This page continues our report on the causes and effects of rust and corrosion in electrical panels, sources of water leaks into electrical panels
A Study and Report on Frequency and Causes of Rust & Corrosion inside of residential electrical panels begins
at CORROSION in ELECTRICAL PANELS. This report by Daniel Friedman was presented to the electrical engineering community at the IEEE Holm Conference on Electrical Contacts.
InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers, products, or services discussed at this website.
- Daniel Friedman, Publisher/Editor/Author - See WHO ARE WE?
This page continues with details supporting
CORROSION in ELECTRICAL PANELS - Holm Conference Study.
Here we detail the specific sources of condensation, moisture, water in electrical panels and the panel contents or components, as observed and reported in that report.
A significant advantage accrues from having a service panel inspected as part of a more comprehensive property inspection: home inspectors are concerned with the building envelope, with water entry, and with damage to building components from moisture.
In normally damp climates moisture is a major factor in building damage; identifying moisture sources and controlling moisture is important both in diagnosing failures and in protecting buildings from future failures. For each panel reported as a "problem" the inspector logged the apparent source of water entry.
(For each of the 126 services for which defects were reported, the apparent sources of water entry was recorded.) [Table 3 below]
Table 3. Apparent Entry Source(s) of Moisture - #Cases - Percent of Total |
||
Service Entrance Cable Defects | 310 | 66% |
Condensation | 83 | 17% |
Surface/Roof Runoff Leakage | 79 | 17% |
1. For a given panel in some instance more than one possible source was recorded
2. High interior moisture levels from any condition could cause condensation.
Naturally a major source of high interior moisture levels is the third item listed,
surface and roof runoff leakage into the building.
3. Percent of total possible sources observed (472)
The most common sources of water and moisture entry were: through service entrance conductor cables which were old and damaged, or which were improperly sealed at meter boxes or building sidewalls; from condensation from high interior moisture levels; and from other building leaks or surface water which passed down building walls where panel enclosures were mounted.
By far the most common source of water entry in service panels, 310 out of 472 possible sources observed, is associated with the passage of an above-ground service entry cable from outside, through the building wall, into panels which are located in basements or at a location lower than the point of penetration of the cable through the building wall.
There was often strong visual evidence that water had entered service enclosure, including: water stains and drip marks on components directly below the center of the entry cable when it enters the service equipment; water stains, sometimes rust marks, down the exposed face of circuit breakers; water droplets present on connectors and other components at the time of inspection.
...Water, often in large volumes from wind-driven rain, followed the entrance cable into the building on these paths:
Figure 7, water follows electrical service entry cable exterior into the building and into the electrical panel through an un-caulked opening in the building exterior wall.
Water, often in large volumes from wind-driven rain, follows the entrance cable into the building on three failure paths:
A surprising number of occurrences of water entry appear to be due to other building leaks, 79 of 472. These sources include roof leaks (water passing from leaks into soffits through building walls and down basement wall - rare), and basement water entry associated with improper handling of roof runoff (leaky gutters) or surface drainage.
Water concentrated around a building from roof runoff or surface drainage often results in moisture seeping through the foundation wall.
It's an interesting coincidence that service panels are often mounted in the corner of a basement, just where water may be concentrated outside from a faulty downspout.
On a typical modern home with a single downspout at front and rear roof edges, chances are one in four that a service panel and a downspout will find themselves sharing a damp corner.
In such cases we've occasionally observed water entering the rear of the service panel at points of contact with the basement wall, even when the panel is actually affixed to plywood or nailer boards which themselves are fastened directly to the foundation.
However the principal path from roof/surface runoff to panel is probably interior condensation due to high moisture levels caused by general basement water entry, discussed next.
The most common mechanism by which moisture entered these panels was from roof/surface runoff, causing basement water entry and high indoor moisture levels which in turn lead to condensation.
This finding is discussed below. In a few other cases there were indications of water entering the rear of the service enclosure at points of contact with the basement wall, even when the enclosure was actually affixed to plywood or nailer boards which themselves were fastened directly to the foundation.
When water, corrosion, or signs of a history of wetness in service equipment were found and when there were no obvious contact-paths for droplets to travel in to the panel from outside, condensation inside the panel was recorded as the apparent source. In 83 of 472 cases there were wet-basement conditions but the service panel was mounted well away from points of outside water entry through walls or cables.
When moisture is observed primarily at specific panel locations, such as below the entrance cable or on the panel base, and when most other panel components are not corroded, we suspect specific points of outside entry such as described earlier.
But in many inspections we observe water, corrosion, or signs of a history of wetness in panels where there are no obvious contact-paths for droplets to travel in to the panel from outside.
In these cases, when corrosion is fairly uniform over panel enclosure sides and top, and over other panel components, we suspect that moisture is occurring as condensation inside the panel. Often the inspector will find such indications.
This was so in 83 of 472 cases, when there were generally wet-basement conditions but when the service panel was fortunate to find itself mounted well away from points of outside water entry through walls or entry cables.
While not a part of this study, we have observed this pattern of rust and corrosion on panel components even in very dry climates (Tucson and Phoenix) where electrical equipment was installed against masonry walls in service closets accessed from outside the building.
From these observations we suspect that the combination of high interior moisture levels in many basements, combined with temperature changes, results in movement of moisture to the interior of service panels on a regular basis during humid weather.
Also see BACKDRAFTING & SEWER/SEPTIC ODORS for an explanation of how negative air pressure in buildings can cause unexpected air and moisture movement, condensation, and moisture-related problems such as rust, corrosion, or odors, or mold.
Burned connectors:Among other common panel "defects," any burned connectors observed in service panels were recorded and tabulated. There were 23 such cases out of the 1052 panels observed, a 2% occurrence. In at least two of these 23 cases, the evidence of an actual fire in the panel was found.
Other Observations:The following incidents, observed one or more times during the 1052 inspections are reported:
See more details about sources of moisture and corrosion in this separate article
CORROSION & MOISTURE SOURCES in PANELS
...
Continue reading at ELECTRICAL PANEL AGES VS FAILURE RATES or select a topic from the closely-related articles below, or see the complete ARTICLE INDEX.
Or see these
ELECTRICAL PANEL MOISTURE / WATER SOURCES at InspectApedia.com - online encyclopedia of building & environmental inspection, testing, diagnosis, repair, & problem prevention advice.
Or see this
Or use the SEARCH BOX found below to Ask a Question or Search InspectApedia
Questions & answers or comments about the causes & frequency of occurrence of dangerous leaks or moisture in electrical panels. .
Try the search box just below, or if you prefer, post a question or comment in the Comments box below and we will respond promptly.
Search the InspectApedia website
Note: appearance of your Comment below may be delayed: if your comment contains an image, photograph, web link, or text that looks to the software as if it might be a web link, your posting will appear after it has been approved by a moderator. Apologies for the delay.
Only one image can be added per comment but you can post as many comments, and therefore images, as you like.
You will not receive a notification when a response to your question has been posted.
Please bookmark this page to make it easy for you to check back for our response.
Our Comment Box is provided by Countable Web Productions countable.ca
In addition to any citations in the article above, a full list is available on request.