Aerobic septic system alarmn installation, alarm codes, & alarm problem diagnosis:
How to fix an aerobic septic system alarm that won't shut off. Checklist for aerobic septic alarm diagnosis & repair.
This article series discusses problems that occur in aerobic septic systems, also known as aeration septic systems or fine-bubble septic aerators.
InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers, products, or services discussed at this website.
- Daniel Friedman, Publisher/Editor/Author - See WHO ARE WE?
Aerobic Treatment Unit Alarms
Turn off the Aerobic Septic Alarm
Aerobic (and other) septic alarms sound to warn of an operating problem with the system that could risk a sewage backup into the building.
If your aerobic septic alarm is visual-only you will see a flashing or solid-on red light on the alarm box or cover over your septic system or pump.
Common Generic Aerobic Septic Alarms
Here are some common septic alarm indicators and what they mean and what to do about each condition. Further below on this page we include septic alarm brand and model instructions and alarm or alarm light flash codes and their meaning.
Yellow light septic alarm: aeration problem.
Red light septic alarm: high water in the septic tank = HWA - high water alarm. Turn off water, turn off the alarm, call your septic contractor. (Below we give a few things to check first.)
Audible septic alarm: buzz, shriek or whistle: go look at the alarm lights. Don't panic.
If your alarm provides a bell or buzz you will, of course, hear it. On the control panel there is usually a COMP switch that yoyu can set to "mute" to stop the alarm sound. More diagnostic and repair steps are given below in enough detail that you may be able to fix the aerobic system trouble yourself.
If there's no COMP switch, look for a lit-up button or red "off" button on the alarm box. This switch will stop the alarm from sounding.
On most septic alarm systems the warning light will remain illuminated until the pump problem has been repaired.
Audible septic alarms are usually installed in a building to alert occupants because the red-light alarm at the septic system may not be readily visible.
Every septic maintenance company, manual, and guide we reviewed says don't panic when your septic alarm sounds - it's usually not an emergency.
Should You Wait Before Calling your Septic Company for Repair?
Some septic repair companies have suggested that you should
Turn off the alarm. For example on a Norweco Service Pro you can try pressing the blue RESET button.
Turn off any water runnning into the tank and let the efflent level in the tank drop, then turn the alarm back on
Let your aerobic effluent-dispersal spray system cycle through its sequence once or twice.
This may make sense if your aerobic spray system has not run for a time AND if your water usage was unsually high - for example during an event at which you had many visitors using the baths or toilets in your home.
Watch out: if your drains are slow, gurgling, or backing up repair is more urgent as you do not want a sewage backup into the home.
As a temporary, emergency measure, if your building's sewer line includes an outside cleanout access port, opening that port can permit sewage to spill onto the lawn rather than backing up into the building.
While it is never proper nor code-legal to discharge sewage to the surface, in an emergency, to protect a buiding, that's a defensible step. In that case you certainly need to call for emergendy repair.
In any event unless you find something trivial, I would call your septic maintenance company to schedule a service call, even if it's not an emergency.
Aerobic components to check in response to an alarm or red light
Illustration: Alderon's Versa'larm™ I/O that can be used to monitor aerobic septic system effluluent levels & pump operation. Below we give information about this pump and include company contact information.
[Click to enlarge any image]
Let's start with the brand and model of your aerobic system - if we know that we can find, if you don't already have one, the owners' manual that will de-code warning lights on the system.
A standard list of aerobic components to check in response to an alarm or red light includes some of the items you've already confirmed, and includes some items or features that may not be present on your aerobic septic system (that's why we need to know what system is installed).
Typicallly an aerobic septic system includes several major components & controls that you will need to check, including an air compressor for the aerator, an effluent pump for effluent disposal, and the controls that operate those pumps.
You'll also check for kinked, leaking, or crimped tubing or piping, and for effluent treatment equipment or its screens or filters that are not working or are clogged.
Homeowner Steps for Aerobic Alarm Diagnosis
Watch out: do not attempt to open, lean over, or enter a septic tank or effluent treatment chamber unless you are trained and equipped to do so. You can be overcome by methane gas and septic fumes; falling into a septic tank is often fatal.
Typically aerobic septic service companies consider only two steps safe for a homeowner to perform:
Check that the system has electrical power
Check that the chlorinator is not blocked
Here are diagnostic steps that are usually followed by an aerobic septic service company:
Aerobic Service Company Typical Septic Alarm Checklist
Check the air compressor or air pump
that supplies pressurized air to the aerator: check that the air pump has electrical power and is running. You'll feel it buzzing or vibrating and you might hear it.
Check for tripped circuit breakers, look for disconnected wires.
Watch out: as reader David reported in 2014, the aerator pump may be running but not actually pumping air. His pump had a bad diaphraghm. Other pump damage such as a damaged or broken impeller or worn bearings can also cause inadequate air pressure in the system.
Check the air pressure sensing tube
that tells the alarm that the system has air pressure: be sure that the tube is not kinked, clogged, blocked
Check the air line between the air compressor and the tank aerator
to be sure the line is intact, connected, not kinked, not leaking (air bubbles coming out of a hole or crack int he tubing).
Check for a clogged diffuser in the septic tank.
A clogged diffuser can block air flow and clog the whole system.
Check the level of wastewater in the septic treatment tank:
is wastewater above high water level line - that will set off a high septic waste alarm.
If there is high water in the effluent tank check the next items:
Check the effluent sprinkler pump control float.
Rising wastewater should lift the float that in turn operates a switch that turns on the pump.
If the float is stuck by debris, obstructions or anything in the pumping chamber the sewage grinder pump cannot turn on and off as it should.
Check the aerobic septic effluent / sprinkler pump timer or photocell
to be sure that these are working to turn on the sprinkler pump
Check the sprinkler pump:
If your aerobic system uses sprinklers to distribute effluent, confirm that the sprinkler pump has electrical power and is working. As we noted for the air pump, a clog, damaged impeller, failed bearing, or a failed pump control can leave the pump not working at all or not pumping adequately.
If the sprinkler pump runs but the effluent distribution sprinklers are not working when they should, then continue to check these items:
Check the pump for a clogged inlet screen
protecting the effluent pump
Check for a clogged chlorinator
treatment system for the septic effluent
Check for clogged aerobic sprinkler spray heads
not passing effluent. A spray head may be jammed or broken entirely or it may be debris clogged. A filter or screen at the inlet or base of sprinklers can become clogged and may simply need cleaning or replacement.
Check for broken or clogged effluent distribution piping
between the effluent pump and the aerobic effluent sprinkler - spray heads
For sewage pumps and septic effluluent pump alarms on other types of septic systems
Our video demonstrates the operation of a septic tank pump system alarm.
InspectAPedia is an independent publisher of building, environmental, and forensic inspection, diagnosis, and repair information provided free to the public - we have no business nor financial connection with any manufacturer or service provider discussed at our website. We do not sell products nor services.
Watch out: As with all electrical equipment these septic system controllers and alarms must be installed by a qualified technician and in accordance with model and local electrical and plumbing codes. Failure to properly install and ground electrical equipment risks shock, fire, injury or death.
Aero-Stream, septic tank alarm kits, Aero-Stream®, LLC
W300N7706 Christine Lane
Hartland, WI 53029
USA Tel: (877) 254-7093 TOLL FREE
(262) 538-4000 Email: info@aero-stream.com, Website: https://www.aero-stream.com/pasc.html
Excerpts:
The Septic Tank Alarm Kit integrates into Aero-Stream®’s Remediator® and Pro Line™ systems and alerts owner when the Remediator® or Pro Line™ Aerobic Generator requires a tune-up or there is an issue with the air line or diffuser.
The Septic Tank Alarm Kit – high water alerts the owner when a high water condition exists in the septic tank before a backup occurs in the dwelling, such as when an effluent pump fails or a filter needs servicing.
Alderon I/O Versa'Larm™ INSTRUCTIONS [PDF] used to monitor effluent pumping chamber, holding tank, sump pump basin,water tank, or septic tank. Retrieved 2018/03/13 original source http://www.alderonind.com/products/7004.html
Alderon Industries, Inc.
P.O. Box 827
151 16th St S
Hawley, MN 56549 USA, Tel: 218-483-3034 Website: http://www.alderonind.com/
Excerpt:
The Versa’larm I/O is powered by 120 VAC, “hard wired”. When a float switch “closes” the buzzer and beacon will
turn “on”.
Pressing the “Silence” button deactivates the buzzer and when the alarm is remedied, the system automatically
resets itself. The system can be tested be pressing the “Test” switch, when pressing the switch, the buzzer
should annunciate and the beacon should illuminate.
Alderon provides flood detection systems, float switches, liquid level alarms, and pump control panels.
The Versa’larm 4X is powered by 120 VAC, “hard wired”. When power is applied, the green “Power” indicator
light (located externally) will illuminate. When a float switch “closes” the buzzer and beacon will turn “on”.
Pressing the “Silence” button deactivates the buzzer and the optional auxiliary contacts. When the alarm is
remedied, the system automatically resets itself.
The system can be tested be pressing the “Test” switch, when
pressing the switch, the buzzer should annunciate and the beacon should illuminate. The auxiliary contacts are
activated when an alarm condition occurs. The single pole double throw contacts can switch a maximum of 5
amps at 120 VAC.
Alderon Versa'larm™ INSTRUCTIONS [PDF],
retrieved 2018/03/13, original source: http://www.alderonind.com/content/2016/ii/Versalarm1ZoneInstallationInstructionsWeb.pdf
Excerpt: A standard Versa’larm™ - Tank Alarm includes an alarm panel and a Unimax™ mechanical control switch. Receive immediate notification of threatening water levels by connecting
an Auto Dialer to the Versa’larm
Above: an AquaAire aerobic septic system as installed, discussed in reader Q&A and for which a user's manual is given below.
AquaAire 500-SERIES AEROBIC SEPTIC SYSTEM MANUAL [PDF] Ecological Tanks, Inc. - Manufacturers of Wastewater Treatment Systems
2247 Hwy 151 North, Downsville, LA 71234 USA
Tel: (318) 644-0397 Website: https://etiaquasafe.com/ retrieved 2020/01/25 original source: https://etiaquasafe.com/wp-content/uploads/sites/28/2019/02/AS500-1500_Series_OwnersManual.pdf?x48794
Excerpt:
If an [Aqua Aire aerobic septic system] alarm condition is observed, it is an indication of malfunction.
First check the electrical circuit providing power to the system to insure the circuit is closed.
Check the aerator compressor to be sure it is operating.
Check for over heating, excessive vibrations and unusual noises.
If an aerator compressor failure is observed, call your service provider for service.
After a power outage, an alarm condition may exist. Should an alarm remain on for more than thirty (30) minutes after power is restored, you should call your local service provider to report the alarm.
Australia DHA, AEROBIC WASTEWATER TREATMENT MAINTENANCE MANUAL [PDF], Department for Health and Ageing,
Government of South Australia. Retrieved 2018/03/13, original source: https://yorke.sa.gov.au/content/uploads/Maintenance-of-Aerobic-Wastewater-Treatment-Systems.pdf
Excerpt: All aerobic wastewater treatment systems must be provided with an alarm system to alert occupants to an
electrical or mechanical malfunction.
The alarm must have an audible and
visual (indicator light) component with
muting for the audible alarm.
The fault indicators should be located
inside the premises, preferably within
the kitchen or laundry.
CLEARSTREAM AEROBIC SEPTIC SYSTEM OWNERS MANUAL [PDF] Models 500NS - 1500N Owners Manual, Parts List, Flow Diagram, Installation Instructions, Design Drawings, Specifications, Service Policy, Warranty, Clearstream Systems, retrieved 2018/03/13, original source: https://www.clearstreamsystems.com/wp-content/uploads/2017/10/N_Book.pdf
CSI Controls, MINUTEMAN LEVEL ALERT MANUAL [PDF], CSI provides a variety of tan k alarms including a pedestal mounted plugger control panel with a high water alarm for aerobic septic systems.
CSI Controls, Tel: 1-800-363-5842, Website: www.csicontrols.com
Excerpt: Using the Test - Silence - Normal toggle switch on the outside of the enclosure
periodically test unit to make sure the unit is working properly.
The test mode will test
the audible and visual alarms, the silence mode with silence the audible alarm during an
alarm condition, and the normal mode allows the system to operate using the alarm and
control floats.
Above and below: the Little Giant 303HWXT Indoor/Outdoor High Water Alarm (115V model) from Franklin Electric, cited below.
Little Giant TANK ALERT XT 303 HWXT SEPTIC ALARM SYSTEM MANUAL [PDF] (2007) Franklin Electric, P.O. Box 12010
Oklahoma City, OK 73157-2010
Phone: 1.800.701.7894
Fax: 1.800.678.7867
www.LittleGiantPump.com
Norweco Aerobic Septic Alarm, Control Panel, Pumps - Contact: Norwalk Wastewater Equipment Company, Inc., 220 Republic Street Norwalk, Ohio 44857-1156 USA, 419-668-4471 Fax:419-663-5440. Website: http://www.norweco.com/
Excerpt: The Service Pro control center with MCD technology shall be UL Listed and provide Monitoring, Compliance and Diagnostic functions for the Singulair wastewater treatment plant and auxiliary equipment using a microprocessor based platform.
The microprocessor shall contain nonvolatile memory to prevent loss of programming in the event of a power failure. When used with the Singulair Model 960 system, the programmed run cycle shall not permit the aerator to be “off” for more than thirty minutes per hour.
When used with the Singulair Model TNT system, the programmed run cycle for the aerator shall be sixty minutes “on” and sixty minutes “off.” The control center shall be housed in a NEMA rated electrical enclosure designed specifically for outdoor use.
Control centers that do not include integral telemetry equipment require multiple enclosures with interconnecting wiring and shall not be considered for this application.
NORWECO HYDRO-KINETIC GREEN Wastewater Treatment System with Service Pro Control Center OWNERS MANUAL [PDF] (at Norweco), local backup copy saved as Nowweco-HydroKinetic-Green.pdf
Excerpt: Developed to serve homes and small businesses outside of city sewers, the Hydro-Kinetic Green system uses the extended aeration process to treat wastewater and features innovative nitrification-denitrification technology.
Above, the Norweco Hydro Kinetic wastewater treatment system, excerpted from the Hydro-Kinetic 600 manual cited above.
Oklahoma DEQ, AEROBIC SEWAGE TREATMENT SYSTEM MANUAL [PDF], Oklahoma Department of Environmental Quality, P.O. Box 1677 Oklahoma City, OK 73101-1677 USA Tel:(405) retrieved 2018/03/13, original source: http://www.deq.state.ok.us/eclsnew/Fact%20Sheets%20ECLS/System%20Fact%20Sheets/Aerobic.pdf
Excerpt:
Every aerobic treatment system must have an alarm (visible, audible, or both) that
alerts the owner/operator of a system failure. This lets the homeowner know if the
aerobic treatment unit or pump tank becomes too full or if there is a malfunction
with the system.
The control box or alarm box should be kept in a place where the
owner/operator can be easily alerted.
If an alarm is activated, call your
maintenance provider or a professional.
Orenco, VeriComm CONTROL PANEL VCOM-S1-RO MANUAL [PDF], (2002) Orenco Systems Incorporated, 814 Airway Ave., Sutherlin, OR 97479-9012 USA, Tel: 541-459-4449
Installation instructions, wiring diagrams, etc. for septic system control and alarm equipment.
Excerpts: This document contains general installation instructions for VeriComm® control panels. Consult all
supplemental documents (Control Panel Wiring Diagram, Float Arrangement Diagram, etc.) before
installation.
VCOMS-S RO Panel overview: The VCOM-S RO telemetry-enabled panel is
used for remote monitoring and control of ondemand
simplex pumping operations.
Basic control logic manages the day-to-day
functionality of the control panel.
As the [septic] tank
fills with effluent, floats activate a discharge
pump. A pump cycle starts when the top float is
raised by effluent, and ends when the middle
float drops.
Fault conditions are automatically reported to
the VeriComm Monitoring System and not
locally at the panel, making the system virtually
invisible to the homeowner.
However, if fault
conditions are not responded to, or the system
cannot communicate with the VeriComm
Monitoring System, then local alarms may be
activated.
To silence local alarms, press the “Push-To-
Silence” button until the audible alarm stops.
Note regarding a normal thumping sound: If the panel contains motor contactors, a thumping sound can be heard each time the pump is started or stopped. Therefore, these panels should not be mounted on an exterior wall unless it is in a location away from living areas, such as on a garage wall.
Illustration: Norweco's Service Pro® Control Center used iwth Singulair® septic systems. On 2019-04-14 by (mod) -
Anon said:
Chris:
Check for an outlet blockage.
Moderator said:
For an open motor or under current condition, the
alarm on a Norweco Singular control center will display two short flashes followed by a pause.
I'm not sure about the 2-3 flash you describe.
You don't describe which septic and control models you have from Norweco except for the Norweco Singulair alarm.
If you have the MCD or TNT model of Norweco Singular system see the appropriate "Quick Start Guide" below for help in responding to an alarm. Else contact Norweco at the location I'll give below.
Here are some Norwco septic system manuals that may help you.
Norweco SINGULAIR® BIO-KINETIC 960 & TNT OWNERS MANUAL [PDF] Norweco
220 Republic St., Norwalk, OH 44857-1156
USA, Tel (419) 668-4471
Fax (419) 663-5440
Website: www.norweco.com retrieved 2020/05/09 original source: https://www.norweco.com/wp-content/uploads/2018/10/sing_om.pdf
Excerpt: The Service Pro control center combines integrated circuitry, advanced telemetry and web-based data acquisition for the remote management of any wastewater treatment system.
Service Pro is the only control center that employs the revolutionary Monitoring, Compliance and Diagnostic (MCD) Technology.
Designed to automatically operate the Singulair treatment plant, Service Pro also monitors the operation of the entire onsite system and provides verification of compliance with installation permit requirements.
Service Pro MCD control centers are equipped with on-board diagnostics that verify when service work is performed and when maintenance is required.
Noreweco SERVICE PRO® CONTROL CENTER SPECIFICATIONS [PDF] retrieved 2020/05/09 original source: https://www.norweco.com/wp-content/uploads/2018/10/Service-Pro-Specifications.pdf
Excerpt: The Service Pro control center shall monitor the operation of the
Singulair system and up to three auxiliary treatment components.
The performance of the Singulair aerator shall be constantly monitored
to detect any aerator over current, aerator under current or open motor
condition.
If any one of these conditions is detected, power to the
aerator shall be interrupted, a diagnostic sequence shall begin and
the visual alarm shall activate. After a factory programmed recovery
interval, an automatic restart attempt shall be initiated.
If normal
aerator operation does not resume during 24 programmed recovery
and restart cycles, the audible alarm shall activate and, if the telemetry
system has been enabled, the control center shall report the specific
condition to the Service Pro monitoring center.
In the event that any
of the auxiliary inputs detect an operational problem, the audible and
visual alarms shall immediately activate and, if the telemetry system
has been enabled, the control center shall report the specific alarm
condition to the monitoring center.
The distributor shall be
automatically notified by the Service Pro monitoring center of the
specific alarm condition using phone, fax or email.
Norweco
220 REPUBLIC STREET
NORWALK, OHIO, USA 44857-1156
TELEPHONE (419) 668-4471
FAX (419) 663-5440
www.norweco.com
Why is our Norweco Service Pro Model 801P red alarm light on
What’s the problem ? On 2020-08-31 by Helene-
by (mod)
- ServicePro 801P septic alarm is a Norweco product. The Norweco alarm continues until the cause for it is fixed.
Helene, Your ServicePro 801P septic alarm is a Norweco product.
The answer to what the red alarm light "on" means is, as Mark Cramer says, "... it depends" - in this case on the light flash pattern, as we will explain here.
First: try pressing the blue reset button once to see if that clears the alarm.
If there's an error condition, the light signal will continue until the problem is corrected.
But you will see in our Norweco alarm light signal table below that the light may flash for "non-error" conditions such as "home phone line in use".
"In the event of an alarm condition from the Singulair system, and up to three separate auxiliary treatment components, the registered service provider is automatically notified.
Notification of the alarm condition continues automatically every 48 hours until the alarm condition is corrected. "
In the Norweco manual we cite below we find this table that explains the Norweco MCD type alarm middle center light (the red Alarm llight) codes:
Norweco Service Pro Septic Alarm Codes
Alarm Light Flash Pattern
Condition
5 Short
Successful Commissioning
10 Short
Alarm test visit start
Alarm test vist end
1 Short 1 Long, pause 3 seconds
Then Repeat
Phone network cable not secure
2 Short, 1 Long, pause 3 seconds
Then Repeat
Phone line in use in home
3 Short, 1 Long, pause 3 seconds
Then Repeat
Number called is busy
4 Short, 1 Long, pause 3 seconds
Then Repeat
Remote monitoring error
Phone service termination
5 Short, 1 Long, pause 3 seconds
Then Repeat
Panel communication error
Red light stays on solid, continuously
Control failure
2 Short, pause 3 seconds
Then Repeat
Aerator under-current
2 Short, pause 3 seconds
Then Repeat
Aerator motor open
Flash at even intervals, continuously
until serviced
Environment One Aqua Safe® aerobic alarm is going off, Why & what do we do?
Thank God you are here!
We have an Aqua safe system. Had it cleaned out yesterday and now our aqua safe alarm is going off.
I was told this is normal and should go off in a few days
I have been trying to research this.
Could this be due to lack of liquid in the tank causing low pressure?
Do we need to fill it with water?
This has never happened before.
Photo of an Aqua-Aire aerobic septic system as installed, showing the control box location. Photo courtesy of AquaAire cited above. - 2020/01/25 Joyce
Reply:
Joyce
First let's silence the alarm; there should be a switch or button on the control box that will do that. (Post a photo of your control box and I may be able to comment further).
An septic alarm might sound for up to 30 minutes after power has been off to the system, but if the alarm is sounding longer than that more action is needed.
If you don't have an owners's manual for your AquaSafe aerobic system, you might give a call to
Ecological Tanks, Inc. - Manufacturers of Wastewater Treatment Systems 2247 Hwy 151 North, Downsville, LA 71234 USA
Tel: (318) 644-0397 (Mon-Fri 8AM - 5 PM) though you can also contact the company by email aquasafe@bayou.com
But you shouldn't need to fill your system with water; normal use of plumbing in the home should be all that's needed.
I rather suspect there's a stuck control or float or a leak in the air pump system.
On your AquaSafe the two causes of an alarm to sound are HIGH water (that would mean a pump isn't working) or an aerator pump failure - check that your aerator pump is running.
The company tells us
What to do if the Aqua Aire Septic Alarm Sounds
" If an alarm condition is observed, it is an indication of malfunction.
First check the electrical circuit providing power to the system to insure the circuit is closed.
Check the aerator compressor to be sure it is operating.
Check for over heating, excessive vibrations and unusual noises.
If an aerator compressor failure is observed, call your service provider for service.
After a power outage, an alarm condition may exist. Should an alarm remain on for more than thirty (30) minutes after power is restored, you should call your local service provider to report the alarm."
I'm looking for more information to see what I can add.
If your Aqua-Safe aerobic is in the AS-500-1500 series then you can download this AquaAire septic system owners' manual
Red alarm light at septic tank stays on even though tanks were cleaned and the air pump runs.
I had all four tanks cleaned and a new air pump installed. Once the tanks got full the main pump comes on but the red light stays on. I can hear the air pump running.- 2020-05-07 by lafondmike634@gmail.com
by (mod) -
If pressing the alarm reset button does not stop the alarm signal, then:
It may not be enough with the pump is running.
Check the effluent level in the tank. If that's not dropping there's something wrong with the pumping system such as a bad pump impeller or a kinked or blocked pump line or a jammed efflent level float (a common problem.)
Aerobic septic alarm and light stayed on - here's how it was repaired
My alarm came on randomly. Turned the buzzer off and the light is still on. Had the septic company come to take a look at it. They said it was something in the control box and that they needed to replace the whole box for $1100. I called bs. So I looked at the schematic and thought it might be the air switch.
I unplugged the air switch and it had a black/charred spade connector. So I replaced the air switch bc I thought I was fried. Didn't fix the issue. Think it might be the air pump. It doesn't seem to be running. No loose connections to it. Could it have gotten fried in a thunderstorm? Any other ideas? - On 2019-04-30 by Matt
by (mod)
- septic alarm came on randomly - what to check
Matt
Well you certainly get my Applause for thinking for yourself and not just throwing money at this problem based on what you suggest was a superficial and careless diagnosis by someone who was themselves perhaps being a bit hasty.
Now with all of that griping aside, you found at least the symptom of a problem in the burned connector.
Typically when a connector chars or Burns it's from an overcurrent which in turn could be caused by a short in the wiring or by a seized pump motor. I would inspect the wiring or tested, and if the wiring is intact then check the pump control switch and then pursue the pump motor.
On by Matt
Thanks for the input. I will check the power to the pump and the switch today when I get home, and go from there.
by Matt - problem was the air pump
Turns out the compressor is not working. Needs a rebuild kit. I have a Hiblow HP80-018. The safety screw inside it broke, which means the diaphragm/s have ruptured. Ordered the rebuild kit for it. Hopefully that is the only remaining issue.
by Matt - Compressor rebuild kit worked!
Compressor rebuild kit worked! $85 and about half an hour to install it. Running perfectly now.
Answer by (mod) -
Thank you for the follow-up - that will help other readers
Air pump off on Hoot Aerobic Septic, but Control Panel Light is Green
I have a hoot aerobic system. The air pump is not running but the system control panel still has a green light and says system is fine. Isn't the pump supposed to always be running and if so why no alarm? - On 2019-10-24 by Michael
by (mod) - DId your Hoot Aerobic septic pump turn back on?
Michael
DId your Hoot Aerobic septic pump turn back on? Some pump systems do not run 24/7 but rather are on a timer while other designs keep the pump on all the time.
If the aerobic pump never turns on then the sensor reporting its operation is defective and it's also time to diagnose and/or replace the pump.
Or see AEROBIC SEPTIC ALARM SYSTEM FAQs - questions & answers about troubleshooting alarms and warning lights on aerobic septic system controls, pumps, etc. - posted originaly on this page.
Or use the SEARCH BOX found below to Ask a Question or Search InspectApedia
Ask a Question or Search InspectApedia
Questions & answers or comments about problems with the operation of aerobic septic systems
Try the search box just below, or if you prefer, post a question or comment in the Comments box below and we will respond promptly.
Search the InspectApedia website
Note: appearance of your Comment below may be delayed:if your comment contains an image, photograph, web link, or text that looks to the software as if it might be a web link, your posting will appear after it has been approved by a moderator. Apologies for the delay.
Only one image can be added per comment but you can post as many comments, and therefore images, as you like.
You will not receive a notification when a response to your question has been posted. Please bookmark this page to make it easy for you to check back for our response.
IF above you see "Comment Form is loading comments..." then COMMENT BOX - countable.ca / bawkbox.com IS NOT WORKING.
In any case you are welcome to send an email directly to us at InspectApedia.com ateditor@inspectApedia.com
We'll reply to you directly. Please help us help you by noting, in your email, the URL of the InspectApedia page where you wanted to comment.
Citations & References
In addition to any citations in the article above, a full list is available on request.
Document Sources used for this web page include but are not limited to: Agricultural Fact Sheet #SW-161 "Septic Tank Pumping," by Paul D. Robillard and
Kelli S. Martin. Penn State College of Agriculture - Cooperative Extension, edited and annotated by
Dan Friedman (Thanks: to Bob Mackey for proofreading the original source material.)
Advanced Onsite Wastewater Systems Technologies, Anish R. Jantrania, Mark A. Gross. Anish Jantrania, Ph.D., P.E., M.B.A., is a Consulting Engineer, in Mechanicsville VA, 804-550-0389 (2006). Outstanding technical reference especially on alternative septic system design alternatives. Written for designers and engineers, this book is not at all easy going for homeowners but is a text I recommend for professionals--DF.
US EPA ONSITE WASTEWATER TREATMENT SYSTEMS MANUAL [online copy, free] Top Reference: US EPA's Design Manual for Onsite Wastewater Treatment and Disposal, 1980, available from the US EPA, the US GPO Superintendent of Documents (Pueblo CO), and from the National Small Flows Clearinghouse. Original source http://www.epa.gov/ORD/NRMRL/Pubs/625R00008/625R00008.htm Onsite wastewater treatment and disposal systems,
Richard J Otis, published by the US EPA. (1980)
"International Private Sewage Disposal Code," 1995, BOCA-708-799-2300, ICBO-310-699-0541, SBCCI 205-591-1853, available from those code associations.
"Manual of Policy, Procedures, and Guidelines for Onsite Sewage Systems," Ontario Reg. 374/81, Part VII of the Environmental
Protection Act (Canada), ISBN 0-7743-7303-2, Ministry of the Environment,135 St. Clair Ave. West, Toronto Ontario M4V 1P5 Canada $24. CDN.
Onsite Wastewater Treatment Systems, Bennette D. Burks, Mary Margaret Minnis, Hogarth House 1994 - one of the best septic system books around, suffering a bit from small fonts and a weak index.
The NSFC Products List has an excellent list of design manuals/modules National Small Flows Clearinghouse (NSFC) now (2019/12/13) hosted at http://www.nesc.wvu.edu/ Tel: 304-293-4191 e-mail info@mail.nesc.wvu.edu.
In addition to citations & references found in this article, see the research citations given at the end of the related articles found at our suggested
Carson, Dunlop & Associates Ltd., 120 Carlton Street Suite 407, Toronto ON M5A 4K2. Tel: (416) 964-9415 1-800-268-7070 Email: info@carsondunlop.com. Alan Carson is a past president of ASHI, the American Society of Home Inspectors.
Carson Dunlop Associates provides extensive home inspection education and report writing material. In gratitude we provide links to tsome Carson Dunlop Associates products and services.