Q&A on how to choose the settings for a heating boiler aquastat control:
This article series explains how to choose the best settings for a heating boiler aquastat - the combination control that sets boiler temperature and may also control hot water production via a tankless coil on the heating boiler.
InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers, products, or services discussed at this website.
- Daniel Friedman, Publisher/Editor/Author - See WHO ARE WE?
These questions & answers were posted originally
at AQUASTAT HI LO DIFF SETTINGS - please be sure you review the advice given there.
The photo at page top shows a the "HIGH" or "HI" setting on a Honeywell R8124A combination heating control, also called an "aquastat".
...
Hi, Jim Hickey again. I wrote to you on 12/16/22. You asked for more info on aquastat. First I'd like to say Thank-You.
Wood boiler 1981 Jenson
Serial #2699
Old aquastat Honey Well
125017AAA7942
New aquastat Risideo
HWL7224U1002
Oil boiler Weil-McLain
Boil size A-B-0815
Series 3 CP0180134?
Old 1977
Don't know old aquastat ??
New aquastat relay
Type L8124A,C
I know not the best Info. Any help or direction to go, would be appreciated. On 2023-01-28 by Jim Hickey -
Reply by InspectApedia Publisher - Resideo L7224U1002/U is a Universal Electronic Oil Aquastat
@Jim Hickey,
Diagnostic might be your observation that the behavior of the boiler has changed from a "normal" or "longer" on-cycle to a much shorter and by your description very regular and unsually-brief on-cycle. So what's changed? When you get an on-site, experienced, service tech s.he will doubtless look at
- control settings
- signs of proper or improper boiler tune, combustion air, operating temperatures, cvntrols
- circulator pump operation
- adequacy of thermal contact of the aquastat's thermal sensor in the sensor well
- (less likely) thermostat wiring and operation
- any changes to control settings or wiring from prior conditions
Your Resideo L7224U1002/U is a Universal Electronic Oil Aquastat with EnviraCOM communication
That means it can be wired and set up for almost any residential heating boiler operating requirement, and it adds a feature that permits addition of an outdoor temperature sensor that adjusts what the aquastat does in an effort to improve system operating economy.
SO do let us know what the onsite service people have to say.by Jim Hickey - some heating pipes may need air bleeding
@InspectApedia Publisher,
Unfortunately, the tech called back and said they'd have to reset the system by bleeding the pipes to the whole house before diagnosing instead of replacing parts and that would take half a day, at $149/hr minus 25% for having the gold contract.Does bleeding the whole house of water make any sense? I get the impression they mean actually removing all water.
I'm sorry to go over this again, but I'm confused why all baseboards and pipes are warm/hot, and when I bled the baseboards upstairs that have valves (no valves on the baseboards in the 2 downstairs rooms) only water came out. I've been told even though we have baseboards downstairs and upstairs that if there's only 1 thermostat, that it's all one zone.However, I do occasionally hear water moving in some pipes in the unfinished ceiling that's the floor under the living room. Those pipes have blue faucets on them.
Should I be bleeding them as well? I just went down to take more pictures of the pipes at the boiler and heard some of what I'm assuming is water bubbles moving through the pipes there as well, so there still must be air, but why isn't it at the valves?
by InspectApedia Publisher - air trapped in heating lines blocks or partly blocks hot water flow
Jim Hickey
Not quite.
There can be air trapped in heating lines that blocks or partly blocks hot water flow somewhere in the loop of heating piping, yet that air may NOT find its way to bleeder valves at individual radiators or baseboards. If a tech suspects that she/he will use a more forceful method (a pony pump) to push water at enough pressure and volume through the system to get rid of any such air.
Air gets trapped at such intermediate location in building heating piping probably as a feature of the pipe horizontal run lengths and lack of slope, possibly affected by the sequence or location of elbows, valves, etc.
The fact that you SEE drain valves installed mid span in some of your piping - like in your photo - suggests that perhaps that someone has had this problem in this building before. But I do NOT advise that YOU try opening the two drain valves in your photo.
From just the photo we don't know where or what those are, and even if they're indeed on heating runs, you don't have the necessary equipment nor training and you might get scalded (burned) or might make the heating system performance even worse.
Let us know what the heating technicians do and what is the result.by Jim Hickey
@InspectApedia Publisher,
So it sounds like we have no choice but to either let it continue running inefficiently, or let them bleed the entire system's pipes, which they say will take half a day? Why would it take that long? This is baseboards, not radiant floor heating that I assume would have a lot more piping.
I think you'd suggested the check the system for overfiring? I found and read an article that also maybe indicates a possibility of the oil pressure being off. Shouldn't they be checked first? https://www [dot] achrnews [dot] com/articles/91933-btu-buddy-11-handling-an-over-fired-boilerby InspectApedia Publisher
@Jim
Sorry, but no, I've exhausted this topic. I've outlined and we've been over every situation suggested by your comments, questions, and discussion - for which we thank you.
In my OPINION it's past time to - that is now quite overdue - to pay for an onsite heating professional.
Do let us know what the service manager and service technician ultimately say and do - as that might help other readers.by Jim Hickey
@InspectApedia Publisher,
I was able to get the tech service manager here. There was air trapped in the system, forcing most of the water to recirculate right in the loop at the boiler, even though all "fin-tube convector" valves we could get to only let water out.Doing research, I realized that what I was calling baseboards was an incorrect term. He checked all zones/equipment including the nozzle, and after getting the air out, said everything is working as it should, and the nozzle size is good for this system, though the one year it was different was not proper.
He then came upstairs and checked the thermostat. As soon as he saw it, he said that's part of the problem. Apparently, even though the Lux 9100uc TT said it could do boilers, it can't do radiant boilers.We now have a Honeywell T6 pro. Unfortunately, it's been warmer a couple days and expected to be a few days more, so it'll be awhile before I can get a good test of the system.
by InspectApedia Publisher - service tech confirms our early diagnosis
@Anonymous,
Thank you for taking time to update us and other readers on diagnosing this heating problem.
Back in January at my initial response I suggested the air-bound heating system problem.
This is a good reminder for us both of the difficulty of trying to diagnose technical issues remotely where all we have is text.
We're so glad that your system is working again.
I think a lesson for me here is to suggest, still ore emphatically, when it's time to get a trained, experienced technician on-site.
by Jim Hickey
@InspectApedia Publisher,
Well, as the service manager requested, I did not program the thermostat yet so that I could turn it up when I got up and pay attention to it. After the first time on in the morning, it's still doing 4 minutes on and 8 minutes off, but at least it reached setpoint faster.On the other hand, it's not very cold outside. I reached out to the service manager again and he said that's normal, that it's keeping the water at a good temp to heat the house.
by InspectApedia Publisher - air bound heating systems
@Jim H
Thanks for the update.
Indeed it's normal for a hydronic (forced hot water) heating system to cycle on and off and for the circulator to cycle as well, though a precise, exact to the second cycling interval is a bit unusual.
Keep in mind that even after air has been bled from a system (in this case they may have had to use a forceful method to do that), if there is an air leak into the system or a water leak out of it, the air blockage problem will return.
You should read
AIR-BOUND HEATING SYSTEMS
Our discussion may fit better on that page than on this one of optimum HI LO DIFF settings for aquastats.
Hi folks. Hope everyone's warm. I have a question an hope some details may help:
I have a nice cast iron OLSEN OSC-4 burning nat gas with the original TACO pushing through all iron rads via a single zone valve. 1500 ft of home, roughly, with decent insulation and windows, so sized right.
Off to the side of the OLSEN, there's a separate loop to an old AERO A-50 storage tank.
All from 1999 and still running strong.
The AERO tank is fitted with its own TACO circulator which runs the tank water through a single-walled sidecar exchanger nestled into the side of the ext tank skin - no internal loop in this AERO - and so the boiler TACO pushes one way, while the tank TACO pushes the other. Voila, hot water in the storage tank.
Priority for the full kit is DHW. Eg if the AERO still wants DHW heat, we get no space heating.
On the AERO are two Therm-O-Disc 59T stats that run back to a control module bolted to the OLSEN boiler. Installer labelled 59T#1 as "boiler" 59T#2 as "pump". I reckon this means #1 calls for the boiler to fire and circulate while #2 runs the other (dedicated) circ for the heat exchanger. All guesses but it kinda makes sense to me.
Assuming this to be mostly true, what should these be set at? Same preferred temp, near enough? One high, one low?
I get the sense that the boiler is running A LOT these days, being called by the tank trying to heat that tank water, and the boiler bumps up against its own high limit, then cycles again after it cools some.
I've tweaked the 59Ts in the past and suffered from a "lock out" of some kind, then re-tweaked one or both of them until the zone valve opens for the rads and all is good. No clue how I messed it up, no clue how I "fixed" it. Just me twiddling slotted dials.
Yet there must be more logic to it versus grabbing a screwdriver and turning the dials.
What's the best practice I should follow here in terms of setting up the twin 59Ts?
We live in the Golden Armpit/Toronto, with -10*C winters not uncommon.
We like ~130* water at the tap and this system delivers unless all the laundry, showers and kitchen are hauling hot water, then it wobbles for a half hour or so (but this doesn't concern me).
- Sidecar heat exchanger stripped and cleaned a few years ago, all good.
- Tank TACO replaced at the same time, all good.
- High Limit on the OLSEN is 180*:
- WATTS tank replaced a few years ago, working great, all good.
- System rests at 12-14 lb
- System runs at 22-26 lb
- T&P on the OLSEN is clean, no drips
- Flue gas analytics shows she still burns clean.
Any ideas on optimizing those two 59Ts or otherwise fine-tuning this rig?
Thanks and Happy New Year.
JC
Toronto, ON On 2023-01-05 by JCReply by InspectApedia Publisher - Boiler is running a lot with twin Thermo Disc 59Ts
@JC,
For a conventional aquastat like the Honeywell described above on this page, I'd use the optimal settings given above on this page - usually.
In Toronto the heating people often set up a boiler so that the circulator runs continuously and the thermostat (the one that calls for heat in the occupied space) will simply turn the boiler on when it wants heat.
The 2nd thermostat for your hot water will run the circ that runs boiler water through the coil to re-heat the indirect hot water tank.
Now about the Thermo-Disc-59T - that's normally used as an electric water heater hot water control - you can see its settings - factory- in the photo.
A Therm-O-Disc 59T 4300 66T 4401 Surface Mount Thermostat Limit 120 to 180 F, 120V like that shown below has its operation given in this nice summary
THERM-O-DISC-59T-66T-CONTROL [PDF]by Jim H - still have issues with boiler short cycling
Hi, follow-up to the conversation about our boiler running 4 minutes then off for 8 minutes repeatedly. I had an appointment for today but the tech called and asked what the problem was. He says that's the way the boiler is supposed to to work, to avoid overheating, but agrees it shouldn't take hours to come up to temp.
I was told the service manager was going to be coming but now he's not available. He's going to try to get in touch with the service manager and I'm not sure if anyone is still coming to day or not From what understand from this conversation, this is not the way t should work and until several years ago, it was fine.
It could come from 62-68 by the time I set the thermostat for, with the early recovery mode. Now it can't do 64-66 in less than a few hours. Suggestions, ideas?
by InspectApedia Publisher
@Jim
Sorry, but no, I've exhausted this topic. I've outlined every situation suggested by your earlier comments, questions, and discussion - thank you.
Do let us know what the service manager ultimately says - as that might help other readers....
by InspectApedia Publisher - why is boiler short cycling
@JC,
Keep in mind that a common issue with any heating or hot water control device that depends on contact with an exterior surface like that of a pipe or tank is that its behaviour can become erratic or flat wrong when any of several factors affect the quality of the contact between its sensor surface and the hot water pipe or tank surface:
For example, if nothing else has changed but your system isn't working as it used-to, I'd consider removing the two sensor controls and cleaning up everything, then re-installing them.by JC
@InspectApedia Publisher, cheers for your reply.
Nope, no continuous-run TACO circ on the boiler. Not set up that way. When nothing calls for heat, nothing runs: either full on or full off.
I think my Q is more about setting the twin 59Ts on the indirect AERO. If one of those calls on the boiler to circ + fire (main loop), while the other runs the heat exchanger circ (tank loop), should they be set at approx the SAME TEMP? Should the heat exchanger circ stir up the tank a little before the other stat calls the boiler?
** And thanks for the schematic and info on the 59T you attached. Mine are older than that, but the point's the same. What that info told me is these stats "sense the surface temperature of the water heater TANK..." eg not the water inside the tank, but the jug that holds it.Which may answer that part of my question as to the apparent short cycling: these stats are inside an ACCESS PANEL the cover of which was lost long ago. So they sit open. Makes it easy to adjust sure, but if they are sensing the TANK surface temp they're probably quickly cooling to the ambient air and fooling the boiler into firing more often.
Of course, the WATER in the tank is pretty hot and the stat is satisfied pretty quickly, ergo, short-cycling. **Does that make any sense to you? I'm gonna search for that access cover or jury-rig something to see if the behaviour changes meanwhile.
Thanks for your thoughts again.
JCby JC
@InspectApedia Publisher, I'll try the low-hanging fruit first and carve some pink foamboard to fit the access cavity in lieu of the lost cover, ... give the 59Ts a warm dark cave to sit in, un-exposed to drafts etc - see if that makes them happier ... cheers, JC
by InspectApedia Editor
@JC,
I appreciate the sense of trying to insulate near temperature sensitive control, but if this is a new problem and the installation hasn't changed and I don't think that that's the issue. Also I'm a little nervous about the fire safety of putting combustible foam insulation around and up close on an electrical device.by JC
@InspectApedia Editor , understood, yet the stats were surrounded by yellow batt, then a steel cover (until i foolishly lost that cover... ) so someone thought these could be enclosed by design i guess... we're not talking mains voltage or any kind of current here, 24V off the transformer ... and beyond losing that cover, nothing else has changed no, just that it seems to be short cycling;
i didn't even think that these were a kind of hard surface stat and not immersed in some fashion - never crossed my mind ...
On 2023-01-06 by InspectApedia Publisher
@JC,
There is both line voltage (120VAC) and also lower voltage inside the aquastat.by JC
@InspectApedia Publisher, thanks but this is all 24Volt running through the 59Ts on 18 ga. wire, stepped down by transformers bolted near the boiler motherboard. (Ignore the AERO rating plate in the picture).
When the stats close across TV-T the mains throw for pumps & the blower happens back in the relay box (R8222C).On 2023-01-06 by InspectApedia Publisher - why a temperature sensor on a hot water tank would turn on a circulator is clear
@JC,
Thank you for the added detail. It's another example of the difficulty we face in trying to be helpful in discussing heating controls when we have so little information about an actual installation. Even now I don't have a complete, clear picture of your installation.
The phrase
When the stats close across TV-T the mains throw for pumps & the blower happens back in the relay box (R8222C).
leaves me uncertain about what components make up your system and what is being controlled. Why a temperature sensor on a hot water tank would turn on a circulator is clear: to re-heat water in an indirect-fired domestic hot water tank, by turning on a circulator pump that circulates heating boiler through a coil that in turn heats hot water in the hot water tank.But what "blower" is where and what you mean by "blower happens" and what "relay box" we're discussing is, apologies, unclear. Maybe a sketch of the system and its components would help.
@InspectApedia Publisher,
Yes, I am in the US.
What we're trying to figure out is why the boiler comes on for 4 minutes, reaches it's HI limit and goes off for 8 minutes, repeatedly until the room is at set temp which is often many hours.
I have observed that the 8 minutes is all it takes for the boiler temp to cool off 10-11 degrees to get below the Hi temp differential so it can come back on. The circulator pumps seem to be working.
We've also just discovered there may be an issue with the thermostat at well. On 2023-01-15 by Anonymous -
Reply by InspectApedia Publisher
@Anonymous,
Yes we understand that that's the question; we've suggested several things to check, including both settings (which you are confident are correct) and over-firing - something that your heating tech can examine.
It may also be diagnostic to consider when this boiler on-4 off-8 minute cycle first occurred. Since new installation, since work was done on the boiler, or since something else changed?
If you're in the U.S. and your heat is controlled as typical,
The articles in this series explain how the aquastat turns the boiler on or off in response to temperature:
The thermostat, on a call for heat, turns on the circulator for that zone.
The aquastat, in response to the temperature in the boiler, will turn on the burner when needed.Keep in mind that I'm quite limited in what I can see of your system from here .
Seems as if the next thing to do is ask your tech to check the firing rate - the nozzle size in gph.On 2023-01-17 by Anonymous - how do I find out the right firing rate for my boiler?
@InspectApedia Publisher,
I assume the firing rate isn't something they can tell me via email or phone and it's at the point where we have no option but to set up at service call? They charge $149/hour and I don't understand why it's not covered by my "gold contract". I believe it had been in the past.I believe I've read all articles suggested. We know it has been taking hours to come up to set temp for years now. I t may have coincided with changing the thermostat or it may coincide with having the aquastat replaced. We're not sure.
Reply by InspectApedia Publisher
@Anonymous,
No it means that the technician has, if you are correct in the number you give is actually the nozzle that's actually installed, downfired the boiler which would be in response too and overfired boiler in the 1st place. Now it's time too get actual data on what's actually installed.
Ask your tech to check the firing rate - the nozzle size in gph Of the nozzle that is actually on the burner.
And then ask the technician to investigate what you have described as a too short and too frequent burner on cycle.
Please report back to us what you are told when you have done that.
You need a heating service call at your home, by an experienced service technician.
Do let us know what you're told - what she or he finds - as that will help other readers who've slogged through this problem.On 2023-01-17 by Anonymous - boiler firing range on burner label?
@InspectApedia Publisher
I went down and found that label. The way I understand the info online, since the label does not show a "firing range" but does show 2 nozzle sizes, does that mean the year a 60-80A was installed, it was not a correct one for this burner?On 2023-01-17 by InspectApedia Publisher - Oil burner nozzle spray patterns and delivery rate
@Anonymous,
Please use our on page search Box and search for the phrase
Oil burner nozzle
And you will see we have articles explaining about spray patterns and angles and delivery rate in gallons per hour. That will be more accurate and thorough than if I try to make that up de novo here off the cuff.The firing rate given on the data tag in hyour photo is 0.85 along with the nozzle type and pattern, but that tells us what the oil burner manufacturer or boiler manufacturer recommended, NOT necessarily what nozzle a service technician has installed.
On 2023-01-16 by Anonymous
@InspectApedia Publisher,
I was just looking back at the service records I got from my provider and it looks like they've always used a 75-80B nozzle (no brand listed) but one year they used a 60-80A Delavan.
I'm trying to decipher the info here about nozzles. Are these 2 nozzles interchangeable or if not, which is the proper size? The boiler is a Beckett RSA85LN-TB. It appears the oil filter has always be #3.On 2023-01-16 by InspectApedia Publisher - checking the firing rate of the oil burner
@Anonymous,
About the changing the delay back to 5 - making no difference, that's a helpful diagnostic step. So we're back to checking the firing rate of the oil burner.On 2023-01-16 by Anonymous - TX9100uc heater settings on our L7224& Aquastat
@InspectApedia Publisher,
I also apologize for how frustrating it must be for you to work with someone who knows nothing about these systems.
When you mentioned the dipswitches, I realized that I typo'd when mentioning which model I have, which is actually the TX9100uc https://www.luxproducts.com/wp-content/uploads/2017/07/tx9100uc_manual_en.pdfThis model has all the settings accessed through programming, and my settings include:
Early recovery: on
System mode: furn
Fan: gas (what directions say for a boiler)
Delay time: 2. default is 5 but I was trying to force it to run more often to get it up to temperature.
Temperature swing is set at 1 (range 1-9 with 1 being smallest) Trying to force t to keep temp once it got it.
Offset: 0 because a boiler doesn't have second stage heat. (default 2, range 1-9)
As far as the backlight apparently sending a signal to the boiler, the manual says: The display screen is lighted to assist viewing at nighttime, or in locations with low light levels. A press of any button on the front panel will light the display for approximately 10 seconds.
The L7224U aquastat settings:
HL_ is set at 190 (was 180)
Hdf is set at 10
LL_ is off
duu is off
ASC is set at 0 sec
tPL is off
PC- is on
Do all these settings look good to you?
Last night I changed the delay back to 5 as suggested, and this morning I see it makes no difference. The boiler is still doing the 4on/8off sequence.On 2023-01-16 by InspectApedia Publisher
@Anonymous,
About your thermostat
Delay time: 2. default is 5 but I was trying to force it to run more often to get it up to temperature.
Try setting that back to 5 and see what happens.On 2023-01-16 by Anon
@InspectApedia Publisher,
Ok, I've changed that setting already. Thank you again. Heat is already set lower for the night, so I will check back tomorrow.
I do wonder if the thermostat is malfunctioning somehow as well as whatever the other issue is, since the instructions say to hit any button to turn on the backlight. Earlier when the set temp and room temp were the same, it clicked and flashed the set temp 3 times then "heat" 3 times then the boiler came on.
However, after being near the thermostat checking settings, and the detected temp raising above set because I was near, I tried again out of curiosity to see if that would happen again and it didn't.
I'll experiment with that again tomorrow as well, but I doubt it's a coincidence.Trouble with LUX 9100U thermostat control signals to burner
@InspectApedia Publisher,
This conversation actually started on Jan 4. When it was moved to here to aquastat, I started a new comment/question.We're now wondering why the Lux 9100u thermostat sends and electrical signal to the burner when I'm only touching a button once to turn the backlight on.
It takes 2 pushes to change anything. On 2023-01-15 by Anonymous -
Reply by InspectApedia Publisher -Temperature swing vs burner cycles per hour
@Anonymous,
You probably have the LUX9100U THERMOSTAT MANUAL [PDF] Lux Products, originaL source: https://www.luxproducts.com/wp-content/uploads/2017/07/tx9100u_manual_en.pdf.
I don't see any discussion from Lux that approaches your question of when the TT is signaling the boiler. For sure, you'd think that just touching to wake up a display ought not "do" anything else.
BTW there are some dip switch setting recommendations in the manual that you might compare with those on your thermostat.
Do take a look at their discussion of the Swing Setting starting on p. 23:TEMPERATURE SWING AND OFFSET SETTING: A thermostat works by turning your heating or cooling system on and off whenever the room temperature varies from the desired set-point temperature.
The amount of this variation is called the swing. Generally your system should cycle on about 3 to 6 times per hour. A smaller swing number makes the system cycle more frequently, so the room temperature is more precise and constant.
A larger swing number will make the system remain on for a longer duration each time and decreases the number of cycles per hour. There is only one Swing setting, and this determines the cut-in and cut-out points for both the first and second stages (if present), in both Heat mode and Cool mode.
Causes for Hydronic (hot water) heating boiler rapid on-off cycling of the burner
OK. So if the circulators are on the return side of the loop, and the pipe coming into the circulator is hot not just right at the circulator but several feet away from the boiler then hot water is circulating through the system.
When a heating boiler is cycling on and off to frequently but we are certain that hot water is running properly through the piping and radiating devices, then there are other things to check including
CIRCULATOR PUMP RUNS INTERMITTENTLY
- be sure to step through the diagnostic suggestions in this article as some of them could explain what you are experiencing.
AQUASTAT HI LO DIFF SETTINGS - above on this page
AQUASTAT SENSOR PROBE HEAT CONDUCTING COMPOUND
Watch the boiler temperature and pressure gauge when the boiler runs.
If its aquastat and aquastat sensor are working normally, when the boiler turns OFF the water temperature will be close to the HI setting on the aquastat and when the boiler turns back on, depending on the aquastat model, the water temperature will be 10-15 degrees below the HI.
You didn't give the fuel for this boiler. If it's heating oil and if the boiler is over-fired (oil burner nozzle size in gph or oil pressure too high) that could also cause the boiler to "get ahead" of the building's heating piping: water in the boiler heats up very rapidly and then is exhausted quickly by the circulator.
Let me know what you find. On 2023-01-15 by InspectApedia Publisher -
On 2023-01-06 by Anonymous
Thank you, I appreciate the help. I know how busy you must be and you still find time to help on this board
Is it odd that the lower limit on the aquastat was turned completely off? The boiler temp was at 70 when we looked at it this morning and when it first came on awhile later for the day setting, it had to come up 110 degrees before it turned off at the high limit of 180. It took maybe 15-20 minutes.
It was only at Christmastime this year during sub-zero temps when factoring in wind chill (very unusual here) and the heat didn’t come up even 2 degrees after literally all day, that I started timing it and saw it runs 4 minutes and off 8 before coming back on again for only 4. This morning was the first time I noticed it was on much longer when first on in the morning.
On 2023-01-06 by InspectApedia Publisher
@Anonymous,
The low limit on the aquastat should be off as you don't have a tankless coil for your hot water.
About the temp not coming up quickly - that sure looks as if either a circulator isn't running OR a heating line is air bound.
PLEASE READ AIR-BOUND HEATING SYSTEMS - home
as that will be more complete than having me try to re-create all of that guidance here, off-the cuff. Let me know if anything you read seems unclear.
On 2023-01-05 by Anon
Does the transformer look normal to you?
Any thoughts on why the gauge at about 172 doesn't agree with the aquastat at 180 or how to fix that?
It looks like the other settings I tried posting didn't actually post. Do these look right?
HL_ is set at 180
Hdf is set at 10
LL_ is off
duu is off
ASC is set at 0 sec
tPL is off
PC- is on
According to the manual, there should be more settings but this is all it shows me when cycling through.
As far as the Lux 9100uc thermostat, I have the temperature setting at 64 for night and 66 for day. I used to let it go lower at night but for years now I don't set it higher when I'm the only one home (and use a small electric heater) because oil costs so much, the last couple years, especially this year.
I believe these problems started when we replaced the old thermostat because it stopped holding it's programming, or it just occurred to me that it may coincide with the aquastat being replaced.
There are other settings I've tried changing to try to make the boiler keep heat at set temp or even reach it, but they don't seem to make a difference and it still takes hours to come up even one degree. It was only this year that I started timing it and see it runs 4 minutes and off 8 before coming back on again for only 4.
This morning was the first time I noticed it on much longer when first on in the morning which seem to me to coincide with your idea that the high and low settings may be off.
Delay time is set at 2 with default being 5.
Temperature swing is set at 1 (range 1-9 with 1 being smallest)
Offset is a 0 because a boiler doesn't have second stage heat.(default 2, range 1-9)
I also realize that a high pitched noise when the boiler first came on is gone. I'm not sure if that's good or bad, but I believe it was there least year as well, maybe longer.
On 2023-01-05 by InspectApedia Editor
@Anon,
Those are reasonable settings
Does anyone know why an oil-fired boiler baseboard heat system would only run for 4 minutes then go off for 8 minutes, then back on for only 4 minutes, repeatedly, even when set temperature on the digital thermostat has not been reached? On 2023-01-04 by Anon -
Reply by InspectApedia Publisher - oil-fired boiler baseboard heat system cycling
@Anon,
There are a couple of causes of heater cycling:
1. the boiler is getting up to its shut-off temperature in just 4 minutes - which might mean that a circulator isn't pushing hot water around the heating zones very fast or not at all
2. there could be another user of boiler heat such as hot water being produced by a tankless coil
I just bought a home with a 20 year old Thermo Dynamics Boiler. Former homeowner said he had a technician change the Aquastat in July.
Tried to heat the home and failed today. It is a problem with the Aquastat he installed just three months ago.
For some reason when the temp differential is set to 20 degrees High above low the system doesn't function.
It shuts itself off. The tech manually adjusted the differential so the High is 180 and the low is 200 and the house heats up now.
What is the issue with the Aquastat? Theoretically this means they're crossed, and the system shouldn't function. On 2022-10-04 by Clare Martinez -
Reply by InspectApedia-911 (mod) - Your aquastat controls are "crossed" incorrectly so it won't heat your home: the fix is easy
@Clare Martinez,
You are absolutely correct that the aqua stat is not set properly. The way that it's set the circulator will never turn on. The high must always be at least 20° higher than the low. Set your high to 180 or 200 and the low at least 20° below that point.
A reasonable starting place would be to set the high to 180 and the low to 155.Now with the aquastat set correctly, set your thermostat well above room temperature to be sure that it's calling for heat.
The circulator should come on and you should feel the water and the pipes returning to the boiler get hot.Let me know how that works and if you still don't have heat we will continue from that point.
Good afternoon, I have Burnham Series 2A with 2 zones circulating pumps, 1 zone for the main house and one zone for one of the bedroom.
The main heat work fine, the bedroom I replaced the circulating pump and the thermostat but the circulating pump wont run.
I tested the pump by connecting it to 120V and it worked fine.
Replaced the old Taco Circulating pump007_F4 with a new model F5
I think my aquastat settings must be wrong. On 2022-01-17 by Sam
Reply by Inspectapedia Com Moderator - No: aquastat settings will affect ALL of your heating zones
@Sam,
If you are absolutely certain that the circulator pump does not run when installed then also ran normally when connected by itself directly to power, there's either a wiring error or a bad control relay.
Watch out: These circulators are so quiet that they can be running without you realizing it.
So the problem could be in air bound heating system zone, OR the circulator isn't running because the HI LO and DIFF settings on your aquastat are incorrect. Start with HI =200, LO=175, DIFF=25.BUT IF the problem were in the aquastat settings, then ALL of the heating zones would be affected, not just some of them
Please take a look at the article AQUASTAT HI LO DIFF SETTINGS as it is a more complete answer to your exact question.
My HI is set to 180 and my house isn’t heating up to what the thermostat is set for, the heat stays below 60° if I set it to 200 it’s better but still has a hard time reaching what the thermostat is set for? On 2022-01-08 by Jeff f -
Reply by Inspectapedia Com Moderator
@Jeff f,
1. Check your Aquastat settings as advised in the article AQUASTAT HI LO DIFF SETTINGS particularly, if you set the LO too close to the HI then the circulator can stay locked out and you won't get heat; the LO must be at least 20 deg F below the HI.
2. If the Aquastat settings are correct and the circulator then runs on a call for heat, your system may be air-bound.
In that case see AIR-BOUND HEATING SYSTEMS - home
About LO setting on cast-iron boilers.
I read that LO setting is set to let cast-iron boiler heat up without running circulator, in order to prevent a lot of condensation and rust. So LO setting lets boiler heat up first and only then to turn on the circulator. On 2021-09-20 by Aydar -
Reply by inspectapedia.com.moderator - keeping some heat in cast iron boiler even when not heating the building can avoid condensation
@Aydar,
You are correct that for cast iron boilers keeping some heat in the boiler even in summer time when you're not heating the building can avoid condensation and also leaks associated with Cooling and move the can and some boilers cause leaks at the push nipples between sections.Elsewhere we recommended keeping some heat in the boiler for those systems.
However that was never the technical or main purpose of the LO control, it's simply a side benefit for those particular heating boilers prone to leakage between sections.
My aquastat has one dial with two pointers on it. Also, it is not accurate, but be that as it may, I would never never never want the high limit set to 180 degrees! It was recently set to 140 by a service man, and the hot water will severely scald you.
I believe that if you can keep the water at the kitchen sink faucet around 125 to 130 it is more than hot enough. On 2020-12-21 by Doug McGarrett
Reply by danjoefriedman (mod)
It sounds to me as if your aquastat is not correctly set. But for heating efficiency (lower heating and hot water cost) a good design is to keep the boiler hot but use an anti-scald device to avoid unsafe temperatures at the building's plumbing fixtures.
Be sure to review the different purposes of the high limit and low limit and differential settings as explained in this article so that you understand what each of them does.
Then see our anti-scald burn safety advice
Setting a high limit at 180 or above is wasteful. I set my high limit at 160. The lower boiler temp is unnoticeable in the home heating. Actually my oil bill dropped 25%. Low limit is always 20 degrees less than high limit. The furnace does not come on all the time as before.
My circulators stay on longer to move heat to baseboard pipes. The heat is very even in the house now. No pinging pipes. A water circulator is low power and costs 90% less to run than the boiler. I am completely happy and promote this to everyone I meet On 2020-11-13 by Jim McMahon -
Reply - by (mod) - Wrong, but several variables determine how efficiently we burn heating oil and thus heating cost
Thank you for your comment, Jim.
I agree that there are a number of variables that determine how efficiently we burn heating oil and therefore what our heating cost is. The greatest Improvement in most buildings is from stopping air leaks.
Watch out: However there's no getting around science which tells us that the thermal conductivity of water and thinned copper baseboards is exponentially greater at higher temperatures.That means we got a more efficient heat transfer out of the boiler system and into the occupied space when the Border Water is hotter. That doesn't speak to the heat loss rate for the building at all.
Aye, that I read recently really stuck with me. Science tells us truth whether we choose to believe it or not.
If I set the Hi at 180 and the Lo at 160 what should I set the Diff. at. I only use the boiler for heat. What could be causing the boiler to short cycle every now and then? On 2020-03-25 by david
Reply by (mod) -
David
Probably the way your aquastat is wired it thinks you've got a tankless coil in use for domestic hot water, so it keeps the boiler hot even when there's no call for heat.
See AQUASTAT LO & DIFF DISABLED
for some suggestions
I bought a house with a Benjamin wood and oil combo boiler and cannot seem to heat it very well with just wood, does anyone know what the settings are for the triple aquastat and for the single aquastat - On 2020-01-22 by Adam
Reply by (mod) - settings for the triple aquastat and for the single aquastat
I don't, Adam, but you can give the company a call
Benjamin Heating Products
166 Junction Road, PO Box 2079
Springhill, Nova Scotia, Canada B0M 1X0
Tel: 1-800-565-5495 · Fax: (902) 597-3797
furnaces@eastlink.ca
and perhaps the company can give you a manual;or see these product specs
FS 140 COMBINATION OIL/WOOD HOT AIR FURNACE [PDF] retrieved 2020/11/22 original source: http://benjaminheating.com/files/8113/1550/1314/FS_140-Eng.pdf
I just put a new temperature gauge on front of my boiler and for an Aquastat setting of 180 for high the gauge temp goes up to 220 .
I set the aquastat to 160 low and high temp reaches 200 . So it's about 40 degrees off . The aquastat is a Honeywell L8124C and probably about 15 to 20 years old . Can i run it like this with the lower setting as long as it doesn't change ?
Where the Aquastat gets it's reading is from a tankless coil area that I don't use because i figured it was burst or broken inside when i moved in. So i set my differential to 10 down from 15 since i have a broken coil that I'm not using and trying to save heating fuel and money here in Maine where it's a long winter usually .
Going to check the temp reading when boiler comes back on,set to 140 low to still give it 20 degree diff from the high even though the high temp is way off maybe due to hard water buildup or something on the sensor on the aquastat .What might be a better Aquastat if I ever change the one I have ? On 2019-12-17 by Tim Clark
Reply by (mod) - dangerous condition needs prompt repair
Tim:
Watch out: this is a dangerous condition. If the boiler temperature is actually over 200F then on a normal residential heating boiler the temperature and pressure relief valve should open and spill.So if that is NOT happening either the temperature isn't really 220 (the gauge is inaccurate) OR the TPR valve is unsafe and risks a dangerous, even fatal boiler explosion.
I would turn the boiler OFF for safety.
For these reasons you want to satisfy yourself that you know what's going on - the solution is NOT in the Aquastat itself it first is in measuring boiler temperature and in inspecting, testing, and if necessary replacing the temperature-pressure-relief valve (TPR valve).
Once those critical life-safety issues are resolved we can worry about
- temperature/pressure gauge accuracy (search InspectApedia.com for these phrases to read details)
- proper aquastat settings (article on this page)
- proper aquastat installation including of its temperature sensor that is inserted into a well on the boiler (maybe you're missing temperature-conductive grease)
Great site! I aImost understand many of your aquastat articles.
I maintain a property that has an oil fired boiler that supplies both heat, via old school radiators and domestic hot water.
The place is seldom occupied.
I know that I can reduce thermostat settings to minimize heating expense, but I also notice a lot of fuel is being used to heat domestic hot water unnecessarily.
How do I reduce or eliminate the heating of domestic water, unless I want it?
Thank you for your help. On 2019-11-24 by Ed -
Reply by (mod) - If the domestic hot water is being produced by an indirect water heater
Ed
If the domestic hot water is being produced by an indirect water heater that's being heated by your boiler then there will be a separate aquastat control mounted on that hot water tank.
If the hot water for your building is being produced by a tankless coil then the aquastat on your boiler controls that setting. However for a tankless coil case, if no one is drawing hot water, the only thing you need to do would be to set the low limit down to its lowest number.
Does this same rule of thumb apply with a steam boiler, with a high/low limit aquatast, with a 5-30 degree differential?. when the heating cycles just reaches its end(the point where the water is the hottest) the temp out of the mixing valve is maxed at 140, for a short period of time. so for aquastat i’m thinking somewhere around 180 for high limit and 15 on the differential? On 2019-03-23 by Dwain Mcmillion -
Reply by (mod) -
In my opinion yes
For other readers, a steam boiler may also use a tankless coil that's of course below the steam boiler water line.
Since it's making steam you can figure that the boiler temperature must be reaching 212 degF (at sea level).
So I'm confused here. In this article on this other webpage on this site, https://inspectapedia.com/heat/Aquastats.php, it says that, when there's no call for heat, a furnace always will turn on at 10 degrees below the LO set point and turn off when the temp reaches the low point plus the differential MINUS 10 DEREES.
In other words, the differential is added to the temperature at which the furnace turns on (10 degrees below the LO set point), not to the LO set point, as it seems to suggest above.
So above it says: If the LO is 120 and the differential is 10, the furnace will shutoff at 130. But according to the other article, if I understand it correctly, if the LO is 20 and the differential is 10, the shutoff is 120. In other words, a 10 degree differential always shuts off a furnace at the LO set point and a max 25 differential always shuts off the furnace at the LO set point plus 15 degrees, not 25.
The second explanation seems to be supported by the website https://forum.heatinghelp.com/discussion/82927/aquastat-settings
But that third webpage raises another point of confusion. It says the circulator is allowed to run at 10 degrees below the LO set point (the furnace-on point). Both articles on this site suggest that the circulator is not allowed to turn on until the LO level plus differential is reached, (differential -10 for the other page).
Can anyone clarify? What is right? Or am I just reading all this incorrectly - I'm not that smart :O)
Many thanks Anthony Giorgianni On 2019-01-12 by Anthony -
Reply by (mod) -
Thanks for asking Anthony, I'll review the two articles and the details to be sure we express these temperatures and limits clearly.
What can be confusing is failing to note that we're talking about the Differential OR DIFF control - on a call for heat, the DIFF control will lock out the circulator at low temperatures.
IF an aquastat is wired and set up to keep the boiler hot for making domestic hot water using a tankless coil, THEN the DIFF and LO become important as they keep heat in the boiler for that purpose, and also because the aquastat will prevent the heating zone circulator from running to deliver hot water to radiators or baseboards while you're in the shower consuming domestic hot water.
Clarifying further, the "130" degrees to which you refer is mentioned in our explanation of the DIFF control and what that does.
Quoting:
Our photo shows the DIFF adjustment on a Honeywell aquastat. This DIFF is set to its lowest value: 10 °F.
At the setting shown, if LO were set to 120, when the burner is re-heating the boiler water and water temperature rises to 130 F the burner will turn off and the heating circulator pumps will be allowed to turn on (and they will actually turn on if the room thermostat is calling for heat).
My boiler aquastat is raised to 160 Hi and 140 LO because part of my second floor is not getting heat but I have not seen any improvement.
While the front half of the house radiators are hot the back part especially the second floor there is no heat. What could be the problem with the hot water circulation?
Thank you for a response On 2018-10-18 by Randy -
Answer by (mod) - when some zones heat and others don't the problem is not the aquastat
If one of your zones is getting no heat at all then the problem is not the settings on the aquastat on the primary controller.
That's simply controls the temperature operating range of the boiler.
More likely you have a zone Valve or circulator pump that is not working, or you might have an air bound heating Zone. If you can confirm that the zone is calling for Heat and the circulator is running and search this website for
air bound heating system
to see the diagnosis and repair needed.
12/30/2014 Ryan said:
Great site and info. I noticed that my aquastat and my boiler temp gauge are a good 20 degrees different.
My Aquastat's HI might be set to 180 but the boilder temp gauge reads 200 before it shuts off then pending no heat is being called, it might heatsoak all the way to 220. I turned the acquastat HI down to 160 and that seems to make the boiler shut off at 185 and max heat soak i've seen was 205 in this configuration. Do I need a new aquastat or does my compensation method work?
Also, is it worth re-greasing the probe well to ensure the aquastat is in good contact with the probe well wall? Any other suggestions?
Another quick question... My boiler has a tankless water heater coil to provide hot water. Recently I had a tech install a 50gal storage tank. The storage tank has no wires going into the the aquastat of the boiler - the storage tank has it's own aquastat that turns a zone circulator on/off. The zone circulator is connected to the in/out of the boiler hot water coil.
Do I still need to set my LOW and DIFF on my boiler aquastat (and if so, can you recommend a setting)? What does the storage tank aquastat do in this set-up and how should I set that in conjuction with the boiler LOW/DIFF settings?
Currently my hot water measures a max of 155 - 160 degrees coming out of a faucet on full blast hot. Looking for some advice on settings that could save me some $$ in oil yet have little impact on current performance (I.E currently 2 simultaneous 10min showers without issue and plenty of hot left over)
Reply:
Ryan,
While aquastats and boiler pressure/temperasture gauges are not lab-grade highly-precise instruments, a 20 degree difference may say something is wrong - or might be normal. It depends. Certainly the HI or upper limit setting, say set to 180F should result in a boiler gauge temperature reading close to 180F when the boiler SHUTS OFF at the end of a heat-on cycle.
But not always. For example if the burner is firing but the thermostat call for heat is satisfied (the thermostat then turns "OFF", at that point the boiler will stop firing even though it has not reached the cut-off temperature.
But your boiler gauge readings of 20-40 degF above the HI setting suggests something's wrong. It could be a faulty temperature sensor, poor contact between the temperature sensor in its well and the sides of the insertion well (use heat-conductive grease provided by the manufacturer) or a faulty control.
It's possible the trouble is your boiler's gauge - it might be sticking. Because typically if the boiler were truly reaching abnormally high temps, over 200F, the pressure/temperature relief valve should be spilling. I might try installing a new gauge first.
For details on how to set the HI LO DIFF optimally, in ARTICLE INDEX see the article titled AQUASTAT OPTIMAL LO/DIFF SETTING - and let me know if questions remain.
12/30/2014 Ryan said:
Thanks Joe. At the moment, the aquastat is set to 150HIGH and 120 LOW which is resulting in consistent boiler temps of 180 - 185 HIGH (even when heat soak comes into factor) and 150 - 160 LOW.
I don't notice the boiler temp gauge sticking, it swings very fluidly but I'll read into what it takes to replace the boiler gauge. Since the aquastat is consistently reading LOWER temps then the boiler gauge, I'm guessing (hoping) based on your response the aquastat is not touching the inside of the probe well. I'll take a look and re-insert grease where needed.
On the other subject I posted about: Boiler coil connected to storage tank; Do you have any thoughts there?
" Another quick question... My boiler has a tankless water heater coil to provide hot water.Recently I had a tech install a 50gal storage tank. The storage tank has no wires going into the the aquastat of the boiler - the storage tank has it's own aquastat that turns a zone circulator on/off. The zone circulator is connected to the in/out of the boiler hot water coil.
Do I still need to set my LOW and DIFF on my boiler aquastat (and if so, can you recommend a setting)? What does the storage tank aquastat do in this set-up and how should I set that in conjuction with the boiler LOW/DIFF settings?
Currently my hot water measures a max of 155 - 160 degrees coming out of a faucet on full blast hot. Looking for some advice on settings that could save me some $$ in oil yet have little impact on current performance (I.E currently 2 simultaneous 10min showers without issue and plenty of hot left over) "
Reply:
Ryan if the gauge seems OK I suspect that the temp sensor on the aquastat is defective or it is not in good thermal contact in the sensor well. Some heating service techs deliberately skipped the manufacturers' instructions to use a thermal grease when installing the sensor, complaining that the grease gets stiff and makes later control replacement difficult.
But I believe that the manufacturer knows what's most important in successful installation of their product.
Further, the current thermal grease has been improved and doesn't create a stuck-sensor issue any longer.
Ryan if you are using an indirect fired water heater with its own heating zone and controls, you can abandon the tankless coil and disable the appropriate parts of the aquastat - see
AQUASTAT LO & DIFF DISABLED
OR there are other options for using both the indirect water heater AND the tankless coil. For your set-up I don't recommend this, but one can pipe the tankless coil after the outlet from the indirect water heater so that the coil only comes into play as a booster unit if the first heater has run out of hot water.
I wouldn't do it.
A decent indirect fired water heater is efficient, a good use of the boiler as heat source, and most likely the added support of the tankless coil is not needed.
...
...
Continue reading at AQUASTAT HI LO DIFF SETTINGS - topic home, or select a topic from the closely-related articles below, or see the complete ARTICLE INDEX.
Or see these
AQUASTAT HI LO DIFF SETTINGS FAQs-4 at InspectApedia.com - online encyclopedia of building & environmental inspection, testing, diagnosis, repair, & problem prevention advice.
Or see this
Or use the SEARCH BOX found below to Ask a Question or Search InspectApedia
Questions & answers or comments about the best settings for aquastat controls on heating boilers
Try the search box just below, or if you prefer, post a question or comment in the Comments box below and we will respond promptly.
Search the InspectApedia website
Note: appearance of your Comment below may be delayed: if your comment contains an image, photograph, web link, or text that looks to the software as if it might be a web link, your posting will appear after it has been approved by a moderator. Apologies for the delay.
Only one image can be added per comment but you can post as many comments, and therefore images, as you like.
You will not receive a notification when a response to your question has been posted.
Please bookmark this page to make it easy for you to check back for our response.
IF above you see "Comment Form is loading comments..." then COMMENT BOX - countable.ca / bawkbox.com IS NOT WORKING.
In any case you are welcome to send an email directly to us at InspectApedia.com at editor@inspectApedia.com
We'll reply to you directly. Please help us help you by noting, in your email, the URL of the InspectApedia page where you wanted to comment.
In addition to any citations in the article above, a full list is available on request.