Aquastat High, Low, & DIFF FAQs
FAQs on best settings for a heating boiler aquastat control:
These articles explain how to choose the best settings for a heating boiler aquastat - the combination control that sets boiler temperature and may also control hot water production via a tankless coil on the heating boiler.
InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers, products, or services discussed at this website.
- Daniel Friedman, Publisher/Editor/Author - See WHO ARE WE?
At AQUASTAT CONTROLS and in the more detailed article AQUASTAT HI LO DIFF SETTINGS where most of these questions and answers were first posted, we explain how aquastats work, defining the functions and dials of the aquastat HI LO and DIFF control along with the reset button often found on these heating boiler controls.
The photo at page top shows a the "HIGH" or "HI" setting on a Honeywell R8124A combination heating control, also called an "aquastat".
Also see our index to all aquastat control setting questions and answers at AQUASTAT HI LO DIFF SETTINGS FAQs
Also see our index to all boiler aquastat questions and answers at AQUASTAT DIAGNOSTIC FAQs INDEX
...
I have a oil hot water with radiator system It has the tankless hot water but I do not use it now If I have a power outage
I Have the furnace hooked up to run off a generator so I would then switch to the tankless water heat.
My question is what should the High/Low on the aquastat Honeywell LB124A,C LB151A be set.
My issue is that some radiators that are the farthest from the boiler do not get as hot as the others.
I have purged all air from the system.
The radiators closest to the boiler provide excellent heat - On 2016-12-11 by Choke51
On 2016-12-13 by (mod) - what should the High/Low on the aquastat Honeywell LB124A,C LB151A be set.
HI 180-200
LO 140-160
Running as hot as you can helps the distant radiators, as would insulating water heating lines.Watch out: But running too hot - over 200, is unsafe.
...
The high cut off on my aquastat is set to 140. when the thermostat is calling for heat. the boiler goes up to 180 before cutting off. the longer it runs the higher the cut off will run. my diff is set at 10. can you help me please/ thank you
Reply:
Bill it sounds as if maybe your Aquastat controls are crossed or not set properly.
If the HI were set to 140 that ought to be the upper limit, right
Check the LO setting. Is it above the HI?
If not the control may be not connected properly or has a wiring error or the temperature probe is improperly installed or finally, the control itself could be defective.
More detailed help is at these two pages
- AQUASTAT SENSOR PROBE HEAT CONDUCTING COMPOUND - can result in mis-reading temperature
- AQUASTAT TROUBLESHOOTING - all types of trouble
I think with the inaccuracies of the temperature sensing equipment, after setting 200hi, 180 low diff 25 (domestic max temp 195) one should monitor the boiler to make sure these temps are reached.
5degs is small buffer if there is inaccurate guage. On my setup i just noticed our "anti-scald" valve says (right on it!) "not anti-scald"
Just some random screw based temperature mixing valve. Very hard to know what temp it's set to. Just do it by feel... 120-160 range. Set roughly middle. Would a real one make for more stable temperatures?
Thank you, i learned a lot. On 2016-07-12 7 by Alex
Reply by (mod) - heating boiler gauge temperature reading accuracy
I agree, Alex, except I might add that monitoring the boiler temperature by its own gauge doesn't reassure me entirely: the gauge is also not precise lab-grade instrumentation. If you set the gap between HI and LO to a bit more than the 20 degF minimum then you can help assure there is no inadvertent lock-out of the boiler.
Lower temperatures waste fuel and thus are inefficient.
The high low limit device on my Weil Mclain natural gas boiler failed. Temp went well over 200F. This set the boiler relief valve off.
I replaced the high/low device and the well the copper sensor end fits in. There was no scale on the old well or the sensor end of the high/low that was replaced. There was just a black film coating, which was easily wiped off.
This new high/low device seems to work but it is not accurate. In order to get the boiler to shut off at 180F the setting on the high/low must be set to 160F.
In Aug 2013 TP valve activation was a real problem which led to new TP, Expan tank, auto water feeder valve, back flow valve and as mentioned at RELIEF VALVE LEAKS the last item the high/low limit replaced Oct 2013.
All was from OCT 2013 till Aug 13 2014 and then the TP was activated for reasons unknown other than the pressure gauge read 30lbs which is the trigger point for the TP. Expan tank checked out at 12 PSI. I do have a street fill valve and this valve was closed since OCT 2013 and boiler pressure was checked every month or so and was a constant 14/17 PSI.
There is a Bock indirect water heater that I thought could have a coil pin hole that opens when it has a mind to, allowing potable street water into the boiler through the coil. System is up a running now for the last several days and the pressure is at a steady 17psi. Hot or cold the pressure is always the same 17psi. I have verified the pressure with a separate 0-30psi gauge.
So do you have any thoughts on the matter that can I apply. Thanks
Boch indirect and boiler 19 yrs old 8/17/14 Donald Fletcher
Reply:
For temperature sensing errors on typical modern aquastats and limit switches:
Do you think the problem could relate to poor thermal contact between the Aquastat's sensor probe and the surface of the well into which it is inserted?
Did you use the manufacturer's recommended thermal conductive grease? (Some heating techs don't)
Thermal grease is recommended by limit switch manufactures for units whose sensor probe fits into an immersion well in a heating boiler or water heater. Absence of good contact between the sensor tip and the sensor well sides can explain off-spec temperature sensing as well as (I think) odd burner on-off cycling.
Reader follow-up;
Dan, I was not aware of the thermal grease. Did not see it mentioned in the directions.
It would seem the grease could help get the high limit set at 180F and a actual boiler flame off at 180F. However it is worth noting that the boiler does flame back on at 140F. I would gladly pull the probe and use thermal grease in an attempt set things to right. Well worth trying. :) - Don Fletcher
Reply:
For a limit control sensor to work properly when inserted into the immersion well on a boiler, it must be in contact with the inner surface of the immersion well; the grease assures good thermal contact. The limit controls I've bought and installed generally came with a little tube of the special grease.
Some time ago some heating techs avoided using the grease claiming it solidified and made later service difficult. That problem was corrected. In sum , the control should be installed according to the manufacturer's specs. Check with the company who made your unit. Let me know if youre' told something different. The thermal grease was commonly provided with older Honeywell aquastats and is also sold at plumbing and heating suppliers - IF your unit's manufacturer specifies its use (not all do) you'll want to add it.
Reader follow-up
Well, I it's a Honeywell L4080D1226 and I called them today and was told heat conductive compound is not supplied with the limit assembly. There is no mention of the grease in the Weil McLain parts list. So I took the sensor body out of the well and tilted the sensor in an effort to get good metal to metal contact.
But, the results changed nothing. I did not call Weil Mclain yet but I will. I will also get some compound to put in there as well. The well is not a snug fit to the sensor, that is to say there is air space. So there is room for thermal compound.
This morning with everyone taking showers I took pressure readings while the boiler was fired up. What was 17psi cold or hot has become 17psi cold & 21psi hot. Higher than needed but OK I think if it stays that way. Pressure release valve is not dripping.
...
Well the boiler is at 100F and I just checked the pressure. It is 21psi. That makes what I said earlier (17psi cold 21psi hot) very wrong.
The street fill valve is closed and as far as I know the indirect water heater is the only other place the extra pressure can be coming from. Although it would seem it is doing so in short intervals.
Reply: other sources of abnormal boiler or water heater tank (cylinder) pressrure
Donald
If your boiler or your hot water system includes a tankless coil or any equivalent (a coil containing house water (to be heated) immersed in the vessel whose TP valve is leaking, shut OFF water entering that coil - to see if house pressure in the coil is sending water through a coil leak into the boiler.
Also, leaks into the boiler from the house pressure side can cause abnormal boiler pressures that can show up as a relief valve leak: see
TANKLESS COIL / HOT WATER COIL LEAKS
Reader follow-up: possible pinhole leak in tankless coil
Coil contains circulated boiler water. Hose water at street pressure may be leaking into the coil by way of a pin hole in the coil. So we are on the same page so to speak.
I have shut of boiler supply to the coil numerous times. But it is not easy to prove out the problem because it happen very intermittently. I will monitor it overnight and see the PSI in the early morning. If it's like past history it will still be 21 lbs come morning.
If I wait it out it could weeks or months before the hole will open up and cause it to happen again. There are no leaks from any pressure relief valves at this time.
The Bock indirect water heater TP has never leaked. Thanks for helping me with Dan, I really appreciate it.
Reply:
Donald
Usually house water pressure is higher than boiler water pressure - but not always.
If the boiler is COLD its internal pressure may be just 12 psi. In that case house water pressure inside the indirect water heater tank, sitting at say 30 psi to 60 psi, might indeed leak INTO the coil through which boiler water is circulating.
You should see that as a pressure increase on the boiler pressure gauge as long as you've left the system off long enough to have a boiler-cold-before and boiler-cold-after pressure reading.
The case you describe, house water pressure leaking INTO the heating coil inside of an indirect-fired water heater is similar to the tankless coil leak case I describe in the article linked below.
Keep us posted.
...
I have a Weil McLain gas boiler. The minimum setting for the aquastat is 140*.
It is hooked up to a heat exchanger that is tied into an outdoor wood furnace. MY gas boiler would kick on when the circulators called for heat and the 3 zones were colder than 140*.
I put a Honeywell 1018 606C aquastat on the water line coming in from the boiler and wired that directly with my aquastat on the gas boiler.
I thought that would stop the gas boiler from coming on if the wood furnace aquastat was up to temp but it still comes on. Is there an aquastat I can put on the gas unit that would stop this?
And why did my second auqastat set up do nothing? (Dec 7, 2015) dave
Reply:
Dave:
I don't have a clear-enough picture of your wiring nor exactly where the second aquastat is installed to feel safe giving advice on this problem. I would like to see a schematic of what you've done, piping and wiring - you can send that by the page bottom CONTACT link if you like.
For a fast solution I suggest stopping by your local plumbing and heating supplier to ask their advice.
Watch out: ANY control wiring, mix, or application that is not what the manufacturer specified and designed is potentially dangerous. ON the combination wood/heat systems that I've inspected the manufacturer provided the controls they wanted us to use, specified their mounting instructions, gave wiring diagrams &c. A mistake could cause a fire or a fatal explosion.
Could use some guidance as my situation is very similar to this thread. Switch to heat pumps for both heating and a separate Heat pump HW system.
My oil furnace is now only for backup forced hot water backup heat on single digit and colder days.
I've left my aquastat hi/low at the summer values, which I thought were efficient (110/140).
Now I notice it takes longer for the backup heat to assist, but I'm ok with that as long as my oil consumption is lower/efficient. Did I miss the mark with these settings? On 2018-01-01 1 by Jim
Reply by (mod) -
If your system uses an aquastat you have hydronic or hot water heat - properly called a boiler, though many people use the word "furnace" generically. (Furnaces are hot air systems) - just to be clear.
Now for a boiler, you'll get more efficient heat transfer by setting the aquastat HI up close to 200F as described at AQUASTAT HI LO DIFF SETTINGS - topic home.by Jim
Thank you for the quick response! You are correct on your assumptions and my incorrect description.
Appreciate it very much and will use that guidance.
I have two boilers for my home heating system. The main system is an electric boiler that runs on a Dual Fuel system. When the Power company decides to turn off the electricity to the main boiler, the system switches over to my backup Oil boiler (Burnham).
The back up boiler is installed in my garage where the temperature is approx. 40 degrees in the winter.
I have tried to set the HI and LOW settings to not run if the house is not calling for heat. Sometimes the cooler temps in my garage will cool off the boiler water temps and want to come on, wasting oil consumption.
What would be the best HI/LOW temps for this situation. Knowing on occasion the Electrical power will be turned off for a few hours and the house might need the back up oil boiler to take over the task. Can I set the LOW on 100 and leave the HI on 180?
I'm thinking the lower limit may not be reached in a few hours of the Main boiler being shut off. Your thoughts? On 2017-09-23 by JIM
by (mod) - LO it's only needed to work with a tankless coil for making domestic hot water,
Jim,
As the LO it's only needed to work with a tankless coil for making domestic hot water, and as apparently you're not making that use of this boiler, you might want to disable the low function entirely.
this article series includes the description of how to do that.
Then you can set the high limit down as you suggest although there is some advantage to keeping a bit of heat in the boiler even when your house isn't calling for heat as it avoids rust corrosion and his damaged.
The fact is that if your house isn't calling for heat when they boiler cools off enough to turn on the burner the on cycle will be rather short because you're only heating the water in the boiler itself. The total cost of those Cycles would be quite small.
keep in mind that it's the inside thermostat in the heated portion of the house that's going to be responsible for turning the boiler on for a longer on cycle.
I actually prefer leaving my boiler set to 180 or 200 because that's more efficient way to operate a boiler when I'm running for heat and when my boiler doesn't include an automatic outdoor temperature compensating device.
Philip asked:
I have just installed an outside wood burning furnace that ties into my oil Furnace via a water to water heat exchanger. The wood furnace cycles Hot water constantly. When the house calls for heat the oil furnace turns on for about 5 minutes or longer. I assume this a result of the colder radiator Water cycling through the heat exchanger.
Once the oil furnace gets up to temp it stops and the wood furnace keeps up. I would like to have the Oil furnace burner not turn on at all. Can I unplug the connector from the Aquastat to the burner? And will the two circulating pumps still work for the Hot water and heat. (Oct 17, 2011) Phillip
Jeff
I have just installed an outside wood burning furnace that ties into my oil
Furnace via a 30 plate water to water heat exchanger. The wood furnace cycles
Hot water constantly at 170. My aquastat settings are HI 130 LO 110 DIFF 10. I have tried to adjust the settings in many ways to eliminate the oil furnace from running at all, but have not been able to do this.
When the house calls for heat the oil furnace turns
on for about 2- 5 minutes. I know this a result of the colder baseboard
Water and the reservoir in the oil furnace cooling between calls for heat. Once the oil furnace gets up
to temp it stops and the wood furnace keeps up. There are times when the circulator pump runs without the furnace running which is ideal.
I would like to have the
Oil furnace burner not turn on at all. I know I can unplug the connector from the
Aquastat to the burner or add a switch and the circulating pump will still work but I was hoping to achieve the never use oil system without having to do this.
What settings would you make for the HI, LO, DIFF and at what temperature would you run the wood furnace? If I bring the HI to 120 can there be be a 20 degree difference between the LO?
Thanks (Dec 7, 2011)
Reply:
Phillip:
I agree that the shot of cold water from the home's radiators will drop temperature in the boiler and cause its burner to turn on.
If the system is wired as usual, if you disconnect electrical power to the oil burner itself the circulator pumps will continue to function normally, Phillip. In fact one could install an electrical switch just for that purpose.
Just watch out: if you leave the burner off and also leave the home such that your wood burner runs down you'll risk frozen pipe damage.
Here's an alternative to consider:
Normally for boiler efficiency we like to set the aquastat HI to 200.
If your aquastat HI limit is set to 200 F (about as high as is safe), as long as the boiler temp stays above about 180F the burner won't come on until boiler water drops below that point. The burner "on" point is fixed at about 20 degF. below the HI (assuming you are not using a tankless coil for domestic hot water and the LO limit and DIFF have been disabled).
But if you temporarily drop the HI down to 120, the "ON" point will be around 100 - that too might prevent unnecessary boiler cycling when the wood burner is working.
If you do use a tankless coil and the aquastat's LO and DIFF are left in service be sure to also keep the LO set to at least 20 degF below the new HI setting.
Phillip replied
Thanks DanJoeFriedman for the response. I have a one zone house with about 18 radiators. The amount of cold radiator water is quite large to cycle through the furnace.
If I understand you correctly no matter what setting I use for the Hi/Lo and differential I would still expect that the oil furnace would kick in until the temp reached the diff limit. Today I set the hi to about 140 the low to 120 and the diff to 10 degrees.
My thought was that with the lo set at 120 the furnace would kick off at about 130 degrees and with the heat exchanger helping out heat the cold return water that that would minimize the amount of time the oil furnace is on.
Ideally I would like the oil burner to never kick on unless the wood furnace burns out or has a failure with its circulating pump. If there is no harm in just unconnecting the burner cable from the aquastat (there is a nice connector in the middle of the cable) then I might try that this weekend.
I can always reconnect during the cold months as a backup. So just to be clear on a typical installation there is no feadback to the Aquastat from the burner unit that would cause the Aquastat from not turning on the circulating pumps when there is a call fro heat from the house or the hot water tank?
Reply:
Not quite Phillip
Please review the explanation of HI LO DIFF
The boiler will start it's oil burner if on a call for heat at the thermosta the boiler temp is about 10F below the HI
The Lo and diff settings maintain heat in the boiler when there is no call for heating, in order to heat a tankless coil in summer.
I'm skipping details found in the articles on this topic.
I have a pellet boiler tied into my oil burner and a super stor water heater. What do you recommend to have aquastat settings H,L DIFF on the oil burner set at so the 2 systems operate efficiently.
Right now the the oil burner kicks on and the pellet boiler doesn't ignite or still at a low burn rate because the unit is not calling for heat. Thanks for the help! On 2016-10-26 by Jesse
Reply by (mod) -
Jim the flow rate of water into a tankless heater will determine if it turns on or not. Too-slow an inlet rate will keep the burner off.
Search InspectApediafor TANKLESS WATER HEATERS for details.
Watch out: You can operate both at once but the output water temp may be too high and so risk scalding burns unless you also install a tempering valve.
Properly adjusted a demand or tankless water heater (not a tankless coil on a boiler) gives endless hot water at whatever temp you want. I would concentrate on solving the input pressure issue.
...
Nick
Currently I have a Burnham oil boiler with a honeywell aquastat set at 180/160/20 diff.
I am planning on installing an electric hot water heater in series with the boiler so that in the winter the coil is used to preheat the water coming into the electric hot water and in summer I can fully turn off the oil boiler and only rely on the electric hot water heater, thus using no oil but still having hot water. IN the winter, when I am using the boiler to heat the house- using copper/aluminum baseboards- what are going to be my best settings.
We tend to keep the house on the cool side, as this is a guest-house that isn't always occupied. We live in Maryland, so there are some very cold days, and some not so cold. My feeling is that settings along the lines of 190/120/25 diff might be good.
It seems that the low should be set very low- on a warm winter day where there is minimal call for heat, there is no reason to keep the water warm, and everything suggests that the high should be high with this type of baseboard as it is much more efficient at a high temperature.
My goal is to maximize efficiency, ie minimize oil usage. What are peoples' thoughts on this??? I'm unclear what my best diff setting is. Does the diff only effect the low?
On reading this, maybe more appropriate settings for me would be 190/120/10 diff. Thoughts? Feb 15, 2012)
Reply:
Buddy
Nick, I installed an electric water heater in parallel with my tankless water heater last year.
You can see my comments on January 12, 2012 on this web-site under "Guide to Heating System Boiler Aquastats (AQUASTAT CONTROLS) ,
Their Settings & Wiring." Installing your electric water heater in series after the tankless seems to makes sense since your hot water usage is probably relatively low.
My old settings were 190 hi/160 low/ 15 diff in order to ensure adequate domestic hot water temperature.
This winter I have my Aquastat set at the lowest possible, 130 hi/ 110 low/ 10 diff although the actual boiler temperature seems to run about 150 hi and 120 low.
I am using the electric water heater but not the tankless.
These settings have been adequate to re-heat the house with copper/aluminum finned baseboard and set-back thermostats set at 58 degrees night and 68 degrees daytime, while maintaining house temperature even on the coldest days.
It does take longer to heat up the house now but the temp no longer swings up past the thermostat setting and rooms that ran colder than others before now seem to benefit from the lower boiler temperature and longer circulator run times. If your guest-house is well insulated you can probably get by with these settings. If not, you can always bump up the high temp.
The lower aquastat settings should save oil due to reduced heats loss out the flue and from the boiler casing and also from the higher heat transfer efficiency from the burner flame to the colder boiler water.
The baseboard will now transfer less heat per hour per square foot at the lower temperature but the heat transfer efficiency will still be 100 percent.
Efficiency will not change with water temperature, only the heat transfer rate. Unintended consequences -
1) The basement is now cooler in the summer and more humid. Running a dehumidifier may kill my savings.
2) The internal cast iron boiler sections may be more rapidly corroding due to not being heated. (Feb 28, 2012)
Efficiency is actually "output divided by input".
Paul
Nick, I have a Weil-Mclain Gold Oil Burner Model P-WTG04 series 3 boiler. I have 4 heats zones controlled by an Agro controller. I also have an Amtrol Boiler mate for hot water connected to the Argo priority zone.
What should I set the Honeywell 8124 A aquastat. I am confused as the what differential and Low limit should be used, It is presently set 160 H 140 Low and 15% DIF. Thank you for your help!
(mod) said:
Nick, for reasons we explain in AQUASTAT HI LO DIFF SETTINGS, we don't prefer your aquastat settings for a boiler that includes a tankless coil.
Buddy, thanks for the helpful detail and update.
On most points including your advice to Radhames, we agree completely. Contact me by email if you want to be more fully identified as a reviewer/commentator. (June 14, 2012)
...
...
Continue reading at AQUASTAT HI LO DIFF SETTINGS - topic home, or select a topic from the closely-related articles below, or see the complete ARTICLE INDEX.
Or see these
AQUASTAT HI LO DIFF SETTINGS FAQs-3 at InspectApedia.com - online encyclopedia of building & environmental inspection, testing, diagnosis, repair, & problem prevention advice.
Or see this
Or use the SEARCH BOX found below to Ask a Question or Search InspectApedia
Questions & answers or comments about the best settings for aquastat controls on heating boilers
Search the InspectApedia website
Need to make a private comment? Email editor@inspectApedia.com. We welcome email with your website content critique, corrections, suggestions or questions. Email is monitored daily but our workload may prevent an immediate reply. For immediate results, we hope you'll first try asking your question using the search box just above.
In addition to any citations in the article above, a full list is available on request.