Circulator Pump Relay Control FAQsFAQs about hot water heating system circulator pump control relay troubleshooting & repair.
In this article series we list & describe both circulator pump relay controls and other heating system controls that manage or impact heating boiler circulator pump operation.
Page top photo: Taco's SR503 switching relay that can control 1 to 3 circulator pumps.
InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers, products, or services discussed at this website.
- Daniel Friedman, Publisher/Editor/Author - See WHO ARE WE?
These questions & answers about circulator relay controls or switches (used to turn hydronic heating system circulators on or off) were posted originally
at CIRCULATOR PUMP RELAYS & OTHER CONTROLS - be sure to see the advice and circulator controls discussed there.
See our index to questions & answers about installing or repairing heating zone circulators at
CIRCULATOR PUMP REPAIR FAQs - index
Photo above-left: a primary or single circulator pump relay switch is found inside of many aquastats such as this Honeywell / Resideo L8182D Aquastat.
I have a 2 zone heating system with 2 circulating pumps when the top floor is turned up the furnace kicks on and heats the top floor.
When the first floor is turned on you hear a click noise from the t-stat and nothing happens went down stairs to boiler the circulation pump for the top floor is working and the pump for the first floor doesn't turn on. replaced the pump still not working.
Removed panel for the aquastat removed the 2 wires for t-stat.
I put a jumper wire on the 2 t-stat terminals.
The primary control relay clicks but the circulator pump still doesn't turn on.
Is it a bad aquastat? (Mar 30, 2015) rusty
Reply: check the circulator relay
If the circulator relay is not pulling in it's a bad relay or control.
If the relay pulls in and voltage is being delivered to the pump but the pump does not run it's most likely either an open wire or a bad pump.
Rusty said:
I wired the pump to a cord that plugs into the wall and the pump turns on.
Reply:
So we know the pump is good.
Check the wiring for continuity and check all connections.
Check whether or not the circulator relay pulls in and when it does if voltage is given to the pump.
Watch out: there are electrocution hazards in what you already did and in what you might do
Rusty said:
All the connections look fine. when I used the jumper wire the relay moved in and when removed the wire the relay pulled back
Moderator reply:
Sounds like a bad circulator relay.
When I turned the 2 thermostats up to start heating the outbuilding this fall, without response, I found the circuit breaker to the boiler circulating pump was tripped, and continued to trip immediately after each time I reset it.
The system is about 16 years old-2 zone, has a Honeywell R8285a-1048 relay and a Grundfos type UP 15-42f circulating pump. Where would be the best place to start troubleshooting this problem? On 2017-12-14 by Jerry
by (mod) -
I would go to the boiler and disconnect power to the primary control. And turn the breaker back on.
If it Trips Again then since you've disconnected everything that your heating system you would expect the problem to be in the circuit wiring itself.
Peerless boiler firing hot water at showers...baseboards cold not heat..no air in lines...taco circulator pump only 5 lbs pressure on gauge at furnace....is there a relay to check if it's working On 2016-12-18 by Michael
by (mod) -
Michael:
5 psi is abnormally low - if the gauge is accurate there's probably a leak and also a defective water feeder valve. At low pressure the circulator may not be able to push hot water up to baseboards at higher levels.
Switch relay r8845u won't start 1of 2 circulator pumps On 2015-11-27 by Tim
by (mod) -
Tim, usually each pump has its own start relay. One of these relays, or its controlling thermostat mat be bad.
Hi - we have a two-stage boiler in our 4-unit mountain condo unit that provides hot water for consumption as well as for sidewalk ice melt (heated glycerine lines).
The unit is about 8 years old, and we're being told by the company that services it we need to replace two relays and a "clock" for each boiler stage.
Is 8 years a reasonable lifespan for relays? And do you have any idea about what is the "clock" that needs replacing? Thanks! On 2014-05-31 by JeffHOA
by (mod) -
Jeff,
Sorry I don't know what the tech is referring to either.
Relays that control the switching of equipment might need replacement if the relay was burned or damaged, and such damage could occur in the time you cite.I don't know what clock they're talking about. Perhaps you could ask that someone point out the part to you - note its brand and model number and let us know.
I suspect that a clock / timer is being used to run the boiler to de-ice sidewalks during certain times of the day or it's providing more detailed controls over boiler internal operation cycles.
Danielby JeffHOA
Thanks, Daniel - will check on the clock and let you know. Appreciate the validation on the relays.
...
Daniel, I heard from our maintenance manager who is coordinating the boiler repair.
He says: "The clock is to time and signal cycles (eg, pre purge, attempt to light, post purge, etc. ).
The boiler company recommended the clock be changed out along with the failed relay."
Sounds like it's not that expensive, but funny that something like an electronic clock would need to be replaced. Thanks for your help.
by (mod) -
Jeff
Thanks for the clarification. Your view is reasonable.
I think tech figure it's easier and safer to swap out multiple old parts (even if some may be ok) than to have to return to the job. Considering service call costs it may be a less expense approach overall
I have a hot water burner with a circulating pump when does the pump start? does it start at a certain temp.?
would you see the shaft spinning when it starts? it is a taco 110 pump. (Oct 27, 2015) John said:
Reply:
John, on most heating boilers in the U.S. the thermostat turns on the circulator pump while independently, the temperature of the boiler, controlled by the aquastat, turns the burner on or off.
When room temperature falls below the set temperature on the thermostat then the circulator pump will start.
In Canada at many hydronic heating system installations the circulator runs continuously and the thermostat will turn the boiler on when room temperatures fall below the set temperature on the thermostat.
See AQUASTAT CONTROLS - home
and
See CIRCULATOR PUMP RELAYS & OTHER CONTROLS
and
See THERMOSTATS, HEATING / COOLING - home
Is the circulate pump still running for 2-3 munites after the boiler shuttoff normal ?
Also the circultor pump starts running for 30 seconds before the boiler turns on On 2014-02-19 by gary
by (mod) -
Gary that sounds correct. When heat is running the boiler will shut off when its internal temperature reaches the HI limit.
The circulator will continue to run until the call for heat is satisfied at the room thermostat.
When heat is not already running, when the room thermostat calls for heat the thermostat turns on the circulator to send hot water to the heating zone baseboards or radiators; as returning cool water drops boiler temperature the boiler's burner will then turn on.
Circulating pump stop working but when I turn off and back to on the furnace then it starts working. On 2014-02-11 by circulating pump
by (mod) -
Circ:
It sounds as if there may be a problem with the circulator relay or even the pump itself;
...
...
Continue reading at CIRCULATOR PUMP RELAYS & OTHER CONTROLS - topic home, or select a topic from closely-related articles below, or select a topic from the closely-related articles below, or see the complete ARTICLE INDEX.
CIRCULATOR PUMP RELAY FAQs at InspectApedia.com - online encyclopedia of building & environmental inspection, testing, diagnosis, repair, & problem prevention advice.
Or see this
Or use the SEARCH BOX found below to Ask a Question or Search InspectApedia
Try the search box just below, or if you prefer, post a question or comment in the Comments box below and we will respond promptly.
Search the InspectApedia website
Note: appearance of your Comment below may be delayed: if your comment contains an image, photograph, web link, or text that looks to the software as if it might be a web link, your posting will appear after it has been approved by a moderator. Apologies for the delay.
Only one image can be added per comment but you can post as many comments, and therefore images, as you like.
You will not receive a notification when a response to your question has been posted.
Please bookmark this page to make it easy for you to check back for our response.
IF above you see "Comment Form is loading comments..." then COMMENT BOX - countable.ca / bawkbox.com IS NOT WORKING.
In any case you are welcome to send an email directly to us at InspectApedia.com at editor@inspectApedia.com
We'll reply to you directly. Please help us help you by noting, in your email, the URL of the InspectApedia page where you wanted to comment.
In addition to any citations in the article above, a full list is available on request.