Building Inspection, Diagnosis & Repair Info

Air check valve on water softener brine tank GE Water Right Water Softener Brine Tank Air Check Valve

Water softener brine tank air check valves:

What problems are caused by a stuck air check valve in water softener brine tanks and how to fix them.

Diagnose & Fix Water Softener Problems:

this article series describes procedures for diagnosing and repairing water softener or water conditioner problems including water conditioner control settings and adjustment or repair, brine tank and brine tank float cleaning and repair, and the proper amount of water softening or conditioning that is needed.

InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers, products, or services discussed at this website.

- Daniel Friedman, Publisher/Editor/Author - See WHO ARE WE?





ADVERTISEMENT





Water Softener Air Check Valve Troubleshooting

Brine tank inteiror with no salt (C) InspectApedia.com David

Many water softener models use a check valve at the top or at the bottom of a brine pick-up tube in the brine tank. This valve closes when the brine level in the tank drops - at the end of a regen cycle - to preven drawing air into the water softener itself.

If your water softener system uses an air check valve

 (sketch at above left example from G.E. [2]) when it should not have one installed (some controls have a built-in air check valve) this can cause the system to stop drawing brine back into the conditioner before the brine tank is empty.

An improperly-installed air check valve can also cause air discharge at plumbing fixtures.

If you find air discharge at plumbing fixtures

after a water softener regen cycle the brine tank tube air check valve itself may be debris-clogged. So if your water softener manual shows an air check valve installed, or if you find one on un-modified original equipment, the valve may need cleaning or replacement.

See WATER SOFTENER CHECK VALVE STUCK where we explain in more detail how a stuck air check valve in the brine tank can cause air discharge at plumbing fixtures after a softener regen cycle.

According to G.E. [2] some water softener models do not use a brine tank check valve:

Water softener air check valve - GE

The regenerant line from the tank connects to the [air check] valve.

Below we illustrate two other air check valves used on some brine level control systems such as GE [2]

Air check valve on water softener brine tank GE Water Right

and Water Right.[1]

Air check valve on brine tank - GE Water Right

Bottom line: until we are sure we have correctly identified the water conditioner model, found its installation and operating manual, and made sure that it has all of the proper parts installed, trying to debug a problem with water level in the brine tank leaves us just guessing.

Also see WATER SOFTENER CHECK VALVE STUCK where we explain that a stuck air check valve in the brine tank can cause air discharge at plumbing fixtures after a softener regen cycle.

Water softener Brine Tank Pick Up Tube Air Check Valve - Fleck at InspectApedia.com

Give your water conditioner manufacturer a call - their contact information is right there in the water conditioner operating manual - and ask about your model and just what brine tank level controls it uses.

In addition to the questions & answers about water softener operating problems presented in the article above, additional Water Softener Diagnosis& Repair Q&As are at WATER SOFTENER TROUBLESHOOTING FAQs-3

and at WATER SOFTENER ADJUSTMENT & CONTROLS

What to Check if the Water Softener Brine Tank is Not Draining

Water Level in the Brine Tank Doesn't Ever Go Down

If the brine tank water level never goes down at all, then see

WATER SOFTENER BACKUP, FLOODING, LEAKS where we describe how to diagnose & fix a water softener that is not draining properly.

Typically the problem is a crimped drain line, a control not operating properly, or a stuck brine control float that is not allowing the regen cycle to function properly.

If the brine tank water level falls but very little or irregularly, it is possible that the float control valve in the brine tank is jammed, sticking or needs cleaning, or the whole tank is due for a cleanout.

See BRINE TANK FLOAT LEVEL ADJUSTMENT - if your water softener brine tank is overflowing the float control may be stuck.

Also see WATER SOFTENER CLEANING & SANITIZING for the steps to solve this problem.

What's the normal liquid level in the brine tank?

Photo of a water softener salt tank ready for cleaningIt's normal to see some water, even over the top of the salt level, in the brine tank.

Without knowing the water softener brand, model, water hardness and salt dose settings, we don't know specifically by quantity, but in general, you should not see water at or close to the very top of the brine tank.

At the end of a normal water softener regeneration cycle water is sent back into the brine tank to dissolve salt so that brine will be ready for the next water softener regen cycle.

The level of water in the tank could be too low or too high either because of improper settings or because of clogging or even leaks in several controls that we discuss beginning

at BRINE TANK DIAGNOSIS & REPAIR - home.

So if the water level in your brine tank is quite high we suspect that the brine tank float level control valve that sets the water level in the tank is not working properly.

Watch out: Not all water softeners use an air check valve.

The BRINE REFILL FLOAT CONTROL VALVE device is a control found in the vertical tube in your brine tank.

More photos of this valve are at WATER SOFTENER CLEANING & SANITIZING.

...





ADVERTISEMENT





...

Continue reading  at BRINE TANK WATER TOO HIGH or select a topic from the closely-related articles below, or see the complete ARTICLE INDEX.

Or see these

Recommended Articles

Suggested citation for this web page

WATER SOFTENER BRINE TANK AIR CHECK VALVE at InspectApedia.com - online encyclopedia of building & environmental inspection, testing, diagnosis, repair, & problem prevention advice.

Or see this

INDEX to RELATED ARTICLES: ARTICLE INDEX to WATER TREATMENT SYSTEMS

Or use the SEARCH BOX found below to Ask a Question or Search InspectApedia

Ask a Question or Search InspectApedia

Share this article:

Search the InspectApedia website

Need to make a private comment? Email editor@inspectApedia.com. We welcome email with your website content critique, corrections, suggestions or questions. Email is monitored daily but our workload may prevent an immediate reply. For immediate results, we hope you'll first try asking your question using the search box just above.

Citations & Reviewers

In addition to any citations in the article above, a full list is available on request.

  • [1] North Dakota Standards for Water Softeners, North Dakota General Authority Law, Chapter 62-04-08, Water Softener Units http://www.legis.nd.gov/information/acdata/pdf/62-04-08.pdf. "The objective of this chapter is to provide a standard of quality, capacity, and performance for water softener units. Water softener performance is to be based upon referee tests procedures described in section 62-04-08-09."
  • [2] Culligan Mark 10 Water Softener 1994-1998 Installation and Operating Instructions (covering models manufactured after 1995) (1-96) 01881948.pdf available from www.culligan.com
  • [3] Water Softeners, CMHC, Canadian Mortgage and Housing Corporation, cmhc-schl.gc.ca/en/co/maho/wawa/wawa_005.cfm - October 2008. Canada Mortgage and Housing Corporation acknowledges the contribution of Health Canada to the development of this document. For further questions regarding water treatment and water quality, contact Health Canada at watereau@hc-sc.gc.ca or call 613-957-2991 or 1-866-225-0709.
  • [4] "Commercial Water Softener Installation and Operating Instructions", IBC Filtration & Water Treatment Products (Australia) for commercial, industrial and residential application www.ibcwater.com.au (07) 3219 2233
  • [5] "Non electric water softener, Installation and Operating Instructions", IBC Filtration & Water Treatment Products (Australia), op.cit.
  • [6] "Water Softener Twin Tank Installation and Operating Instructions", IBC Filtration & Water Treatment Products (Australia), op.cit.
  • [8] Thanks to reader Gail Sanchez for discussing water softener backups and floods after an electrical outage - August 2010
  • [9] Water Right, 1900 Prospect Court Appleton, Wisconsin 54914, Tel: 920-739-9401, Website: http://www.water-right.com/ and their water softener manuals are available online at http://www.water-right.com/library/literature/literature_manuals.html
  • [10] General Electric Corporation, Operation Manual, 740/760 [Water Conditioner or Water Softener] Control, 255 and Performa Series Valves, (268, 268 FA), General Electric Corp. 2007
  • [11] Ecodyne Industrial, 1270 Frontenac Road, Naperville, IL 60563 Tel: 1 800-228-9326 (USA Only) Tel: +1 630-961-5043 Fax: 1 800-671-8846, Customer Service: 1 800-228-9326, Email: customers@ecodyneind.com, Website: http://www.ecodyneind.com/
  • In addition to citations & references found in this article, see the research citations given at the end of the related articles found at our suggested

    CONTINUE READING or RECOMMENDED ARTICLES.


ADVERTISEMENT