How to measure municipal or well water water pressure at a building: this article describes how to measure water pressure and water flow in buildings in order to diagnose bad pressure or bad water flow.
The process of water pressure problem diagnosis and the costs of the repair are explained. We explain the difference between measuring static water pressure (nothing running) and dynamic water pressure.
We explain the difference between water pressure, and water flow rate, and we describe how to measure water flow rate in a building.
InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers, products, or services discussed at this website.
Distinguishing between static water pressure, dynamic water pressure, and water flow rate can help diagnose water problems in a building.
Here we explain these concepts and we describe how to measure water pressure and flow at a property where either municipal water supply or a private well and pump water supply is in use.
Static water pressure is the pressure shown anywhere on the water supply piping system when no plumbing fixtures are running.
Typically on a municipal water supply the static water pressure in the building will be 30-60 psi, depending only on the setting of the water pressure regulator - the regulator determines static water pressure in the building.
On a private well and pump water supply system water pressure varies between 20-40 psi or 30-50 psi depending on the equipment installed and the pump pressure control switch settings.
See WATER PRESSURE CONTROL SWITCH ADJUSTMENTS
Our photo (left) shows a simple and inexpensive home-made water pressure measuring gauge that we attached to the cold water faucet for a washing machine hookup. Building suppliers also sell water pressure gauges with the same fittings to attach the gauge to a hose or faucet hookup (see our page top photo).
To measure static water pressure, attach a pressure gauge anywhere in the building on water supply piping. Make sure that no plumbing fixtures are running, and if the building is served by a well and pump system, make sure that you have run water until the pump starts running, then turn water off.
The pressure read on the gauge with all fixtures "off" is the maximum static water pressure at the building.
Dynamic water pressure (as used in this article) is the pressure shown anywhere on the water supply piping system when one or more plumbing fixtures is drawing water. You can see that the more fixtures that are running, the lower the dynamic water pressure will be.
Technical note: Our use of this term dynamic water pressure is not the more rigorous term used in fluid dynamics.
By "dynamic water pressure" as used here here we simply mean that if you put a pressure gauge on a hose bib, laundry faucet, etc. while water is running elsewhere in the building the measured pressure is ambiguous.
Similarly, in a pump and well system, if you make a pressure measurement at any time other than at the point that the well pump cuts on or off the results can be confusing if not ambiguous.
On a municipal water supply system the dynamic water pressure and flow seen in a building will drop to a number lower than the static water pressure but will normally remain steady when you turn on one or more plumbing fixtures.
On a pump and well water supply system the dynamic water pressure and flow seen in the building will drop to a lower number than the static water pressure, and will also vary as the pump cycles on and off.
Example of variation in building water pressure:
On a pump and well water supply system when multiple plumbing fixtures are operating, the dynamic water pressure will fall to a lower number and will hover there once the quantity of water being drawn causes the pump to turn on and stay on - that is, when you are running water fast enough that the pump cannot "get ahead" of the water draw out rate.
Reader question: 3/3/2014 Rob Cunningham said: What is the water pressure per foot, I know it is 2.? per foot but I don't remember the the formula.
The pressure of water is usually stated in psi or pounds per square inch. Here are some water volume, weight & pressure basics:
The weight of a cubic foot of water: cubic foot of water weights about 62.42796 pounds (at 32 °F).
This weight can also be expresses as the pressure that would be measured at the bottom of a cubic foot of water.
At the bottom of the cube of water, each square inch of the base of a 12"x12"x12" cube of water will exert a pressure of (62.4796 / 144 sq.in) = 0.433 pounds per square inch or psi.
The number of gallons in a cubic foot: a cubic foot of water is about 7.48 U.S. gallons
Since 1 cubic foot = 12x12x12 cubic inches = 1728 cubic inches, we can calculate that one cubic foot of water contains (1728 cubic inches per cubic foot / 231 cubic inches in a gallon ) = 7.481 gallons.
1 U.S. gallon of water contains 231 cubic inches and weighs about 8.3454 pounds
SInce 1 cubic foot of water contains 7.48 gallons and 1 cubic foot of water weighs 62.4 lbs., we calculate (62.4 / 7.48 = 8.3554 lbs)
1 liter of water weighs 2.204 pounds
Since water is virtually non-compressible, its density doesn't vary by height. And we can ignore width or diamater of the water pipe or well casing too. Only the height of the column of water matters.
The pressure exerted by a vertical column of water inside of a well casing or a pipe, measured at the bottom of that column, is determined as follows:
The pressure of a column of water is about 0.434 psi per foot of column height
We calculated this psi above by dividing the weight of a cubic foot of water by the number of square inches in the bottom of the cubic foot: (62.4796 / 144 sq.in) = 0.433 pounds per square inch or psi.
That's for water at 32 °F. If warm the water up it will weigh a little less - the actual weight of water varies slightly by temperature as its density varies by temperature and possibly also by the effect of impurities in the water.
1 ft of water produces 0.433 psi of pressure at the bottom of that column [re-stating the information just above]
So the formula for the psi pressure of a column of water is
PSI of water pressure at the base of a column of water of height H in feet = H x 0.433
Examples:
No. Using the formula given just above,
PSI of water pressure at the base of a column of water of height H in feet = H x 0.434
This formula is accurate regardless of the pipe, casing, or well shape or diameter. Height matters, but not diameter.
We can calculate the water pressure at the bottom of any vertical height. But for water inside of a well or well casing, we need to be sure that we are calculating correctly by counting only the height of the column of water, not the total height that for most wells (except artesian wells) will include an air space above the top of the column of water.
The size or volume of water inside of a well or well casing when the well is at rest (not in use) and has fully recovered from any recent use (the well has re-filled from its water source) is defined as the static head.
At WELL DYNAMIC HEAD & STATIC HEAD DEFINITION we show how to calculate the volume of water in a cylinder of various diameters. Recapping:
PSI of water pressure at the base of any column of water of height H in feet = H x 0.434
Thanks to reader Gary A Sale for pointing out confusion in an earlier version of the text above. - 4 Dec 2014
1 Gallon (U.S.) = 3.785x10-3 m3 = 3.785 dm3 (liter) = 0.13368 ft3 = 4.951x10-3 yd3 = 0.8327 Imp. gal (UK)
At sea level the atmospheric pressure on earth, on the top of the water and on us = 14.7 psi. The "container size" as reader GaryASale pointed out, is not a factor. If we ignore the very small variations over our height and assume we're standing, we're being pushed-in on all sides by air at 14.7 psi. (more or less).
Let's dive down to about 33 feet below sea level in sea water. Water pressure is now 2 atmospheres or 29.4 psi (little enough to be safe from getting the bends even if we hold our breath a long time or swim around using a SCUBA tank).
Diving down just 33 feet below the surface of the ocean exposes the SCUBA diver to a second atmosphere's worth of pressure, referred to in SCUBA training as 1 ATM (since we start counting at 0 at sea level). But of course you're now under water, so you're experiencing water pressure, not air pressure, on the outside of your body.
Really? Ok so "static" water pressure is not perfectly static even if no water is running in a building. Why?
At RELIEF VALVE LEAKS we explain that when no water is being run in a building water pressure will still change depending on what the water heater is doing.
This is particularly true if your hot water is made by a water heating tank or cylinder - where a reserve of some significant number of gallons or litres of hot water is being maintained, and it's not particularly true if your hot water is made by a demand type system such as a tankless coil or a tankless water heater.
See HOT WATER PRESSURE EXPANSION RATE - for an explantion of just how much pressure increase to expect when heating water.
When no water is being run and the water heater raises the temperature of water inside the water heater or water cylinder tank, thermal expansion of the heated water will increase the water pressure in the entire system.
Purchase a water pressure gauge that includes a "telltale" - a second pressure indicating needle that is pushed upwards to show higher pressure when the acutal moving pressure-indicating needle moves. When pressure in the system falls, the telltale indicator is left at its "high pressure" mark.
The water pressure test gauge shown at left has this needed feature. This is a Watts Model 276H300 water pressrue test gauge.
"A" marks a 3/4" FPT fitting designed to permit the gauge to be installed on a hose bibb.
"B" marks the "high reading" indicator, showing the highest pressure that the gauge has seen during a test period (typically 24 hours).
"C" marks the gauge dial face giving pressure in psi. Other pressure gauges are available in common pressure readings that you may require such as Pa or pascals. The gauge's indicating meter is sitting on the pin at 0 psi in this image.
You'll also find this type of gauge on hydronic heating boilers but those gauges are not so easily adapted for monitoring a building's water system pressure. Where do you find one of these telltale water pressure gauges: at your local plumbing supplier.
These water pressure test gauges cost less than $15. USD. Ask for any of these water pressure test gauges. If you are shown a different brand or model be sure that it includes a high-pressure indicator needle so that you don't have to stay up all night in your sleeping bag watching the gauge's pressure readings as they change.
Typically the gauge will include an external re-set knob or button to allow you to re-set the maximum pointer to zero before the gauge's next use.
All of the water pressure test gauges listed below include a "Maximum Pointer" feature that will record the highest pressure reached. These are sold at your local plumbing supplier, at Grainger.com, and at other online vendors.
To monitor the operating pressure range of your system to see the effects of hot water on its pressure (and maybe to explain a leaking TPR valve), simply install a water pressure gauge on to a hose bibb that's easy to see such as at your washing machine or at an outdoor hose bibb. Leave the gauge in place for 24 hours.
Static municipal water pressure
may vary at different times of the day depending on what pressure is being delivered by the municipal supplier. In some communities municipal water pressure varies little while in others the variation can be significant.
To measure municipal water pressure in a building, use a water pressure test gauge like the home made water pressure test gauge shown above or the store-bought water pressure gauge shown at page top.
Install the water pressure gauge at a convenient outside hose bibb or to the drain connection on a water heater, or at a washing machine hot or cold water hose connection point.
If the building water pressure gauge reading is below 60 psi
leave the gauge in place for two days, checking it frequently for different pressure readings, because water pressure may vary by time of day or by the plumbing fixtures in use in the building.
An advantage of the store-bought Watts water pressure test gauge over the home-made version is that the special Watts test gauge includes a high-point red indicator needle that will record the highest water pressure sensed by the gauge during the test period, even if you did not happen to be looking at the gauge when that condition occurred.
Since your water pressure measurement itself could be inaccurate,
see WATER PRESSURE GAUGE ACCURACY where we explain causes of false high water pressure readings and false low water pressure readings.
For pressure gauge repair or replacement
see WATER TANK PRESSURE GAUGE.
If your dynamic water pressure is too low on a municipal water supply system you can boost building water pressure by installing a pressure booster pump and water tank.
See WATER PRESSURE BOOSTER PUMP.
Also see our discussion of parallel water pressure reducing valves found
at WATER PRESSURE REDUCER / REGULATOR.
If your municipal or city water pressure is always too low, perhaps below 30 psi,
see WATER PRESSURE LOSS DIAGNOSIS & REPAIR.
For more help figuring out why your municipal water pressure is too weak,
see MUNICIPAL WATER PRESSURE DIAGNOSIS and
then see MUNICIPAL WATER PRESSURE IMPROVEMENTS.
Also see WATER PRESSURE VARIATION CAUSES.
Watch out: If the building water pressure gauge reading is ever found at 80 psi or higher, you will want to install a water pressure regulator at the point where water supply enters the building.
Watts produces a Watts Governor 80™ used for this purpose, but other manufacturers also produce a wide variety of water pressure regulators.
If your building already has a water pressure gauge installed, it may be defective or it may be set too high. If your static water pressure is too high on a municipal supply,
See WATER PRESSURE REDUCER / REGULATOR.
Also see WATER PRESSURE CONTROL SWITCH ADJUSTMENTS
At HOT WATER PRESSURE EXPANSION RATE we discuss how we measure water pressure and how temperature changes affect water pressure in a closed water heater tank or heating boiler.
Static well water pressure depends on the setting of the pump controls. You can try reading the water pressure shown on the pressure gauge that is usually installed at the pressure tank or near the pump pressure control switch.
Watch out: dirt or debris in the small diameter pressure switch mounting pipe at your water pressure tank, or a failing pressure gauge itself can give inaccurate water pressure readings.
Particularly if your water pressure gauge reading does not rise and fall smoothly as the water pump turns on and off, you may want to replace the gauge and/or make an independent water pressure reading using the water pressure test gauge we have described just above.
Since your water pressure measurement itself could be inaccurate,
see WATER PRESSURE GAUGE ACCURACY where we explain causes of false high water pressure readings and false low water pressure readings.
If your well water pressure is always too low, perhaps below 30 psi,
see WATER PRESSURE LOSS DIAGNOSIS & REPAIR.
Also
see WATER PRESSURE VARIATION CAUSES.
If your dynamic well water pressure is too low on a private pump and well system you may be able to boost water pressure by adjusting the pump pressure control switch.
See WATER PRESSURE CONTROL SWITCH ADJUSTMENTS
Also, because poor water flow rate from a private well system is often due to a limitation of the well's flow rate,
see WATER PRESSURE LOSS DIAGNOSIS & REPAIR.
Watch out: If your well water pressure is too high,
see WATER PUMP CONTROLS & SWITCHES and see WATER TANK SAFETY.
This topic has moved to WATER FLOW RATE MEASUREMENT - live link given just below.
Watch out: measuring "flow rate" at any faucet or fixture served by a well pump system will be inaccurate and will reflect pump capacity, piping restrictions, fixture restrictions, and even actual well flow rate variations where pump protection tailpieces or similar devices are installed.
Measuring flow rate at a fixture does not measure the well's true flue rate.
...
Below you will find questions and answers previously posted on this page at its page bottom reader comment box.
On 2020-07-03 by RICHARD DALE WATTS
I live in oildale ca.And family owns watts valve world wide.
As a child I would want water after grade school, standard jr. High short for standard oil
.None of the water works up the road for miles.
There was one cold water place next to a coke mec. At 63 its still that way. I hope to change that with help.
On 2020-04-17 by Pressure Variation - Why would the high reading ever approach ~ 100 PSI if the regulator is doing it's job?
Use Watts Pressure Measurement - static is ~ 40 PSI. After 2 days of monitoring the high reading is ~ 100 PSI.There is a pressure regulator installed correctly right behind the gate valve from the supply (from the street). I replaced the regulator ~ 3 yrs ago. Why would the high reading ever approach ~ 100 PSI if the regulator is doing it's job?
On 2020-04-17 - by (mod) -
Press
Where are we measuring water pressure, and on what kind of system with what equipment?
Municipal water supply
vs
Well water pump and tank supply
Heating boiler
Other equipment?
I am guessing we're talking about municipal water supply, with a pressure regulator at the incoming supply, and no water pressure tank.
In that case if you're seeing water pressure in the building above what you had when you first installed and adjusted the water pressure regulator, then the regulator is not working and probably needs replacement.
Note that some pressure regulators will malfunction if their internal parts become debris clogged, so if that's your case you might first try cleaning yours.
Keep me posted. Post a photo.
...
Continue reading at WATER PRESSURE VARIATION CAUSES or select a topic from the closely-related articles below, or see the complete ARTICLE INDEX.
Or see WATER PRESSURE MEASUREMENT FAQs questions and answers posted originally at this article
Or see these
WATER PRESSURE MEASUREMENT at InspectApedia.com - online encyclopedia of building & environmental inspection, testing, diagnosis, repair, & problem prevention advice.
Or see this
Or use the SEARCH BOX found below to Ask a Question or Search InspectApedia
Try the search box just below, or if you prefer, post a question or comment in the Comments box below and we will respond promptly.
Search the InspectApedia website
Note: appearance of your Comment below may be delayed: if your comment contains an image, photograph, web link, or text that looks to the software as if it might be a web link, your posting will appear after it has been approved by a moderator. Apologies for the delay.
Only one image can be added per comment but you can post as many comments, and therefore images, as you like.
You will not receive a notification when a response to your question has been posted.
Please bookmark this page to make it easy for you to check back for our response.
Our Comment Box is provided by Countable Web Productions countable.ca
In addition to any citations in the article above, a full list is available on request.