Roof Drip Edge Flashing Installation FAQs
Roof drip edge flashing installation questions & answers.
This article series discusses roofing drip edge installation specifications and details that prevent leaks and damage to buildings.
Page top photo: rain pouring off of this metal roof is directed out, away from the fascia board by the roof's drip-edge, thus reducing the risk of rot or other fascia damage.
InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers, products, or services discussed at this website.
- Daniel Friedman, Publisher/Editor/Author - See WHO ARE WE?
These questions and answers about the right way to install roof drip edge flashing were posted originally
at DRIP EDGE FLASHING for ROOFS - be sure to review the details given there.
Our photo at page top shows roof shingles dripping behind a loose gutter and no visible drip edge flashing.
[Click to enlarge any image]
Can this just be covered or do shingles have to be torn off? thanks - On 2021-11-24 by Christine claxton
Answer by Inspectapedia Com Moderator (mod) - no need to remove shingles to repair flashing
@Christine claxton,
You certainly should not have to tear off roof shingles in order to either add a bit of additional flashing at the roof corner and / or insert a color matched sealant into those openings so the water doesn't leak behind the drip edge nor into the fascia.by cora
Thank you for the advice. The problem is that if a gap exists because of the way the roof decking and fascia board were installed, what can the roofer do to address this when putting on the new roof
Unless the wood has to be replaced (and I hope that not much needs to be as it was all replaced 22 years ago with the last roof replacement and lumber is so expensive now!) what can be done?
Warning by inspectapedia.com.moderator (mod) - concern for using drip edge to keep squirrels out of roof
@cora,
Drip edge is not intended to be a rodent shield but rather to direct roof runoff into the gutter rather than down the fascia board.
But your roof and fascia and soffit might have been built with gaps that enticed squirrels into your attic.
And some roofs, without a roof overhang or soffit, use special venting products to admit air into the lower roof edge as part of the attic or under-roof venting system.
Discuss these with the roofer to be sure that no rodent-openings are left when the new roof is installed.
We need to take care of here to avoid the trap of micromanaging.
If you over-specify to the roofer she/he will do exactly what you say and then disclaim any responsibility for any unsatisfying result.
So the right thing to do is to name the problem and ask the roofer for suggestions for solving it.
If I were doing such a roof I expect that it would be trivial to install some flashing, wrapping any openings, before I put the drip edge on.
I certainly would not be relying on the drip edge to do a job for which it's not designed.
But we're going to leave that to your roofer to solve.
Let me know what your roofer suggests and attach a photo or two, you can attach one photo to each comment.by cora
Thank you for the response. Years ago my attic was invaded by flying squirrels. I had no drip edge so it was put on by the pest control company. Idk how thick the flashing (that is what they called it) is.
I am going to be getting a new roof and the roofer said he will be removing the drip edge and putting on new. (I didnt quite understand his explanation for wanting to remove it, but it seems that is just what he does.) I don't want to exchange something thicker for something thin and weak which may be bent and then allow for an animal to get behind.
by cora What's the right thickness of aluminum drip edge?
How thick do you recommended aluminum drip edge be?
Answer by inspectapedia.com.moderator (mod) - How thick do you recommended aluminum drip edge be?
@cora,
All of the drip edge dimensions are given on the page DRIP EDGE FLASHING for ROOFS Please take a look.by mak.church (mod) - thickness of roof drip edge material
@cora,
OPINION:
Thank you for the added detail and the clarification. You're, of course, quite right that there is some variation in the thickness of the metal used for drip edge and other flashings.It will be obvious to any of us that thicker metal is more resistant to being bent. In our view, and having install drip edge flashing on buildings for over 40 years, those variations in thickness in residential application at least are not functional.
The thinner metals are of course a little easier to nail in place, but the events that bends drip edge such as falling tree limbs will bend any drip edge of any thickness.
Our view is that it is the width of the drip edge and both horizontal and vertical directions that may make a difference in some applications. That's particularly true on lower slope roofs, or where the roof decking doesn't come all the way to the outer edge of the fascia board and we need a wider drip edge flange in order to be able to nail the drip edge to the deck. That's why it's not thickness.by cora
@mak.church,
Thank u for responding. I am not referring to width. I do see some brands (for example Quality Edge) which makes thicknesses in .016 and .019Explanation by mak.church (mod) - role of thickness vs width of roof drip edge flashing
@cora,
There is no meaningful variation in the THICKNESS of drip edge metal. There may be some variations in the WIDTH which perhaps is what you meant. This image shows typical dimensions from AmeriMax cited at Home Depot. Also read this section in DRIP EDGE FLASHING for ROOFS:Roof Drip Edge Flashing at Roof Eaves & Gable Ends
[Click to enlarge any image]
Is F4 or F5 drip edge thick enough to keep squirrels out? - On 2021-06-14 by sandy
Answer by inspectapedia.com.moderator (mod) No, let's do it right.
@sandy,
I need to understand more what's going on with your squirrel problem.
Drip edge on a roof Edge is not normally a location invaded by squirrels nor are its dimensions designed for that purpose.You need to carefully identify the poink of entry of the squirrels into the roof structure and to close those.
See our complete advice on this topic
Can anyone tell me what this is called
On 2020-05-13 by James Calhoun
Answer by (mod) -
James
I can give a better answer you can clarify what you mean by "this" - which part of your photo is the subject of the question?
If the photo is from a home inspection I'm disappointed that your inspector was so vague.The photo I see what looks like some odd green opening at the top of the fascia board which is the vertical front of the soffit or eave or overhang of your roof.
That could be an entry point for animal pests.
Is this installation of Tamko Heritage Laminated Shadowtone Asphalt Shingles without drip-dege OK?
Hi, my home is approximately 1475 sq. ft. My new roof was installed June 11, 2019 with Tamko Heritage Laminated Shadowtone Asphalt Shingles. The shingles have a 3"-4" overhang down into the gutters.
How much more difficult and costly would it be to install drip edge now without damaging the existing asphalt shingles?
Will the shingles readhere?
Can the drip edge be screwed through the front, flat against the fascia board and Aanot fasted to the roof deck?
Should there be open corners where the drip edge is cut and folded?
Do you use the same style drip edge for eaves, rakes and gables? Do you cut notches for the gutter brackets?
Also there is a wide open gap below the decking where I have noticed nesting, how would this be corrected? I hope you can see my photos. Shingle overhang, shingles cut short, drip edge screwed into fascia board, not overlapped in the corner, all sorts of issues :(
Sorry, a lot of questions. Any input you could provide would be greatly appreciated.
Thank you for your time. On 2020-09-14
by Anonymous
-
Typicalliy we add or retrofit drip edge on an existing roof by slipping it up under the lower edge of shingles, lifting shingles just enough to put a few roofing nails or screws through into the roof deck.
Watch out: some of your photos show excessive shingle overhang into the gutters - several inches.
This is not a practice recommended by the manufacturer, and it increases the risk of both future wind damage to the roof and also early break-off of these shingle tabs where they bend over into the gutter, shortening roof life. Check the instructions for Tamco asphalt shingle installation given below.
If you don't have the instructions see
I feel doped that the roofer only installed drip edges on the front gables. He said not enough width on the fascia around the house to properly install (by code) unlike the gables.
Couldn't he of had another solution like using silicone sealant on the top of the drip edge and then a nail on each end? On 2020-06-24 by GIL
Notes by (mod) -
I can't comment on this without seeing the details.
Drip edge is principally functional on the lower roof edges or eaves
Perhaps there was no adequate nailing surface
Can I seal the bottom of a drip edge to stop water from getting into this pop out? On 2020-02-17 by Aaron
Solutions by (mod) -
Better would have been a z-flashing that extended up under and behind that drip edge, but you can Try cleaning the surfaces thoroughly then using a thin bead of silicone sealant
I have a room in the back yard that has a flat roof that I want to put up rain gutters on.
I had the roof redone several years ago and they tarred the roof and tarred the top edge of the metal roof edge down under the tar.
The strip of wood on the outside under the roof edge has rotted and needs to be removed and replaced for the rain gutters.
How do I get the wood out without tearing up the top part from underneath. On 2019-12-14 by Dave
Solution by (mod) -
Dave
I've faced that problem and found it very difficult to separate the tarred drip edge from any adhesion to the roof or to the fascia.
However often you can pry out the fascia and drop it straight down (you might need to hacksaw or cut some nails high up behind the present fascia), then prime and paint the new fascia, then shove it up under the drip edge and nail it into the lower portions of the rafters. (Or use screws for better connections).
Hello, I have a gable roof with Architectural shingles.
The fascia around the home is covered in aluminum flashing, but there is no drip edge as local code does not require it. The flashing itself comes up under the shingle overhang and extends for 3/4 an inch following the overhand away from the roof.
I have found several 6 or 7 in sections at the end of the 4 corners of my roof, where the shingle and decking extend above the reach of the flashing.
So, a small section of decking and fascia board are exposed. I would imagine that this is a bigger deal for wind blown rain and that's my concern. Given the photos, is this something I can fix with a sealant, or extra flashing?
I would hate to have the entire fascia flashing redone if that was not necessary. Note: the exposed areas are a bit weathered, but do not show signs of mold or rot at the moment.
Another photo of my roof with improper "drip egee" from the underside. On 2019-10-14 by Justin

Suggestions by (mod) -
Justin
I think the opening shown in your photo is tough to seal reliably with a sealant while keeping the roof edge neat and clean; you might simply install a white drip edge or if you don't like the drip edge showing past the roof gable edge, a simple L-shaped white aluminum flashing that slips up under the shingles and laps over the gable or fascia.
I agree that re-doing the fascia is probably not justified;
I can't see in the photo: was the roof installed with no protective underlayment? If there's underlayment it needed to come just past the edge of the deck and fascia;
What are the country and city of the home - and thus its weather?Details by (mod) - Tips for making your own flashing bends
You can rent or borrow a brake and bend your own flashing (doing it inch by inch by hand or with a DIY pair of 2x4s as I have tried is hell and looks that way) - or you can find it pre-bent or have a local metal supplier do it for you - it's not costly for what - probably less than 100 ft.
On 2019-10-14 by Justin
thank you, sir. I'll do just that.
On 2019-10-14 by (mod) -
Ah ok that's more clear;
That gap between the gable end covrering and the gutter ought not to be a weather or rain penetration issue as the fascia is wrapped; water blowing in there ought to fall out below the gutter.
Along the gable there's plenty of space to add a white drip edge if you want.You'll need to carefully lift just 2-3 shingles to tack the drip edge to the roof deck or if shingles are nailed too closely to the edge you may need to just nip the drip edge to provide slots around those existing nails. A dab of clear Silicone or white silicone under the drip edge at 3 spots along its 10 foot length can help assure it doesn't blow or fall out.
by Justin
I had begun to do just that with a hand molded L shaped piece of flashing. I didnt know if that was a dumb idea. I live in Northern Arkansas, USA. Moderate climate. Winters rarely getting below 0 but often below freezing. We don't get snow often, but we do get freezing rain and its kin.
One last question, to that end. If I made my own drip edge, and placed it under the shingles. I would anchor the drip edge by "tacking" with good silicon caulk? I fear ripping roofing shingles by trying the nail it down. Also, don't want a roofing inspector down the road to tell me I did it wrong. Ha
by (mod) - tacking down an add-on drip edge with silicone sealant
I have had success doing that as long as the drip edge will at least temporarily stay in the proper position on its own to allow the three or four dabs of silicone to dry
Is it common practice for the roofer to leave the corner shingles on a new roof extending out over the edge?
On 2019-09-11 by Diane
On 2019-09-11 by (mod) -
Not as shown in your photo, Diane.
When a roof shingle is left with several inches of material hanging out past the roof Edge there's a good chance that as the shingle ages and bends it will crack and break, possibly two short up onto the roof deck. It's an incomplete job.
I noticed so that your roofer did not use any drip edge flashing. Some shingle installation instructions permit omission of the flashing but it may be required by local building codes depending on the country and state where you live.
It's of course correct for the shingle Edge to project about 1/2 to 3/4 of an inch past the roof Edge.The exact details of shingle projection are given in the article for which this page is the FAQs - see the link to
DRIP EDGE FLASHING for ROOFSAt Continue reading at the end of this page
Hired contractor to re-roof and re-side old garage with flat wood siding that will be overlaid with new lap vinyl siding.
They did roof first with drip edge adhered on old fascia which is going to be replaced with new fascia when they re-side.
Also, I believe the new fascia on top of new siding will extend out farther than existing.
I expressed my concerns to the contractor, who got very annoyed that I would question how they do their job, and anything they did would have to pass inspection. Was this a valid concern? On 2019-09-11 by Anonymous
Detailed advice by (mod) -
contractor irate when drip edge instalaltion questioned
I'm a little confused by the wording of your question but we don't require that every reader hold a PhD in roof flashings:
The fascia board is the vertical board on the front of the roof eaves or soffit overhang that projects out past the building walls;
The siding will be on the wall below - not shown in our drawing.
Let me take a guess-stab at the question and tell me if I've got your situation right - or attach a photo too.
OPINION: Contractor who's annoyed? Not such a great contractor, right. Success by bullying is hardly a way to build a good reputation. And "pass inspection" is also a bit vague; it's not likely that there will be any building expert inspection at the conclusion of a building re-siding job.Or am I wrong: does your country, city, town require building permits for siding repair and replacement? And for fascia trim installation?
In any case, it would be a good practice, though it's a bit more trouble, if the vertical bend of the drip edge is spaced about 1/8" or more off of the fascia - that helps direct water into the gutter and avoids - where the gutter is secured low on the fascia board as it inevitably will be at its lower end - sending water by capillary action down the fascia and behind the gutter.
If your project is going to include- gutter removal
- installation of a fascia covering of vinyl or aluminum
- re-installation of the gutters and downspouts
then IF the new covering material is shoved up under and behind the too-tight vertical bend of the drip edge, THEN water running down the fascia, behind the gutter, will probably drip harmlessly onto the ground below, leaving perhaps drip stains on the soffit but not causing fascia board rot.
Watch out: however. Sometimes when water runs down a covered fascia it will run by capillary action into the horizontal projection of the soffit or eave where, over time you might get more ugly stains or even rot of the underlying material.
It won't be a catastrophe but all in all a projecting drip edge is in my experience a better installation, though you won't find details like that discussed explicitly in many building codes. At DRIP EDGE FLASHING for ROOFS - topic home - https://inspectapedia.com/roof/Roof_Drip_Edge_Flashing_Specifications.php
You will find drip edge installation instructions from several roofing manufacturers.
An astute building code inspector might argue that since building codes generally require that products be installed according to the manufacturer's instructions, failing to respect those is worse than "not the best practice" - it could also be a technical code violation. It's unfortunate that one has to resort to "it's illegal" statements rather than just saying "here's the best practice, let's do that"Be sure to also read DISPUTE RESOLUTION on ROOF JOB PROBLEMS
Questionable gap in roof edge flashing in Florida: what's "code"?
Hello, my roofer says that this drip edge is OK and passes code, it’s about a half inch away from the vertical wall and when it rains hard water does blow up and into it.
Also worried living in Florida when a real big storm comes wind will catch it because of the large gap and blow it up and hurt the shingles. It appears the gap is caused by the alignment shingle they used as shown in the below picture.
Does anyone have the code for Florida on this and how close the gap should be. Thank you. On 2019-08-06 by Dana
Comments by (mod): a "meets code" answer may be nonsense!
Dana I don't understand the photo or quite what we're looking at - I think I see a drip edge spaced a bit away from a vinyl wrapped fascia.
It is good practice to space the vertical edge of the drip edge about 1/3" away from the fascia just as I THINK is shown in your photo; that encourages water to drip off of the drip edge into the gutter (missing in your photo) rather than to run by capillary action down and back up under the fascia and soffit.
But "meets code" is baloney. There is no precise code detail such as the drip edge spacing gap we're discussing.
Here is FL 905: excerpt:
Provide drip edge at eaves and gables of shingle roofs. Overlap to be a minimum of 3 inches (76 mm).Eave drip edges shall extend 1/2 inch (13 mm) below sheathing and extend back on the roof a minimum of 2 inches (51 mm).
Drip edge at eaves shall be permitted to be installed either over or under the underlayment.
You'll see that the gap or spacing out from the fascia isn't discussed.
Please see details at DRIP EDGE FLASHING for ROOFS - topic homeby Dana
Thank you, this might be a better picture of what I am seeing, but if It is legal then I guess I will just need to find someone to do it so it at least looks right.
This is the upward shot.
by (mod)
That looks very strange - as if there are two metal flashings - looking at theupper roof: a drip edge that looks to me like the underside of drip edge that was supposed to be up under the shingles. But I can't say as we annot see the rest of the metal drip edge material.
IF there is a wider metal flange that is UNDER the roof underlayment at the eaves and ATOP the roof underlayment at the house gable ends then you may be OK; it's possible that the installer added a second flashing shoved up under the drip edge and covering the rest of the fascia in effort to protect the fascia board from water damage.
From a ladder at roof edge if you can safely do so, lift the lower shingles and show me what you see
And do the nailers for the corrugated roofing go on before the moisture barrier? Thanks again.
We are replacing the roof of my shed. We are replacing it with metal corrugated roofing.
My question is does the water barrier go over or under the drip edge flashing. Most everything I have read is about shingled roofs, not metal corrugated roofing. Thanks for your help! On 2019-08-05 by Rose
Answer by (mod) - The underlayment or water barrier goes atop the drip dge.
Thanks for the helpful question, Rose. The underlayment or water barrier goes atop the drip dge.
While I've seen drip edge installed atop the underlayment or moisture barrier on a roof deck, best practice is to nail the drip edge on first, then carry the underlayment or water barrier atop the drip edge roof nailing flange.
That avoids the chance of sending water under the drip edge and thus into the edge of the roof sheathing where it'll make trouble: first mold then rot, and ultimately a possible leak into the interior or into the soffit or fascia of the building.
I've updated one of our sketches to show (in gray) the roof underlayment or ice and water barrier going atop the roof sheating AND atop the drip edge. It doesn't have to go all the way to the very edge of the roof drip edge - within 1/4" is probably ok.
On a composition shingle roof I have installed a 1 by 2 shingle overhang along the table edges and have the comp hanging over 3 quarters of an inch; Do I still need a drip edge ? On 2019-07-08 by Wade
Answer by (mod) - Yes, Most roofing codes and specs expect a drip edge.
Wade.
Most roofing codes and specs expect a drip edge.
Watch out: I have often found that un-supported shingles hanging out past the roof edge fail over time, either by curling over or by simply breaking off - inviting a bit of leakage at the roof edges.
A drip edge also helps direct water away from the fascia and out into the gutter. So you're extending the fascia life too.
I have an Arizona flat roof with drip edge and gutter. The home is 40 years old. The drip edge has curled up/pulled up the full length of the top of the roof creating a small dam that prevents effective water flow over the edge of the roof. Now I have pondingl What has happened and do I need to replace all of the drip edge? On 2019-04-05 by Gary
Reply by (mod) - replace the drip edge
Gary:
You will want to replace or re-install the drip edge, but before tackling that job take a close look under the drip edge to see why its nailing has failed; if the roof decking edge has rotted to let nails pop up you'll want to do a more extensive repair: maybe replacing some decking as well.
If that's not the case it may be possible to nail flat and seal with roof edge EPDM flashing tape.
What to do if roof sheathing stops short of the fascia?
What happens if roof sheathing is 1/2" short of sub-fascia and roofer added drip edge but it just touched sheathing and some places it was short but nailed to rafter?
There isn't any space between drip edge and fascia.
Can I add a 1/4" thick treated board ( like a shim) under drip edge to fascia to make water go out away from fascia?
On 2019-02-08 by Bob wilson
Bob
I've seen roof sheathing that was as much as an inch shy of the inner edge of the fascia board - that was not a problem as long as the drip edge was wide enough that we could nail it to the roof deck.
The drip edge simply covered the gap.
However if the drip edge vertical lip is tight against the fascia board it can be impossible to get water to run into the gutter rather than down the fascia.
In that case I might add a second drip edge atop the original, the new one extending out further into the gutter. There are some tricks to get this to work including
- cutting a "vee" in the drip edge where it encounters shingle nails, so we don't have to disturb the shingles
- using peel and stick flashing tape to secure the add-on drip edge (under the shingles) if there's nothing to nail-to.
Can you attach a photo or sketch so that I can be sure I understand the issue?
In Texas, Bexar county, is it required to have the drip edge installed completely around your entire home? On 2018-10-03 1 by Stacy
Answer by (mod) -
Most roofing codes and specs expect a drip edge. Even where it's not explicitly included you may find drip edge required indirectly by the way building roofing codes are written:
Because you find drip edge detailing in typical asphalt shingle installation instructions from the manufacturer, and because typical building codes require that roofing be installed according to the manufacturer's instructions, that adds up to a "yes".
Your local code inspector is, of course, the final authorityBut the installation of drip edge is a recommended practice and in my OPINION is such a trivial cost compared to the cost, time, and trouble of a roofing job that it's silly to omit it.
My photos at DRIP EDGE FLASHING for ROOFS illustrate how roof runoff will run behind the gutter and down the fascia, soffit, and wall of the building rather than spilling into the gutter where roofing drip edge is omitted and the gutter is even slightly loose.
Should the drip edge wrap around at where two perpendicular gutter meet at a roof ridge? If so how it's done? On 2018-09-12 by Winston
by (mod) -
The drip edge at a wrap-around corner can be handled by two independent, intersecting drip edge pieces,
or
One length can be bent around the corner by snipping the on-roof or horizontal flange, then bending to the 90 degrees needed.
It's trivial to simply snip the metal and bend the drip edge.
If you want to get fancy you can include an extra square of metal flashing on top of and sealed to the snipped-bent-drip edge to add bullet-proofing at the point of the turn - though I've never seen a professional roofer bother with that detail.
Is it ok for a roofer to put new drip edge over the old original drip edge. not mention it and bill the insurance company of the work . On 2018-05-31 by Frank
Answer by (mod) - Yes
Yep. Often a new drip edge is needed in order to get the roof runoff into the gutter or eaves trough, and yes it's fine to install a new one atop the lower or gable edges of an existing roof during a roof-over job.
On a typical residential home the cost of adding new drip edge is absolutely trivial.
...
...
Continue reading at DRIP EDGE FLASHING for ROOFS - topic home, or select a topic from the closely-related articles below, or see the complete ARTICLE INDEX.
Or see these
DRIP EDGE FLASHING for ROOF FAQs at InspectApedia.com - online encyclopedia of building & environmental inspection, testing, diagnosis, repair, & problem prevention advice.
Or see this
Or use the SEARCH BOX found below to Ask a Question or Search InspectApedia
Or see
Or use the SEARCH BOX found below to Ask a Question or Search InspectApedia
Search the InspectApedia website
Need to make a private comment? Email editor@inspectApedia.com. We welcome email with your website content critique, corrections, suggestions or questions. Email is monitored daily but our workload may prevent an immediate reply. For immediate results, we hope you'll first try asking your question using the search box just above.
In addition to any citations in the article above, a full list is available on request.