above, a full list is available on request.



ADVERTISEMENT