Building Inspection, Diagnosis & Repair Info

Corroded metal parts contributd to electrical failure of this back-wired receptacle at a beach house (C) InspectApedia.com Curt RussellBackwired Electrical Outlet Failure Report

Back wired electrical receptacle failure field report:

Curt Russell describes the detection and repair of electrical receptacles in a beachfront home. A combination of use of back-wired electrical outlets or receptacles and the corrosive effects of exposure of electrical wiring to salt air led to loss of electrical power.

This article series explains and documents cases of the failure mechanisms that lead to loss of electrical power or overheating and fires that occur on electrical circuits wired using back-wired electrical receptacles and switches.

InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers, products, or services discussed at this website.

- Daniel Friedman, Publisher/Editor/Author - See WHO ARE WE?





ADVERTISEMENT





Lost Power: Back-Wired Electrical Receptacle Failure & Repairs at a Beach-Front Home

Leviton back-wired or side-screw-terminal-wired electrical receptacle (C) InspectApedia.com photo provided by Curt Russell - Curt Russell July 2018

We Lost Electrical Power, Breakers Were Not Tripped

On Sunday, as we were cleaning up, the hot water went off. I went down to the utility room to see if there was a problem I could resolve.

I found that the electricity was off in the utility room which serves the controls on the hot water heater as well as the lights and receptacles in all of the closets.

The refrigerator was also off and all of the outdoor ground fault receptacles were off as well. At first, I thought maybe one of the outdoor ground fault receptacles had gotten wet.

[Photo shown provided by the author, used here with permission. ]

[Click to enlarge any image]

We had heavy rain and high winds on Saturday and through Saturday night. I pulled each of these receptacles out and tested them for current… all were dead.

I checked the breaker panel and none of the breakers were tripped - which made me very curious. I pulled the cover off of the breaker panel that fed this circuit and verified that there was juice going to the circuit - which there was.

I noticed that there is a receptacle on the wall to the right of the breaker panels that mirrors a ground fault receptacle on the outside wall.

Thinking that this receptacle might be the first in the circuit, I pulled it out to check it. As I was pulling it out, I noticed that the light in the utility room came on.

Good: I found the problem!

Not good: the problem was caused by what I consider bad electrical wiring technique by the electrician who installed the receptacle at the time of construction of the home.

I corrected the problem (by installing a new electrical receptacle using its screw terminals rather than push-in backwiring connectors), and everything is now well with this receptacle and the circuit downstream.

But this circuit is not unique. Nearly all of the switches I replaced have the same issue, and this is a serious safety (fire hazard) concern.

Two Ways to Wire Switches & Receptacles: screw terminals or back-wired push-in connectors

Push-in connection opening on the back of an electrical receptacle (C) Daniel FriedmanShown in the photo: on many electrical receptacles and switches (let’s call them “devices”) sold in North America, both screw terminals and push-in type back-wire connectors are provided.

Other devices include only screw terminals, and still others previously included only push-in terminals.

So there are two ways to wire these switches and receptacles in residential circuits.

  1. Use the screw terminal side-wired connectors - the hot and neutral wires are connected to the device by screws located on the side of the switch or receptacle. The wire is stripped, bent into a loop around the screw, the loop is pinched closed, and the screw is tightened.
  2. Use the push-in back-wired connectors - the hot and neutral wires are connected to the device using a push-in connector: a hole into which a straight section of stripped wire is simply inserted.

    This second connector is called a "back-wire" connection because the connector is located on the back of the device.

    The wire end is stripped (a strip length gauge is provided on the device) and pushed into a hole where it is gripped by an internal spring in the device.

    Avoiding having to bend the wire around a screw and then tighten the screw is a big time saver for the electrician.

    There are actually four versions of push-in back-wire connectors used on receptacles and switches. Details are

    at BACK-WIRED ELECTRICAL DEVICES, 4 TYPES

Many residential 15A and 20A rated receptacles and switches included and still include both screw-terminal and push-in back-wire terminal wiring connectors, giving the electrician a choice of how to connect those devices.

In the photo above, you can see the two different types of connectors provided on the same receptacle.

Watch out: In my view spring-type push-in wiring terminals are unreliable, therefore unsafe, and they should not be used.

What's Wrong With Spring-Type Back-Wire Connectors?

Corroded metal parts contributd to electrical failure of this back-wired receptacle at a beach house (C) InspectApedia.com Curt RussellThe problem with back-wiring into a spring-type connector like the ones we illustrated earlier is that due to any or a combination of factors, spring force, small contact area, and corrosion, the connections can fail. "Fail" here means either loss of a functional connection or overheating at the connector.

Photo provided by the author. [Click to enlarge any image]

Watch out: Loss of connection is experienced as a loss of electrical power to the receptacles (or lights or switches) - a circuit failure like the failure we had. Worse, overheating at the connectors is a fire hazard.

Shown here is the Beach House receptacle that failed (in the foyer, to the left of the back door going out to the utility room).

The four copper wires you were all back wired. I pulled the black wires out so you can see the corrosion on the stripped-back copper wire ends.

They look black and green - corroded. The wire-to-spring connectors may have been arcing as well.

Note also the rust and corrosion on the screws that connect the receptacle to the electrical box and the rust on the ears of the steel receptacle mounting strap: these tell us that this device was installed in a corrosive environment - consistent with exposure to damp salt air at a beach-front home.

Both arcing and corrosion could explain the black, oxidized surface shown on these wires. That oxidized surface means that the electrical connection through the stripped wire end has to pass through oxidized copper: a poor connection that risks loss of current flow (no power) or overheating (fire).

Watch out: Because this is a beach-front home on salt water, it is also likely that the exposed copper wire and all electrical connectors in this home suffers extra corrosion from the moist salt-laden air. That makes the quality and security of electrical connectors all the more important.

Wiring Electrical Receptacles In Series

When a receptacle is wired as shown in this photo, all of the circuit neutral (white) wires are connected to the neutral terminals or connectors right on the receptacle, and all of circuit hot (black) wires are connected to the hot terminals on the receptacle.

All of the current used downstream of the receptacle goes through the connectors on this receptacle - the entire circuit load.

That puts a huge electrical flow through the device. Where back-wiring connectors were used, all of that current is flowing through a tiny contact area between the spring and the wire of the the back-wire connections.

Back-wiring using the manufacturer-connections provided for that purpose is permitted by the U.S. and Canadian electrical codes.

Watch out: in my opinion the wiring practice of wiring receptacles in series and using push-in back-wire connectors is less reliable and less safe than two alternatives:

  1. The screw-type terminals are used for all wire connections, thus assuring that circuit current flows through a physically larger copper connector).

    This wiring approach still has the risk that if any connector in the circuit fails, all of the downstream devices will also lose power.
  2. The receptacles are wired not in series but in parallel (explained below) with the electrical circuit bringing current independently to each device on the circuit. In my view this is the best and safest wiring method.

Details of exactly how and why backwired connectors fail in receptacles and light switches are given by Friedman

at BACK-WIRED ELECTRICAL DEVICES.

Separately at RECEPTACLE WIRE-TO-CONNECTOR CONTACT AREA SIZES he explains that in addition to contact-force concerns, the very small contact area in back-wired connectors on receptacles is likely to contribute to connector failures.

Wiring Electrical Receptacles in Parallel to Improve Circuit Reliability

Rather than running all of the inbound and outbound wires through the device, the wires are all connected together with twist-on connectors.

Wiring uses a set of “pigtails” wired to connect the circuit conductors to the device.

In this way, the downstream circuit passes through the box without passing through the device itself. The only load on the device is whatever you plug into that device… not the rest of the circuit.

Photo provided by the author. [Click to enlarge any image]

For example, the 3 black wires left to right are as follows:

Hot coming in

Hot going out to other devices

Pigtail going only to this receptacle

The same goes for the white wires and the ground wires.

Watch out: when converting from device-wired to a parallel-wired electrical circuit in a string of receptacles, you can not use this pigtailing method unless the electrical box size is of sufficient cubic inches to contain the additional wires and connectors.

See details of wiring receptacles in series or in paralle

at ELECTRICAL RECEPTACLE WIRING SERIES vs PARALLEL

Repairs & Recommendations for Electrical Wiring & Devices in the Beach House

In the Beach House, every switch I replaced that had a downstream circuit was back-wired. The receptacles are likely done the same way. This means that the juice feeding everything downstream is passing through these devices and their back-wired connections.

Watch out: The circuit I fixed had the refrigerator, the hot water heater, all of the outdoor receptacles, the storage room receptacles and lights, and the ground floor toilet pump all going through this receptacle and these back-wired connections.

That’s a lot of juice to be passing through a receptacle, much less through a back-wired connection! That electrical circuit is overloaded.

Given the salt air environment and the amount of electrical load on your circuits, it is my opinion that the wiring in each and every receptacle and switch box should be reworked to eliminate back-wired connections as well as connections that pass through the devices.

That will require

I am not trying to be alarmist, but the wiring on the receptacle I fixed looked really bad. I didn’t like the wiring methods I saw elsewhere, and then this happened. It gives me a lot of concern.

The dimmer switches that are original to the house were designed for incandescent bulbs which are now nearly obsolete. These dimmers are not designed to work with new LED bulbs and the like. They will need to be replaced at some point fairly soon.

The refrigerator on the ground floor should probably be on a separate circuit. If this were new construction, a separate circuit would be required by code. While it is safe to have it as is, it consumes a lot of the capacity of that circuit which really limits what you can do with the other outside outlets, etc.

Here is what else should be done:

- ©2018 as Adapted & edited at InspectApedia.com


...

Continue reading  at BACK-WIRED ELECTRICAL DEVICES - topic home, or select a topic from the closely-related articles below, or see the complete ARTICLE INDEX.

Or see these

Recommended Articles

Suggested citation for this web page

BACKWIRED RECEPTACLE FAILURE REPORT at InspectApedia.com - online encyclopedia of building & environmental inspection, testing, diagnosis, repair, & problem prevention advice.

Or see this

INDEX to RELATED ARTICLES: ARTICLE INDEX to ELECTRICAL INSPECTION & TESTING

Or use the SEARCH BOX found below to Ask a Question or Search InspectApedia

Ask a Question or Search InspectApedia

Share this article:

Questions & answers or comments about how to install and wire electrical outlets or receptacles in buildings.

Search the InspectApedia website

Need to make a private comment? Email editor@inspectApedia.com. We welcome email with your website content critique, corrections, suggestions or questions. Email is monitored daily but our workload may prevent an immediate reply. For immediate results, we hope you'll first try asking your question using the search box just above.

Citations & References

In addition to any citations in the article above, a full list is available on request.



ADVERTISEMENT