Aluminum wire connections can overheat enough to start a fire without ever drawing enough current to trip a circuit breaker.

Other products sold for repair of aluminum wiring connections: Scotchlok 3M™, Ideal 65™ Purple "Twister", Marrette B-Cap ACS™ #63 AL/CU Twist-On Connector, Electrical Receptacles and switches marked "COALR" or CU/AL, and Harbor Freight's Aluminum to Copper Crimping Tool are not recommended.

Caution - some of these products are not recommended or have been superceded by newer listed products. This website answers nearly all questions about aluminum wiring inspection, hazards, repairs



Green links show where you are. © Copyright 2017 InspectApedia.com, All Rights Reserved.

OTHER Not-Recommended ALUMINUM WIRING REPAIR PRODUCTS: for Aluminum Electrical Wiring - Ideal 65 Purple Twister and Other Aluminum Wire Products/Articles

Currently-recommended aluminum wiring repair products & methods such as the AMP/TYCO COPALUM TM crimp connector and the AlumiConn TM connector, as well as other aluminum wire repair methods can be read-about at ALUMINUM WIRING RISK Reduction.

Aluminum Wiring Connectors or "repair methods" which are obsolete or which are not recommended, such as the COALR or CU/AL devivces, the now obsolete Scotchlok TM 3M Special Method, and aluminum wiring connectors and repair methods such as the Ideal-65 TM Purple Twist On Connector, or conventional twist-on wire connectors are described just below.

Further details are also found at Aluminum Wiring Repair Methods - CPSC Meeting.

COALR or CU/AL - Marked Receptacles & Switches for Aluminum Wire "Repair"?

Photo of a back-wired electrical receptacle Electrical Receptacles and switches marked "COALR" or CU/AL are also not recommended for aluminum wiring repairs:

The photograph shows a back-wired electrical receptacle with an aluminum-wired branch circuit. In this photograph case the electrical receptacle was marked as "AL-CU" but was further marked as Backwire CU-ONLY by its manufacturer.

[Photograph courtesy of Roger Hankey. Contributions of photos of CU-AL and COALR receptacles are sought by the author.].

See COALR & CU-AL Devices? for the details of these COALR or CU-AL (or AL-CU) products and why they should not be used with aluminum wiring.

Harbor Freight's Aluminum to Copper Crimping Tool

Harbor Freight offers a hydraulic crimping tool advertised as usable for aluminum wiring repairs. The tool is displayed and sold only by Harbor Freight as the Hydraulic Wire Crimping Tool Model 66150. Harbor Freight is a large, long-established tool retailer (since 1978) retailing a wide variety of tools and equipment.

We recommend that you read the instruction manual for this tool (large PDF).

As of 7 Feb 2009 we don't know the approval status of this tool for aluminum wiring repairs.

We took a preliminary look at the Harbor Freight Hydraulic Wire Crimping Tool Model 66150 and also at the instruction manual, and we saw that HF advertises that this tool intended for connecting copper and aluminum wires. The text does not say that the tool is approved for joining copper to aluminum wires as is performed in the standard aluminum wiring repair procedure. But we may be interpreting the manufacturer's text more carefully than did their ad copy writer.

What we don't yet know about this aluminum or copper wire crimping tool:

What we have learned so far about this copper to aluminum wire crimping tool

The Harbor Freight Hydraulic Wire Crimping Tool Model 66150 instruction manual has some interesting paragraphs like

6. Refer to the wire manufacturer's instructions for specific crimping instructions prior to using this product.

That paragraph alone might exclude the use of this tool for aluminum-copper pigtailing repairs. There are no such instructions. The manual also, quite understandably, includes a general disclaimer:

We shall in no event be liable for death, injuries to persons or property, or for incidental, contingent, special or consequential damages arising from the use of our product.

Is the Harbor Freight hydraulic crimping tool for copper and aluminum wires recommended for repairing aluminum wiring?

No.

But given the difficulty people in some areas have finding qualified aluminum wiring repair electricians, connectors, and tools, here some

IFs

THEN having another aluminum wire repair method would be a boon for the AL wire repair topic.

This tool is Distributed exclusively by Harbor Freight Tools®. 3491 Mission Oaks Blvd., Camarillo, CA 93011
800-444-3353. We recommend that before using it for aluminum electrical wiring repairs you call the company to ask the questions listed above.

Until those safety conditions are met we do not recommend any aluminum wire repair method other than those described at ALUMINUM WIRING REPAIR METHODS. Using a non-recommended tool for repairing aluminum electrical wiring might be unsafe and might also create fire insurance issues with your carrier.

On 3/6/14 we again asked the company for clarification, including an explanation of this concern:

These questions are critical because the tool is marketed as a repair for aluminum electrical wiring but only two methods of such repair are recommended by the US CPSC. If you or we send readers to a tool that is not recommended AND worse if it does not use a recommended method or connector, you might be actually increasing the risk of your customer having a fire in their home. 

Ideal 65 Purple Twist-On Connector for Aluminum Wire "Repair" ?

Ideal 65 Twister meltdown

Ideal-65 Purple Twist On Connector the Ideal 65 Twister (don't call it a "wire nut") - this one doesn't work - purple twist-on connector sold for aluminum wire repair

CPSC reiterates unsuitability of twist-on connectors (Including the Ideal No. 65) for repairing aluminum wiring in residences.

CPSC CONCERNS RE: ALUMINUM WIRING CONNECTORS

Independent Tests indicate Ideal-65 Twist-on retrofit connector fails UL 486C Safety Standard despite UL-listing

Ideal 65 "Twister" History of and Links to CPSC Documents about Purple Twist-on connector failures

Ideal Industries, Inc., 1000 Park Ave, Sycamore IL 60178-994. 800-435-0705 U.S. or 800-527-9105 Canada ideal@wirenut.com

Note: The instructions for this connector require that it always include a copper pigtail when making aluminum wiring connections - a condition impractical for splicing aluminum-to-aluminum wires.

Dr. Jesse Aronstein, "Evaluation of a Twist-on Connector for Aluminum Wire", Forty-Third IEEE Holm Conference on Electrical Contacts, Jan 1997, 0-7803-3968-1/97.
[This article describes the Ideal Industries Ideal#65 purple "Twister" twist-on connector marketed as a repair/retrofit for residential aluminum wiring.--DJF]

Abstract: A new type of twist-on splicing component for use with aluminum and copper wire combinations is tested to determine initial resistance, performance in a zero-current environment test, performance in a heat-cycle test, and portion of current carried by the connector's steel spring. The splices tested consist of two aluminum wires and one copper wire.

The aluminum wire samples used for the test are of the types actually installed in aluminum-wired homes. Initial resistance is found to be relatively high, and there is a significant sample-to-sample variation. This reflects failure to consistently establish low-resistance wire-to-wire contact through the insulating oxide film on the wire. Results of the environmental and heat-cycle tests show deterioration of a significant portion of the samples.

The splices made with this connector are also found to be sensitive to mechanical disturbance, such as applied in normal installation when the completed splice is pushed back in to the junction box. Based on the test results, it is concluded that this connector has not overcome the fundamental deficiency of twist-on connectors for use with aluminum wire applications. Keywords: aluminum wire, connectors, twist-on connectors, environmental test, heat-cycle test.

Marrette B-Cap Twist-On Connector for Aluminum Wire "Repairs"?

Marrette B-Cap ACS 63 Twist On Connector (C) Marrette Brown

Marrette B-Cap ACS#63 AL/CU Twist-On Connector for aluminum wire repair - is also not recommended for aluminum wire repair by the pigtailing approach. Dr. J. Aronstein provided this answer to the question that we have been asked, "Can I use the Marrette B-Cap ACS 63 AL/Cu twist-on connector along with antioxidant for reliable copper-to-aluminum pigtailing repair of aluminum electrical wiring?"

"The Marrette (Brown) ACS™ Aluminum Wiring Connector (Thomas & Betts) twist-on connector is basically the same as the Marrette "Special Service" twist-on connector, which was tested by Dr. Jess Aronstein shortly after that connector came out in the early 1980's. It performed poorly in tests with aluminum wire within rated conditions."

A paper was published on those tests and is our first citation just below. Aronstein comments that "The addition of an inhibitor compound does not correct the underlying deficiency of the twist-on connector type when used with aluminum wire." See "Reducing the Fire Hazard in Aluminum-Wired Homes" for additional information on twist-on connectors with aluminum wire. -- Jesse Aronstein, Ph.D., P.E.

Scotchlok 3M Connector for Aluminum Wire "Repair"?

Photo of the 3M Scotchlok wiring connector which can be used for aluminum wiring repairs, has tested successfully but has not been recommended by the US CPSCScotchlok 3M Special Method [- superceded by new alternate repair as of June 2007 -]: this ""Scotchlok 3M Special Method was previously recommended as independent tests showed that it performed acceptably.

While this repair method has been superceded by new alternate repair methods as of June 2007, we have kept this description available to aid home buyers, electricians and home inspectors who may discover or need to be able to recognize this aluminum wire repair method if it was previously used in the building.

Aluminum Wiring Repair Articles

...


Continue reading at ALUMINUM WIRING REPAIR METHODS or select a topic from closely-related articles below, or see our complete INDEX to RELATED ARTICLES below.

Or see ALUMINUM-WIRED HOMES, REDUCE THE HAZARD - PDF

Suggested citation for this web page

ALUMINUM WIRING REPAIRS NOT-RECOMMENDED at InspectApedia.com - online encyclopedia of building & environmental inspection, testing, diagnosis, repair, & problem prevention advice.

INDEX to RELATED ARTICLES: ARTICLE INDEX to ELECTRICAL INSPECTION & TESTING

Or use the SEARCH BOX found below to Ask a Question or Search InspectApedia


...

Frequently Asked Questions (FAQs)

Click to Show or Hide FAQs

Ask a Question or Search InspectApedia

Use the "Click to Show or Hide FAQs" link just above to see recently-posted questions, comments, replies, try the search box just below, or if you prefer, post a question or comment in the Comments box below and we will respond promptly.

Search the InspectApedia website

Comment Box is loading comments...

Technical Reviewers & References

Click to Show or Hide Citations & References

Publisher's Google+ Page by Daniel Friedman