InspectAPedia®   -   Search InspectApedia

GFCI wiring details, back view (C) Daniel FriedmanElectrical Receptacle (wall plugs) & Switch Connector Performance

Comparison of combined effects of contact area x clamping force supports use of screw connectors

Electrical receptacle & switch connection performance over their service life:

When we consider the effects of differences in contact area and clamping pressure, simple measurements suggests that there may be significant differences in the reliability of different types of wire connectors used on receptacles and switches.

Longer term study of the performance of these connector types in homes is needed. Meanwhile, using the binding-head screw or screw-clamp connector certainly seems to offer a more-confident wire-to-device connection than using the push-in back-wired spring-clip connector.

This article summarizes measurements of connector size and clamping pressure of three types of electrical connectors and combines those effects into a "connection quality" number.

Using the back-wire or push-in type connection points on an electrical receptacle or switch may be just fine, or it may not be reliable nor safe, depending on the age and type of back-wire connector provided. This article series describes the types of backwire connectors used on electrical receptacles and light switches and we explain the safety and performance questions that may arise.

The conclusion is that using a spring-clamp connector is superior if you must back-wire a device, and using a wire wrapped around the shaft of a binding-head screw connector is best.

InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers, products, or services discussed at this website.

- Daniel Friedman, Publisher/Editor/Author - See WHO ARE WE?

Electrical Wire to Receptacle Connector Type Service Life Performance Comparisons

Article Contents

Types of Electrical Wire Connectors at Receptacles & Switches

Wire being pushed into the back of a back-wired spring clip type receptacle (C) Daniel Friedman

The following summary is derived from detailed data given in two supporting articles cited below.

At BACK-WIRED ELECTRICAL DEVICES we describe three common methods (and a fourth less-common back-wire only method) of connecting electrical wires to electrical receptacles ("outlets") and switches. Here is a recap of the three connector types:

  1. Push-in back-wired connectors using an internal spring-clip inside the device

Wire contact points in a push-in type backwired electrical receptacle (C) Daniel Friedman

[Click to enlarge any image]

  1. Screw-Clamp connectors that permit connecting of wires through the back of the device

Receptacle 20A backwired clamp type © D Friedman at InspectApedia.com

  1. Binding-head screw connectors that secure a wire wrapped around the screw shaft between the under-side of the screw and a mating connecting surface on the device.

Binding head screw connector with copper wire on an electrical receptacle (C) Daniel Friedman

The first two of these electrical wire connectors are popular because of the speed and ease of making the connection. The third, the binding head screw can accept either a straight wire, making it similar to the screw-clamp connector, or a wire can be wrapped around the screw after which the screw is tightened using a hand or power screwdriver.

While opinions may vary, field failure reports that seem to occur principally among push-in backwired electrical devices as well as objective measurements suggest that the safety, performance, and reliability of these three connector types varies considerably.

In particular, the bulk or gross-level size of physical contact area size between the wire and the connector as well as the clamping force of the connector against the wire are very different among these three choices.

The connection quality and reliability varies accordingly. Low contact force between the wire and the receptacle connector where spring-type push-in backwired terminals are used on receptacles is probably the most significant reason that these connections can be expected to deteriorate over many years, but the contact area size also varies considerably.

Summary of Wire to Connector Contact Area Size & Clamping Force for Electrical Receptacles

These conclusions are based on supporting details for these wire to receptacle connector service life performance estimates are in the two articles linked in the text below.

From the summary table at RECEPTACLE WIRE-TO-CONNECTOR CONTACT AREA SIZES we have these contact area sizes:

The ratio of best case (straight wire, looped under a binding head screw) to worst case (bent wire under a spring clip) the contact area ratio is

Next, from WIRE-TO-CONNECTOR FORCE COMPARISONS Aronstein reports a 75x difference in clamping pressure or force between spring clip and screw connector, where the screw connector exerts the much greater force.

In that article we state that

Contact Resistance is a function of (force x micro-contact points x other factors such as oxide resistance)

Ignoring other factors that remain the same among these connector design differences (or differences that we are not considering such as resistance to mechanical disturbance)

To compare overall contact quality of a spring clamp backwired device with a binding head screw connector, we multiply these two factors (ratio of differences in contact area x ratio of differences in clamping force) together to claim that comparing best to worst case among the connections examined,

assuming that all other features such as wire and contact smoothness that would affect micro-level contacts are equal.

Note 1: while my estimate of the area of round wire surface in contact with a flat surface (x length of wire) is a guess at the width of round wire actually touching at the tangential point of contact with the flat surface (0.1mm), that doesn't matter nor does it change these ratios since I use the same wire surface contact width in all cases. It's the varying lengths of the bulk contact areas that I'm comparing.

Note 2: the quantitative analysis given above is for purposes of demonstrating relative differences among different electrical connectors and does not attempt to represent the exact function that would describe the precise product of connector clamping force and contact area as a means of comparing electrical devices.

The actual relationship may be more complex and might require measuring other forces such as electrical resistance and mechanical motion as well as a tabulation of force with contact area combined with numerical analysis that is beyond the scope of this article.

Electrical Wire to Receptacle Connection Quality Conclusions

OPINION:

  1. Binding head screw vs. spring clip backwire connector:

    For electrical receptacles and switches that offer a choice of using a push-in type spring-clip backwire connector and using a binding head screw connector to connect a No. 14 copper wire to the device, the overall quality and thus long term reliability of the electrical connection made by the combined effects of contact area (wire to connector) and contact force (wire to connector) under a binding head screw is between a maximum of 300x (straight wire) and 750x (wire not straight) better than that obtained using the push-in spring-clip connector.

    A wire wrapped around the screw shaft and tightened under a binding head screw gives the most-reliable electrical connection at an electrical receptacle or switch.

    The actual benefit of using wire wrapped under a binding-head screw will be less than the theoretical maximum because the wire under the screw will never form a perfect 360 degree circle when applied in the field. However the relative contact area x clamping force differences among these connectors remains dramatic for all cases.
  2. Pressure plate screw vs. spring clip backwire connector:

    For electrical receptacles and switches that offer a choice of using a push-in type spring-clip backwire connector and using a pressure-plate screw connector, other constraints kept as in the case above, the pressure plate screw connection is between 150x (straight wire) and 200x (wire not straight) likely to be more reliable in long term use.

    Overall, the binding-head screw offers the best electrical wire connection quality and long term reliability, all other features being equal, because it offers the greatest bulk surface contact area and significantly-higher contact pressure. The pressure-plate connector is also likely to perform significantly better than the spring-clip connector.
  3. Back-wiring best choice:

    Electrical workers installing receptacles and switches who want to back-wire a device will be selecting the more-reliable connector using the back-wired screw-clamp connector than a push-in spring clip connector.

    Inserting a straight wire end into a screw-clamp connector gives more contact surface than inserting a straight wire end beneath a binding head screw, but either of these connections is probably more reliable than using a back-wired push-in spring clip connector because the screw exerts much greater clamping force than a spring-clip connector.
  4. Best choice in electrical connections at a receptacle or switch:

    Electrical workers installing receptacles and switches who want the most-reliable connector should wrap the wire under a binding head screw.
  5. Long term vs. short term performance & mechanical disturbance:

    These are electrical connection performance estimates are for the service life of the connector and do not predict short term performance nor do they address differences in the vulnerability of these wire connection types to mechanical or environmental disturbances.

    However it is apparent that a wire held in place by either of the two types of screw connectors is likely to be more secure against mechanical disturbance than wires held by the spring clip connector - an effect that we have not quantified.  

InspectAPedia is supported by ads placed on our pages by Google. InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers, products, or services discussed at this website.

Aronstein Comments:

Dan:

The actual metallic conducting area together with the mechanical resistance to motion at the contact interfaces strongly influence the life of a wire termination. For terminations in the permanent electrical power circuits in our homes, the safe life is the time in the expected range of normal service conditions before some samples start to heat abnormally.

Connections with relatively tiny metallic areas of contact and which are susceptible to motion at the contact surfaces may initially provide low resistance, but they are more likely to fail after some years in service. They cannot be depended on to provide the type of permanent connection that is required for long-term safety in buildings.

What your engineers interested in this matter need to do next is some life testing under actual service conditions to determine the relative life of a low-force contact vs. a high force contact.

All other things being equal, they will find that higher contact force yields longer life.

The field failures and the long-term test results provide the most persuasive evidence that push-in backwired receptacle wiring connections are not suitable for the permanent wiring system in homes. The performance of the older generation of back-wired push-in receptacles was poor, leading to limiting the size of wire that could be inserted to #14, reducing the number of wiring openings, and changing or eliminating the wire release features.

It is yet to be seen whether today's push-in wire termination types are sufficiently improved to provide the required low resistance performance over the long-term in actual installations. I do not want my home to be part of that experiment. What is crystal clear is that the binding-head screw termination is vastly superior to the push-in terminations, and that's what I would want - and what I have - in my home. - Jess Aronstein

Shields Comments

Contact force and contact area most likely have limits of benefit to both mechanical resistance of motion and electrical resistance.

The limits are likely to be a function of each parameter. I have not conducted tests to determine the nature of the limits and whether they occur within the range of actual contact areas and forces afforded by these connectors. If there is credible evidence of significant receptor malfunction or testing that raised question of malfunction I would expect a receptacle manufacturer would want to provide in-house data to support its product. - Lee Shields

References


...

Continue reading  at BACK-WIRED ELECTRICAL DEVICES - home or select a topic from the closely-related articles below, or see the complete ARTICLE INDEX.

Or see these

Recommended Articles

Suggested citation for this web page

WIRE-TO-CONNECTOR PERFORMANCE SUMMARY at InspectApedia.com - online encyclopedia of building & environmental inspection, testing, diagnosis, repair, & problem prevention advice.


Or see this

INDEX to RELATED ARTICLES: ARTICLE INDEX to ELECTRICAL INSPECTION & TESTING

Or use the SEARCH BOX found below to Ask a Question or Search InspectApedia

Ask a Question or Search InspectApedia

Questions & answers or comments about how to install and wire electrical outlets or receptacles in buildings.

Try the search box just below, or if you prefer, post a question or comment in the Comments box below and we will respond promptly.

Search the InspectApedia website

Note: appearance of your Comment below may be delayed: if your comment contains an image, photograph, web link, or text that looks to the software as if it might be a web link, your posting will appear after it has been approved by a moderator. Apologies for the delay.

Only one image can be added per comment but you can post as many comments, and therefore images, as you like.
You will not receive a notification
when a response to your question has been posted.
Please bookmark this page to make it easy for you to check back for our response.


Comment Form is loading comments...

IF above you see "Comment Form is loading comments..." then COMMENT BOX - countable.ca / bawkbox.com IS NOT WORKING.

In any case you are welcome to send an email directly to us at InspectApedia.com at editor@inspectApedia.com

We'll reply to you directly. Please help us help you by noting, in your email, the URL of the InspectApedia page where you wanted to comment.

Citations & References

In addition to any citations in the article above, a full list is available on request.



ADVERTISEMENT